Parts list VALLOX 75 VKL / VALLOX 95 VKL

Code Name

Technical details

Standard /

option

© VALLOX • We reserve the right to make changes without prior notification.

Description of operation for VALLOX 75/95VKL

Control of operation

Power supply to the unit is controlled with the 0/1 switch in the
distribution panel. There is also a maintenance / safety switch 

SS

inside the unit. It stops power supply when the door of the unit is
opened.

Fan speed adjustment

The operation of the fans 

S

 and 

E

 of the unit is controlled with a

separate control centre 

HS

, located in the ventilation zone, or with

a cooker hood.

Supply air temperature

Self-actuated control valve 

V1

 controls the operation of the postheating

radiator 

R

, maintaining the temperature of supply air going out from

the unit at the setpoint value.

Heat recovery bypass

Summer-time bypass of the heat recovery cell 

HR

 is done manually

by turning the 

HR

 damper 

H

 in the bypass position for the summer.

Heat recovery defrosting

The defrost thermostat 

T1

 of the 

HR

 cell keeps stopping the supply air

fan 

S

, thereby preventing the risk of the freezing in the 

HR

 cell. The

fan starts automatically as soon as the risk of freezing has passed.
The threshold temperature of the risk of freezing can be set at the
thermostat 

T1

.

Water radiator defrosting

The defrost thermostat 

T2

 of the post-heating radiator 

R

 stops the unit

when the temperature of water radiator goes below the threshold
value, preventing the risk of freezing in the water radiator. This also
causes self-actuated one-way dampers 

SP

 to close, preventing the

flow of outdoor air to the unit. The unit starts automatically as soon
as the risk of freezing has passed. The threshold temperature of
freezing risk can be set at thermostat 

T2

.

VALLOX 75/95 SILENT

9

CONTROL DIAGRAM AND DESCRIPTION OF OPERATION FOR VALLOX 75/95 VKL 

WATER RADIATOR

G3  Filter, extract air and supply air 

G3 

Standard

F7 

Fine filter, supply air at least F7 

F7 

Standard

HR bypass damper 

Manual 

Standard

HS 

Speed adjustment 

Separate control centre 

Option

or cooker hood

Post-heating radiator 

Water radiator 0.5 kW 

Standard

HR  Heat recovery cell 

Efficiency approx. 60% 

Standard

Supply air fan / VALLOX 75 

105 W, 65 l/s (50 Pa) 

Standard

Supply air fan / VALLOX 95 

180 W, 80 l/s (75 Pa)

Standard

SS 

Service switch 

Door switch 

Standard

T1 Regulating 

thermostat 

0…40 

°

C Standard

Extract air fan / VALLOX 75 

105 W, 75 l/s (80 Pa) 

Standard

Extract air fan / VALLOX 95 

180 W, 95 l/s (100 Pa) 

Standard

V1 

Control valve 

Self-ac 5…21 

°

C  Standard

T2 

Water radiator defrost thermostat  Factory s5 

°

C Standard

SP 

One-way damper, 2 pcs 

Air flow operated 

Standard

G3

G3

SILENCER

SILENCER

H

F7

E

S

R

HEAT RECOVERYCELL

(HR)

SP

M

M

SP

POST-HEATING

RADIATOR

DISTRIBUTION
PANEL

10A

230 V

VALLOX 95/75

INTERNAL ELECTRICAL AND CONTROL CONNECTIONS

FAN SPEED ADJUSTMENTSEPARATE
COOKER HOOD OR
CONTROL CENTRE

VENTILATION ZONE

SS

T1

T2

V1

Ljm

Ljp

HS

Summary of Contents for 75 SILENT

Page 1: ...changer efficiency approx 60 Summer winter damper Electric 500 W radiator or water radiator VKL G 3 F 7 G 3 52 kg Door switch Cooker hood PTX PTXP control centre 1992 1992 EK or remote monitoring cont...

Page 2: ...welling 4 3 2 1 VALLOX 75 95 SILENT DIMENSIONS AND MAIN PARTS 2 2 Main parts Extract air fan Supply air fan Postheating radiator electric or water Heat recovery cell Outdoor air filter F7 1 2 3 5 4 6...

Page 3: ...OX 75 95 SILENT Pressure loss in ducts Total pressure SFP Specific Fan Power guideline value 2 5 kw m3 s SFP Input power total W Air flow max dm3 s Pressure loss in ducts Total pressure SFP Specific F...

Page 4: ...52 53 55 28 36 44 47 51 53 54 20 30 39 42 45 47 49 19 33 37 41 43 44 76 79 83 85 89 90 89 50 54 60 62 65 67 68 61 67 73 74 79 78 80 53 61 67 69 72 74 75 41 48 57 60 63 65 67 29 32 39 42 44 46 47 22 3...

Page 5: ...summer position airflow through the cell is prevented and heat recovery bypass is activated REMOTE MONITORING CENTRE VALLOX 1993A ON OFF switch Operating status data to remote monitoring Transformer...

Page 6: ...he flow of outdoor air to the unit The unit starts automatically as soon as the risk of freezing has passed The threshold temperature of the risk of freezing can be set at the thermostat J of the wate...

Page 7: ...the front edge of the damper below the front edge of the collar When detaching the damper take the same steps in the opposite order Self actuated one way dampers are only used in VKL model units B C D...

Page 8: ...of the electric radiator The overheat protector T2 of the radiator R is triggered and power supply to the heating unit is stopped if the temperature of the thermostat exceeds 80 C The overheat protect...

Page 9: ...stops the unit when the temperature of water radiator goes below the threshold value preventing the risk of freezing in the water radiator This also causes self actuated one way dampers SP to close p...

Page 10: ...1 L L N L 3 2 N INTERNAL ELECTRICAL CONNECTION OF THE HOODS N L VALLOX 95 75 COOKER HOOD PTXP A 27983 COOKER HOOD PTX 27983 HOOD Distribution panel L3 230 V 160 V 120 V 70 V L N 90 V 135 V 180 V 1 5...

Page 11: ...internal electrical connection F1 Supply air fan F2 Extract air fan T1 Post heating radiator regulating thermostat 0 25 C Limitation T2 Defrost thermostat 5 C K Capacitor SS Safety switch Wire colour...

Page 12: ...LENT 12 ELECTRICAL CONNECTIONS REMOTE MONITORING VALLOX 75 95 control through remote monitoring with control centre 1993 YK 2A VALLOX 1993A YK 2A VALLOX 75 95 REMOTE MONITORING CONTROL CENTRE DISTRIBU...

Page 13: ...plate has to be fixed horizontally in order to ensure that the unit will be straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate S...

Page 14: ...he pipe and its components Examples of condensing water connections Yli 600 n 100 n 100 Suction air COLLECTOR condensing water goes to the cellar Water seal at the lower end n 100 Suction air and fill...

Reviews: