background image

12

CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell is clean roughly once a year, 

or whenever the filters are being replaced. Clean by washing 

as required.
To check and clean the heat recovery cell:

1.   Disconnect the ventilation unit from the mains electricity 

supply.

2.   Open door of the Vallox ventilation unit by undoing the 

finger screws.

3.   Lift the door off. 

CAUTION

The door is heavy.

4.   Remove the sealing strip (E) above the HR cell in the 

direction of the arrow.

5.  Remove the extract air filter (C).

6.   Lift and pull the HR cell (D) out of the unit.

7.   If the cell is dirty, clean it by immersing it in warm water, 

to which a small amount of a mild detergent has been 

added.

8.   Rinse the cell clean with a water spray. Do not use a high-

pressure cleaner.

9.   When all the water has drained from between the layers, 

reassemble the ventilation unit as follows:

10.   Ensure that the lower support (F) is in place between the 

knobs at the bottom of the unit.

11.  Push the heat recovery cell in place.

12.  Push the sealing strip (E) in place so that the strip is 

supported by the corner bracket (G) at the rear. 

13.  Install the extract air filter (C) in place.

14.   Close the door. Ensure that the safety switch catch of the 

door is touching the safety switch.

15.  Plug the ventilation unit back into the mains. 

 

The heat recovery cell has now been checked and 

cleaned.

MAINTENANCE

IMPORTANT

If the unit has an 

enthalpy cell, it must 

not be washed. Only 

aluminium or plastic 

cells can be washed.

IMPORTANT

Handle the cell 

carefully! For example, 

do not lift the cell by the 

layers. The cell layers 

are very thin and easily 

damaged.

CONDENSING WATER

In the heating season, the extract air humidity condenses to 

water. In new buildings, condensation runoff can form rapidly. 

Condensed water must be able to freely leave the unit. 

At some time before the heating season begins (e.g. during 

autumn maintenance), check that the siphon or the condensing 

water outlet in the bottom pool are not clogged. To check this, 

pour some water into the pool. Clean as required.

NOTE

Some condensing water 

may have accumulated 

in the bottom pool 

of the unit; this is 

normal and requires no 

corrective action. 

WARNING

Water must at all times 

be kept out of the 

electrical system.

D

C

G

E

F

Summary of Contents for C3741

Page 1: ...Manual Model Vallox 101 MV Type C3741 Document D5331 Valid from 05 05 2021 Updated 03 05 2021 Ventilation unit MANUAL...

Page 2: ...required by the alternative Vallox Silent Klick siphon installation method elbow 9 Measuring and adjusting the air flows of the ventilation unit 9 Dimensions and duct outlets 10 MAINTENANCE 11 Before...

Page 3: ...al installations and connections must be carried out only by an electrician and in compliance with local regulations GUARANTEE The guarantee and liability exclude damage resulting from Inappropriate u...

Page 4: ...result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor...

Page 5: ...ws for controlling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation...

Page 6: ...figure MAIN PARTS Post heatingresistor in the supply air duct 8 Safety switch 9 Internal carbon dioxide and humidity sensor 10 Control panel 11 Carbon dioxide sensor optional 12 Humidity sensor option...

Page 7: ...p edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling Alternatively a concealed mounting method can be used in which case the ceiling can be 30 mm below...

Page 8: ...x can be accessed The distance between the service door and the ceiling mounting plate must be around 500 mm Alternatively the cables can be fed between the ceiling mounting plate and the ventilation...

Page 9: ...ing tubes These can be inserted in the ducts to allow for easier ventilation adjustment NOTE The Vallox Silent Klick siphon package is delivered with the unit Installation instructions for the siphon...

Page 10: ...ating resistor in the supply air duct 9 Safety switch 10 Internal humidity and carbon dioxide sensor Dimensions and duct outlets Dimensions Duct outlets R model Inner diameter of the female collar 125...

Page 11: ...very cell clean The filter replacement interval depends on the ambient particle concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To...

Page 12: ...rip E in place so that the strip is supported by the corner bracket G at the rear 13 Install the extract air filter C in place 14 Close the door Ensure that the safety switch catch of the door is touc...

Page 13: ...the fans J 3 screws per fan Undo the mounting screws K 3 screws of the air flow control grille of the extract air fan and remove the grille 8 Remove the fan from the unit by pulling it forward and by...

Page 14: ...m s 15 24 34 42 51 62 69 77 83 23 31 41 50 60 70 78 86 92 Air flow m h 54 86 122 151 184 223 248 277 299 83 112 148 180 216 252 281 310 331 Medium frequency of the octave band Hz 63 62 64 69 73 77 82...

Page 15: ...elay output T Supply air fan P Extract air fan M Damper motor TK Safety switch AHS Post heating control RH Internal humidity sensor RH CO2 Internal humidity and carbon dioxide sensor R1 Post heating r...

Page 16: ...2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potential free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV rad...

Page 17: ...rd MLV control External temperature sensor NTC 4K7 MB_A External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A s...

Page 18: ...ature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Manual In summer the duct radiator will turn on when the outdoor temperature rises ab...

Page 19: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Page 20: ...24 MyVallox Control panel 949033 5 Coarse and fine filter for supply air 978225 15 Mounting screw of the door 990712 25 MyVallox humidity sensor optional 946149 6 HR cell aluminium HR cell enthalpy 93...

Page 21: ...CONFORMITY CERTIFICATES...

Page 22: ...22...

Page 23: ...23 Vallox Oy All rights reserved...

Page 24: ...D5331 03 05 2021FIN 03 05 2021ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND...

Reviews: