Vallox 3603 Manual Download Page 5

5

© Vallox Oy - All rights reserved

 

MAINTENANCE

TROUBLESHOOTING

Flashing LED

Problem

Correction

1

NTC sensor of the supply air from the cell is faulty

Check the sensor and the wires, replace as required

2

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

3

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

4

NTC sensor of the exhaust air is faulty 

Check the sensor and the wires, replace as required

5

NTC sensor of the outdoor air is faulty 

Check the sensor and the wires, replace as required

6

The supply air fan has stopped. 

Check the wiring of the fan, replace the fan as required

7

The extract air fan has stopped. 

Check the wiring of the fan, replace the fan as required

8

EEPROM is faulty 

Replace the circuit board

BEFORE BEGINNING  

MAINTENANCE WORK

The safety switch (S) automatically turns off the power 

when the door of the Vallox TSK Multi 50/80 MC ventilation 

unit is opened. Always disconnect the power plug before 

starting the Vallox TSK Multi 50/80 MC ventilation unit 

maintenance. 

FILTERS

When the maintenance reminder becomes activated, 

check the cleanliness of the filters and replace them if 

required. The Vallox ventilation unit has three air filters: 

•  Coarse filter for supply air (A) filters insects, heavy 

pollen and other relatively large foreign objects out of 

the outdoor air. 

•  Fine filter for supply air (B) filters microscopic pollen 

and dust particles out of the supply air. 

•  Coarse filter for extract air (C) filters the extract air 

and keeps the heat recovery cell clean. 

Using original Vallox filters ensures the best operation 

of the ventilation unit and the best filtering results. The 

filter replacement interval depends on the ambient dust 

concentration. It is recommended that the filters be 

replaced every spring and autumn, or at the very least 

once a year.

S

R model in the figures. 

In the L model, the parts are mirrored

TROUBLESHOOTING TABLE

If the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error 

relay, signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring.  

NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.

A

B

C

Summary of Contents for 3603

Page 1: ...Manual MANUAL Low energy ventilation unit with heat recovery Document D2585 Valid from 07 03 2022 Updated 20 06 2022 Model Vallox TSK Multi 50 MC Vallox TSK Multi 80 MC Types 3603 B3602...

Page 2: ...er 8 or by persons with reduced sensory physical or mental capabilities or whose lack of knowledge and experience do not ensure safe operation of the unit Such persons can use the unit under supervisi...

Page 3: ...post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AU...

Page 4: ...entiometer is turned clockwise the extract air flow is reduced The potentiometer for adjusting the supply and extract air flows Concealed installation of the fireplace switch optional MAINTENANCE REMI...

Page 5: ...aintenance FILTERS When the maintenance reminder becomes activated check the cleanliness of the filters and replace them if required The Vallox ventilation unit has three air filters Coarse filter for...

Page 6: ...OVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Pull the coarse filters including the frames out of the uni...

Page 7: ...ass duct filter stand package out of the unit and turn to the right 3 Disconnect the cable of the bypass damper motor 4 Tilt the supply air fan to the right and push the connectors out of the way 5 Tu...

Page 8: ...3 kW 0 32 A EC 0 043 kW 0 32 A EC Specific energy consumption SEC in a cold climate in a temperate climate A B Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 79...

Page 9: ...74 77 250 47 55 62 66 68 69 71 73 73 39 47 55 60 61 62 63 65 67 500 36 44 50 55 59 63 66 68 70 26 33 38 42 47 52 55 57 57 1000 29 39 45 50 54 59 61 63 65 21 29 34 38 42 45 48 50 52 2000 21 29 39 45 5...

Page 10: ...PM ISO Coarse 75 Heat recovery bypass Automatic Dimensions w x h x d and weight 1026 x 293 x 626 58 5 kg Working point defined in the Ecodesign Directive 2009 125 EC Southern Finland Helsinki Vantaa T...

Page 11: ...22 36 42 51 60 66 67 Fre quency of the octave band Hz 63 60 67 68 72 73 79 79 78 54 58 59 63 66 78 70 73 125 56 65 64 66 68 70 72 73 48 56 54 56 58 62 63 64 250 51 58 67 70 74 78 76 76 43 50 61 59 61...

Page 12: ...hood Cables BK black BN brown BU blue GN green GY grey WT white YE GN yellow green RD red 951155 951123 951153 951159 BU 1 BN 2 YEGN 9 951150 951152 BN 7 W T 8 GN 15 YE 16 RD 7 W T 8 BU 15 YE 16 BK 1...

Page 13: ...CHO GND PWM DAMP IN OUT MODE IN OUT F ALARM RS 485 A B GND N L DAMPER 1 2 3 LIGHT N L FAN N L VDC VDC Tacho S MC VENTILATION UNIT five terminal connector GND S GND S MV VENTILATION UNIT GND AN I RM I...

Page 14: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Page 15: ...ot cause any disturbance Such locations include storage premises and technical spaces Important The whole length of the outdoor air duct to the unit and exhaust air duct from the unit must be insulate...

Page 16: ...942211 13 Side sealing strip of the heat recovery cell 3356300 Vallox TSK Multi 50 MC 13 Side sealing strip of the heat recovery cell 3352600 Vallox TSK Multi 80 MC NO Part Product number 14 Upper sea...

Reviews: