14

TROUBLESHOOTING

Outdoor air coming to
the dwelling is cold.

SYMPTOM

REASON

• Air cools down in the attic ducts.

• The heat recovery cell is frozen, which is

why extract air cannot heat outdoor air.

• The post-heating radiator does not work.

• The extract air filter or cell is clogged.

• The initial adjustment of ventilation has not

been done.

1

• Check the insulation of the attic ducts.

• If the heat recovery cell is frozen, check the setpoint for

freeze protection. The setpoint for freeze protection can be
raised by 1 or 2˚C, or the sensor can be bent closer to the
cell, in which case the supply air fan stops earlier (see the
instructions for using the control panel, section 3.3.20).
Thaw the cell before closing the door.

• Check that the filters and the heat recovery cell are clean.

Supply air fan keeps
stopping.

• The stopping of the supply air filter is acti-

ve.

NOTE!
If you decrease the setpoint too much, the cell
may freeze. Compare with list item 1.

2

• The fan stops more rarely and the efficiency of the heat

recovery cell gets better when the setpoint is decreased by
1 or 2˚C. (See the instructions for using the control panel,
section 3.3.20.)

Supply air fan stops and
starts too frequently.

• The difference between the stopping and

starting temperatures is too small.

3

• Raise the difference between the stopping and starting tem-

peratures by 1 or 2˚C. It extends the period between stop-
ping and starting. (See the instructions for using the control
panel, section 3.3.19.)

The maintenance reminder
symbol  ( ) is displayed and
the unit operates otherwise
normally.

• The maintenance reminder lights up the

service reminder symbol in the main
display of the control panel at an interval
of approximately 4 months (factory set-
ting).

• You may change the interval (see the

instructions for using the control panel, sec-
tion 3.3.18).

4

• Check the cleanliness of the filters and the unit. If needed,

clean or replace the filters. Also check the external grille.

• Acknowledge the maintenance reminder symbol to make it

disappear. (See the instructions for using the control panel,
section 3.3.7.)

"Exh air sensor faulty"
message is displayed and
the unit is stopped.

• There is a fault in the freezing protection

sensor.

5

• Contact a maintenance company. The sensor installation

must be checked and if necessary the sensor replaced.

"Inp. air sensor faulty"
message is displayed and the
unit is stopped.

• There is a fault in the supply air sensor.

6

• Contact a maintenance company. The sensor installation

must be checked and if necessary the sensor replaced.

"In air sensor faulty" message
is displayed and the unit is
stopped.

7

• Contact a maintenance company. The sensor installation

must be checked and if necessary the sensor replaced.

"Out air sensor faulty"
message is displayed and the
unit is stopped.

• There is a fault in the outdoor air sensor.

8

• Contact a maintenance company. The sensor installation

must be checked and if necessary the sensor replaced.

DO THIS

• There is a fault in the extract air sensor.

Summary of Contents for 90 SE L

Page 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Page 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Page 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Page 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Page 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Page 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Page 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Page 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Page 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Page 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Page 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Page 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Page 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Page 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Page 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Page 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Page 17: ......

Reviews: