VALLOX 90 SE
MAINTENANCE INSTRUCTIONS
13
4.3. Fans
Check the cleanliness of the fans in connection with the maintenance of
the filter and heat recovery cell. Clean the fans if necessary. You can
remove the fans from the unit before cleaning them.
The fan blades can be cleaned with compressed air or with a brush. Do
not remove or move the balancing pieces on the fan blade.
Removing the supply air fan (A)
Before removing the supply air filter, you have to remove the F7 fine filter
(C) and the protective sleeve (D) of the preheating radiator. The F7 fine
filter can be removed by pulling, and the protective sleeve of the preheating
radiator is fixed with four screws. The fan is attached to the fixing plate
with a butterfly nut. Loosen the butterfly nuts and lift the fan out. Finally
disconnect the quick coupling of the fan conductor.
Removing the extract air fan (B)
The fan is attached to the fixing plate with a butterfly nut. Loosen the
butterfly nuts and lift the fan out. Finally disconnect the quick coupling
of the fan conductor.
If you use water in cleaning the unit or its parts, do not let it flow to the
electrical parts.
4.4. Condensing
water
During the heating season, humidity of extract air condenses to water.
Water formation may be abundant in new buildings or if ventilation is
low compared to the humidity build-up caused by the residents. Condensing
water needs to flow out from the ventilation unit without hindrance. In
connection with maintenance, e.g. in autumn before the beginning of the
heating season, make sure that the condensing water outlet (L) in the
bottom tank is not clogged. You may check it by pouring a little water in
the tank. Clean if necessary.
Do not let water flow to the electrical parts.
L
A
C
B
D
L
170
150