background image

VALLOX DIGIT SE / VKL

°

C

°

C

Temperature of supply air going

from the unit to the dwelling

Temperature of outdoor air coming to the unit

-20

22

°

C

-10

0

+10

0

10

20

30

Temperature of outdoor air coming to the unit

1

2

3

4

HR cell anti-freezing starts to function

+20

© VALLOX • We reserve the right to make changes without prior notification.

POST-HEATING

10

EXAMPLE: Outdoor air temperature rise in the heat recoverycell
with an electric and water radiator

Curve 1

Supply air temperature without post-heating = only heat
recovery.

Curve 2

Supply air temperature controlled by the thermostat of the
electric radiator, adjustment setting 23 

°

C (air flow less than 75

l/s).

Curve 3

Supply air temperature with water radiator, water +35 

°

C and

water flow 0.05 dm

3

/s. Air flow 50 l/s. Valve fully open.

Because heat release of water radiator is dependent on many
factors, the curves are approximate. Glycol decreases radiator
power by circa 10...20% depending on mixture.

Curve 4

A 1000 W post-heating radiator can heat e.g. 100 l/s air by
circa 8 

°

C at most.

Post heating radiator

Electric radiator 1000W, or water radiator (VKL model)

Post-heating in DIGIT SE VKL operates in a similar fashion to an electric radiator but the actuator

is an electric thermostat valve, which is open when dead. The water radiator in the VKL model

also has an automatic anti-freezing function, which stops all functions when supply air temperature

is below 7

°

C and outdoor temperature is below 0 

°

C. At the same time, the valve remains

open and the self-actuated dampers of the fans close. (The control panel shows the fault message

FREEZING ALERT.) The unit restarts and the dampers open as soon as supply air temperature

exceeds 10 

°

C.

In the VKL model it is also possible to bring non-freezing heat transfer fluid into the post-heating

radiator. In addition, the radiator can be provided with a separate non-freezing heating circuit.

It can be built for example with the heat exchanger (V) supplied with the unit. See the mounting

examples in the technical specification in the section describing water-circulating radiator

connections.

Post-heating regulation

There are two ways to control post-heating.

1.   Supply air constant temperature control

• In DIGIT SE, post-heating control is proportional: when the chosen temperature exceeds

supply air temperature by more than 2.5

°

C, the radiator is on 100% of the time; when

the temperature differential gets smaller, the on time of the radiator is reduced

automatically in two-minute sequences. The temperature range is 10…30

°

C.

• The heating radiator is on when the ( ) sign is displayed in the main display of the

control panel.

• The main display of the control panel shows the temperature of supply air.
• Temperature control is only active when post-heating has been switched on.

2.  Supply air cascade control

• Supply air temperature control can be replaced with cascade control.
• Cascade control changes the mode of regulating the post-heating radiator: the

temperature of air blown to the ventilation zone is controlled on the basis of extract air.

• The program aims at keeping supply air temperature at the value that depends on the

difference between extract air and the setpoint as follows: if extract air is hotter than the

setpoint, the temperature of supply air is lower than the setpoint by the same amount. If

extract air is cooler than the setpoint, supply air is hotter by the same amount. For

instance, if indoor air temperature is 25

°

C and the setpoint is 24

°

C, the aim is to blow

23

°

C air to the ventilation zone. If temperature in the ventilation zone is 24

°

C and the

setpoint is 25

°

C, the aim is to blow 26

°

C air to the ventilation zone.

• The aim is to permanently keep the temperature of air blown to the ventilation zone

within the range +10...+30

°

C.

• Cascade control can be chosen on the control panel, and it is active when post-heating

has been switched on.

• The heating radiator is on when the ( ) sign is displayed in the main display of the

control panel.

Heat exchanger (V)

Water/liquid-
radiator
(VKL model)

Electric
radiator

Summary of Contents for DIGIT SE L

Page 1: ...e control panel Timing of fan speeds and post heating control at the control panel Week clock control at the control panel Ability to control from several places max 3 control panels LON remote monito...

Page 2: ...ting radiator electricity 1000W or water Heat recovery cell Outdoor air filter EU7 Outdoor and extract air prefilter EU3 Summer winter damper Duct connections duct inside 160mm extension joints 1 2 3...

Page 3: ...IR FLOW Sound power level from the ventilation unit to extract air ducts by octave band Lw dB ADJUSTMENT POSITION AIR FLOW Medium frequency of the octave band Hz ADJUSTMENT POSITION AIR FLOWS supply e...

Page 4: ...off When the indicator is lit the unit is on Carbon dioxide adjustment With this button you set carbon dioxide adjustment on and off When the indicator is lit the adjustment is on Humidity adjustment...

Page 5: ...T TERMINAL BLOCK HUMIDITY SENSORS When mounting two or more humidity sensors connect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the re...

Page 6: ...ide DIGIT SE 130 E VALLOX SILENCER UNIT EXTRACT AIR SUPPLY AIR 10 m2 sound absorption ROOM SOUND LEVEL MEASUREMENT Expected sound levels db A in a room with a VALLOX silencer 10 m2 sound absorption Ex...

Page 7: ...PRESSURE Pa 65 69 72 74 76 78 78 51 59 61 64 66 68 69 33 39 44 47 50 52 54 24 28 32 36 38 41 43 19 22 24 26 27 28 31 0 0 0 7 10 15 19 0 0 0 13 0 65 70 72 74 77 78 79 40 45 48 50 53 54 55 Extract air...

Page 8: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification INTERNAL ELECTRICAL DIAGRAM 8...

Page 9: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification 9 EXTERNAL WIRING DIAGRAM...

Page 10: ...mple with the heat exchanger V supplied with the unit See the mounting examples in the technical specification in the section describing water circulating radiator connections Post heating regulation...

Page 11: ...is switched on at a temperature higher than the stopping temperature factory setting 6 C If preheating cannot keep exhaust air temperature warmer than the stopping temperature the supply air fan stop...

Page 12: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification 12 CONTROL DIAGRAM DIGIT SE electric radiator...

Page 13: ...also choose automatic search for thehumidity content threshold on the control panel H One or more modes of control may be used simultaneously the mode demanding boosting is the dominant one Fan speed...

Page 14: ...Ljp TS3 TS4 EU 3 EU 7 PF SOUND ABSORBER DISTRIBUTION PANEL REMOTE MONITORING CENTER OF THE PROPERTY ALARM RUNNING MODE CONTROL MEASUREMENT REGULATION INTERNAL ELECTRICAL AND CONTROL CONNECTIONS OF TH...

Page 15: ...operation ofthe damper motor FG on the basis of measuring results given by theoutdoor sensor TE3 and the extract air temperature sensor TE4 The aim isto get as cool supply air to the ventilation zone...

Page 16: ...becau se of sound conduction Condensing water A water seal is included in the delivery Through the piping connected to this water seal the water condensing from ex tract air is led to a floor drain an...

Reviews: