NOTE:

 If the duct 

radiator is used in 

the supply air duct, it 

can only be used for 

cooling. 

NOTE:

 When used to 

control the outdoor air 

duct radiator, the exter-

nal NTC sensor is ins-

talled in the outdoor air 

duct before the radiator. 

When used to control 

the supply air duct ra-

diator, the external NTC 

sensor is installed after 

the radiator.

NOTE:

When selecting the 

relay (C), take account 

of the maximum 

allowed combined 

power supply (6W) of 

the circuit board in the 

external MV electrical 

box, if the relay power 

supply comes from the 

circuit board’s +24V 

connector.

NOTE:

Due to the risk of humi-

dity damage, in a duct 

that has not been insu-

lated for condensation 

the supply air tempera-

ture must not fall below 

+16 … 20 °C.

DUCT RADIATOR OPERATION

Always follow first and foremost the connection diagram 

provided by the HVAC designer or heat pump manufacturer. 

Also read the duct radiator manual. 
The accompanying figure shows an example of the 

arrangement for connecting the heating/cooling radiator unit 

to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit 

return pipe. Direct the fluid returning from the radiator unit to 

the heat collection circuit return pipe. If you know that there 

is a large loss of internal pressure inside the heat pump, the 

heat pump should be bypassed. If this is done, the fluid circuit 

will come into operation when the heat pump comes to a halt. 

When this happens the pressure loss in the one-way bypass 

valve Y2 must be lower than the pressure loss in the heat 

pump.

Heating:

 The pump starts when the outdoor air temperature 

drops below the winter limit value set at the factory (-5 °C).

Cooling 

The supply air setpoint value for the active mode 

(for example, At home) controls the pump start-up. The pump 

starts when the supply air setting is below the temperature of 

the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air 

duct and the outdoor air duct. If the radiator is installed in 

the outdoor air duct, it can be used for both preheating and 

cooling. If the radiator is installed in the supply air duct, it can 

be used for heating or for cooling only. 

The duct radiator can be set to function either automatically 

or manually. 

•  Automatic

 - In summer, the supply air temperature will 

be maintained at the level specified in the temperature 

setting. In winter, the duct radiator will turn on, when the 

outdoor temperature falls below the winter setting.

•  Manual

 - In summer, the duct radiator will turn on, when 

the outdoor temperature rises above the summer setting. 

In winter, the duct radiator will turn on, when the outdoor 

temperature falls below the winter setting.

To prevent the risk of condensation in the supply air duct, you 

can set the adjustment of the supply air limit to automatic or 

manual. 

•  Automatic

 - The supply air limit is adjusted automatically 

based on the dew point of the extract air. When the supply 

air temperature falls too low, the duct radiator will turn off.  

•  Manual

 - The supply air limit can be set manually. When 

the supply air temperature falls down to the set value, the 

duct radiator will turn off.

If an external sensor is in use, it is selected from the settings of 

the external sensor whether it is used to control the outdoor air 

duct radiator or the supply air duct radiator. The temperature of 

the external sensor can be read from the service menu: 

menu >  

service menu > 

unit information page 5 ”

External sensor

”.

Summary of Contents for A3609

Page 1: ...l Vallox TSK Multi 50 MV Vallox TSK Multi 50 MV EH Vallox TSK Multi 80 MV Vallox TSK Multi 80 MV EH Type A3609 A3609 1 C3608 C3608 1 Document D5321 Valid from 7 3 2022 Updated 20 06 2022 Ventilation u...

Page 2: ...nd space required for installation of the Vallox Silent Klick siphon 8 MAINTENANCE 9 Before beginning maintenance work 9 Changing the filters 9 Cleaning the heat recovery cell 10 Condensing water 10 C...

Page 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Page 4: ...result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor o...

Page 5: ...automatically by using the optional carbon dioxide humidity or VOC air quality sensor When these are used ventilation remains optimal even when the dwelling is unoccupied Each user can use the week cl...

Page 6: ...act air 7 Bypass damper of the HR cell 8 R model in the figure MAIN PARTS Vallox TSK Multi 50 MV and Vallox TSK Multi 80 MV Safety switch 9 Control panel 10 Internal humidity sensor 11 Internal carbon...

Page 7: ...ront of the unit for servicing purposes The service space in front of Vallox TSK Multi 50 MV must be at least 530 mm The service space in front of Vallox TSK Multi 80 MV must be at least 600 mm NOTE T...

Page 8: ...239 1 935 935 547 547 L model R model R model 1 Outdoor air to the unit 2 Supply air from the unit to the apartment 3 Extract air from the apartment to the unit 4 Exhaust air flowing outdoors from the...

Page 9: ...and dust particles out of the supply air Coarse filter for extract air filters the extract air and keeps the heat recovery cell clean To replace the filters 1 Disconnect the ventilation unit from the...

Page 10: ...een added 10 Rinse the cell clean with a water spray Do not use a high pressure cleaner 11 When all the water has drained from between the layers reassemble the ventilation unit in the reverse order 1...

Page 11: ...2 Unfasten the four screws to open the door of the unit 3 Lift the door off CAUTION The door is heavy 4 Remove the extract air filter C the cell top bracket E and the heat recovery cell D as described...

Page 12: ...oving the supply air fan Figure 1 6 Remove the connector package from the wall 7 Separate the connectors from each other 8 Tilt the fan to the left and turn 90 9 Tilt the fan forward to pull it out of...

Page 13: ...t air supply air TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS AIR FLOWS AND SOUND VALUES Pressure loss in ducts Total pressure Pa Volume flow rate dm3 s TECHNICAL SPECIFICATIONS Product title Val...

Page 14: ...level coming through the envelope of the unit in the room in which it is installed 10m sound absorption Adjustment position Air flows supply extract Adjustment position 10 20 30 40 50 60 70 80 100 Air...

Page 15: ...0 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100 Air flow dm s 15 20 32 37 47 57 62 65 17 22 36 42 51 60 66 67 Medium frequency of the octave band Hz 63 60 67 68 72 73 79 79 78 54 58 59 63 66 78...

Page 16: ...TSK Multi 50 MV EH Vallox TSK Multi 80 MV EH EHX R2 Additional heating resistor with 90 C and 130 C overheating protection Vallox TSK Multi 80 MV EHX BK Black BU Blue BN Brown WT White GY Grey YE Yel...

Page 17: ...ICAL CONNECTION Analog input two different functions Potential free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV radiator Plug...

Page 18: ...winter limit value set at the factory 5 C Cooling The supply air setpoint value for the active mode for example At home controls the pump start up The pump starts when the supply air setting is below...

Page 19: ...alve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example Danfoss 032U161431 K Condensing water tube Not included in the delivery...

Page 20: ...External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A signal RS_B Local hardware Modbus B signal NTC External t...

Page 21: ...R model Vallox TSK Multi 80 MV 942210 14 b Additional heating resistor L model Vallox TSK Multi 80 MV 942211 15 Side sealing strip of the heat recovery cell Vallox TSK Multi 50 MV 3356300 15 Side sea...

Page 22: ...CONFORMITY CERTIFICATES...

Page 23: ......

Page 24: ...www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND D5321 20 06 2022FIN 20 06 2022ENG PDF...

Reviews: