Vallox 75 Instructions Manual Download Page 8

Parts list VALLOX 75 VKL / VALLOX 95 VKL

Code Name

Technical details

Standard /

option

Description of operation for VALLOX 75/95VKL

Control of operation

Power supply to the unit is controlled with the 0/1 switch in the
distribution panel. There is also a maintenance / safety switch 

SS

inside the unit. It stops power supply when the door of the unit is
opened.

Fan speed adjustment

The operation of the fans 

S

 and 

E

 of the unit is controlled with a

separate control centre 

HS

, located in the ventilation zone, or with

a cooker hood.

Supply air temperature

Self-actuated control valve 

V1

 controls the operation of the postheating

radiator 

R

, maintaining the temperature of supply air going out from

the unit at the setpoint value.

Heat recovery bypass

Summer-time bypass of the heat recovery cell 

HR

 is done manually

by turning the 

HR

 damper 

H

 in the bypass position for the summer.

Heat recovery defrosting

The defrost thermostat 

T1

 of the 

HR

 cell keeps stopping the supply air

fan 

S

, thereby preventing the risk of the freezing in the 

HR

 cell. The

fan starts automatically as soon as the risk of freezing has passed.
The threshold temperature of the risk of freezing can be set at the
thermostat 

T1

.

Water radiator defrosting

The defrost thermostat 

T2

 of the post-heating radiator 

R

 stops the unit

when the temperature of water radiator goes below the threshold
value, preventing the risk of freezing in the water radiator. This also
causes self-actuated one-way dampers 

SP

 to close, preventing the

flow of outdoor air to the unit. The unit starts automatically as soon
as the risk of freezing has passed. The threshold temperature of
freezing risk can be set at thermostat 

T2

.

VALLOX 75/95

8

CONTROL DIAGRAM AND DESCRIPTION OF OPERATION FOR VALLOX 75/95 VKL 

WATER RADIATOR

G3  Filter, extract air and supply air 

G3 

Standard

F7 

Fine filter, supply air at least F7 

F7 

Standard

HR bypass damper 

Manual 

Standard

HS 

Speed adjustment 

Separate control centre 

Option

or cooker hood

Post-heating radiator 

Water radiator 0.5 kW 

Standard

HR  Heat recovery cell 

Efficiency approx. 60% 

Standard

Supply air fan / VALLOX 75 

105 W, 65 l/s (50 Pa) 

Standard

Supply air fan / VALLOX 95 

180 W, 80 l/s (75 Pa)

Standard

SS 

Service switch 

Door switch 

Standard

T1 Regulating 

thermostat 

0…40 

°

C Standard

Extract air fan / VALLOX 75 

105 W, 75 l/s (80 Pa) 

Standard

Extract air fan / VALLOX 95 

180 W, 95 l/s (100 Pa) 

Standard

V1 

Control valve 

Self-ac 5…21 

°

C  Standard

T2 

Water radiator defrost thermostat  Factory s5 

°

C Standard

SP 

One-way damper, 2 pcs 

Air flow operated 

Standard

G3

G3

SILENCER

SILENCER

H

F7

E

S

R

HEAT RECOVERYCELL

(HR)

SP

M

M

SP

POST-HEATING

RADIATOR

DISTRIBUTION
PANEL

10A

230 V

VALLOX 95/75

INTERNAL ELECTRICAL AND CONTROL CONNECTIONS

FAN SPEED ADJUSTMENTSEPARATE
COOKER HOOD OR
CONTROL CENTRE

VENTILATION ZONE

SS

T1

T2

V1

Ljm

Ljp

HS

Summary of Contents for 75

Page 1: ...Handy ceiling mounting plate for simple and quick mounting Service switch as standard All models are available as R and L models Fans 105 W 65 dm3 s 90 Pa 105 W 75 dm3 s 130 Pa 180 W 85 dm3 s 75 Pa 1...

Page 2: ...1 VALLOX 75 95 DIMENSIONS PERFORMANCE 2 2 Pressure loss in ducts Total pressure SFP Specific Fan Power guideline value 2 5 kw m3 s SFP Input power total W Air flow max dm3 s Dimensions and duct outlet...

Page 3: ...19 31 34 40 43 47 19 25 33 38 43 62 68 75 78 86 82 86 37 43 51 54 60 60 64 41 56 65 65 71 72 76 41 48 55 57 63 67 69 30 34 42 45 50 54 58 24 28 34 36 40 43 46 15 24 34 37 40 42 44 17 27 30 35 38 43 1...

Page 4: ...prevented and heat recovery bypass is activated REMOTE MONITORING CENTRE VALLOX 1993 A ON OFF switch Operating status data to remote monitoring Transformer with eight voltage options of which two one...

Page 5: ...unit starts automatically as soon as the risk of freezing has passed The threshold temperature of the risk of freezing can be set at the thermostat J of the water radiator Though VALLOX 75 95 VKL unit...

Page 6: ...front edge of the collar When detaching the damper take the same steps in the opposite order Self actuated one way dampers are only used in VKL model units B C Detaching of thermostat sensor from and...

Page 7: ...iator The overheat protector T2 of the radiator R is triggered and power supply to the heating unit is stopped if the temperature of the thermostat exceeds 80 C The overheat protector is reset manuall...

Page 8: ...ture of water radiator goes below the threshold value preventing the risk of freezing in the water radiator This also causes self actuated one way dampers SP to close preventing the flow of outdoor ai...

Page 9: ...230 V 160 V 120 V 70 V L N 90 V 135 V 180 V 1 5 X 1 5 S 2 3 PL 11 L 1 2 3 230 V 160 V 120 V 70 V L L 2 N 90 V 135 V 4 L2 180 V 1 2 3 PL 11 0 4 N L3 N VALLOX 75 95 3510 external electrical connection w...

Page 10: ...Wire colours m black r brown s blue T2 F1 F2 K TK m s s s s s m m m m m L N N 1 L T1 m m K r r N L m 1 m s L 1 s V W 2 3 3 X 1 5 S L 10 A N N 1 L N L 1 L L N L 3 2 N INTERNAL ELECTRICAL CONNECTION OF...

Page 11: ...NITORING VALLOX 75 95 control through remote monitoring with control centre 1993 YK 2A VALLOX 1993A YK 2A VALLOX 75 95 REMOTE MONITORING CONTROL CENTRE DISTRIBUTION PANEL OPERATING STATUS DATA OPERATI...

Page 12: ...e approximately 40 kg The ceiling mounting plate has to be fixed horizontally in order to ensure that the unit will be straight Installation Lift the unit straight upwards till the locking wings on th...

Page 13: ...s wall mounting accessories with the exception of screws The unit has to be mounted horizontally and vertically straight Wall construction Pay attention to the wall construction when mounting the unit...

Page 14: ...nted The delivery does not include a water seal nor the pipe and its components Examples of condensing water connections Yli 600 n 100 n 100 Suction air COLLECTOR condensing water goes to the cellar W...

Reviews: