SILENCER UNIT INSTALLATION INSTRUCTIONS

General

•  The silencer unit is meant as a duct silencer mounted on top of

the Vallox 200 SE unit. The unit has an opening cover, thanks
to which it can be cleaned without detaching the ducts.

•  The unit also incorporates detachable lamellar silencer plates

in supply and extract air ducts.

•  4 x 200-mm external joints are used as duct joints, allowing

the leading of ductwork directly from the unit with curved
sections, for instance.

• Detach the door of the silencer unit. If you want to make the unit lighter so that it will be easier to lift it in

place, you can also detach the lamellar silencer plates of the supply and extract air ducts. (See the adjoining
figure.)

• If Vallox 200 SE is equipped with a water-circulating heater and/or MLV unit, you should always detach the

lamellar silencer plate of the supply air duct. (See the adjoining figure.)

• Mount the internal joints (4 pcs, 200) included in the delivery to the duct outlets, which are situated either at

the top of the Vallox 200 SE unit or at the bottom of the silencer unit.

• If Vallox 200 SE is equipped with an MLV preheating/cooling unit, pierce the grommets situated at the

bottom of the silencer unit, through which the connection pipes of the MLV unit go. When installing the
silencer unit, make sure that these pipes go through the grommets. The ferrules and compression couplings
delivered with the unit can be used to connect the pipes of the MLV unit to the pipes in the ground collector,
led through the lead-in seals at the top of the silencer unit to the point of connection. (See the adjoining
figure.)

• Lift the unit on top of Vallox 200 SE. (See the adjoining figure.)
• Mount the lead-in pipes (included in the delivery) for cables in place by pushing them first through the lead-

in seals located at the top of the silencer unit and then through the lead-in seals located at the bottom of the
silencer unit and at the top of Vallox 200 SE. (See the adjoining figure.)

Installation

• Thread necessary cables through lead-in pipes to the connection box located

within Vallox 200 SE.

• If you use a water-circulating heater, mount the supply and return water pipes

for it (not included in the delivery) through the lead-in seals located at the top
and bottom of the silencer unit and at the top of Vallox 200 SE, and connect them
to the heating unit. (See the adjoining figure.)

• Mount the lamellar silencer plates in place.
• Carefully fix the door of the silencer unit in place.
• Fix the ducts steadily and tightly to the relevant outlets.  Implement duct

insulation if needed as defined in the ventilation plan.

•  The top and bottom of the unit have lead-in sealings for

the lead-in pipes of cables and also for the supply and
return water pipes of a water-circulating heater if such a
heater is used.

•  The weight of the silencer unit is 97 kg with door, and

60 kg without door and silencers.

NOTE! BEFORE INSTALLATION CHECK THE MODEL OF VALLOX 200 SE
(L OR R). TURN THE SILENCER UNIT TO THE CORRECT POSITION.

SILENCER UNIT, L MODEL

Duct connection ø 200,

4 pcs

Supply and return water

pipe Ø 15/13, 2 pcs

Lead-in seal for supply and return

water pipe, 2 pcs

Lamellar silencer plate,

extract air ductwork

Lead-in seal

for cable

lead-in pipe,

3 pcs

Lamellar silencer plate,

supply air ductwork

Lead-in seal for supply

and return water pipe,

2 pcs

SILENCER UNIT, R MODEL

Door of the silencer unit

Lead-in seal

for cable

lead-in pipe,

3 pcs

VALLOX 200 SE

Vallox 200 SE L

Cable lead-in pipe,

3 pcs

Lead-in seals for ground

collector pipes

Cable lead-in pipe

Ground collector pipes, e.g.
Ø 15 Cu

Straight reducer coupling
15 x 12

MLV unit connection pipes
ø 12 mm

ø 200 4 pcs.

Summary of Contents for 3527800

Page 1: ...iency 60 B Supply air efficiency 84 Specific Fan Power SFP 1 3 125 dm3 s B Filters Supply air G4 F7 Extract air G4 Heat recovery bypass Automatic Weight 146 kg Comes standard with control Vallox Digit...

Page 2: ...overy cell Heat recovery bypass Supply air filter F7 Extract air filter G4 Outdoor air filter G4 Condensing water outlet Electrical connection lead ins Control panel Measurement outlets behind the cov...

Page 3: ...ON AIR FLOW 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the room...

Page 4: ...Herz ADJUSTMENT POSITION AIR FLOW Sound power level going from the unit to the extract air ductwork by octave band Lw dB ADJUSTMENT POSITION AIR FLOW ADJUSTMENT POSITION AIR FLOWS supply extract A wei...

Page 5: ...xtract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE MLV electric 5 63...

Page 6: ...IR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE M...

Page 7: ...sorption LpA A painotettu nenpainetaso 10 m2 n nenabsorptio 63 125 250 500 1000 2000 4000 8000 Lw dB LwA dB A Hz LpA dB A 2 70 77 4 96 l s 2 63 l s 2 95 l s 4 125 l s 6 161 s 8 174 l s PERFORMANCE WIT...

Page 8: ...ay contact signal is issued It is possible to manage the whole operation of the unit via remote monitoring control by using a Vallox LON or KNX converter that is available as an option Week clock cont...

Page 9: ...terminal block of the con nection box by connecting the first hu midity sensor to RH1 in place of the 6K8 resistor in the terminal block re move the resistor in this case and the second humidity sens...

Page 10: ...W DC PF EXHAUST AIR FAN 2 X 117 W DC H INTERFERENCE SUPPRESSOR K CHOKE FG DAMPER MOTOR 24 VAC TE TEMPERATURE SENSORS R1 AUXLIARY RESISTOR 6 8 KOHM TR TRANSFORMER 1 3 A 16 V F MOTHERBOARD FUSE 800 mA S...

Page 11: ...L ME HUMIDITY SENSOR 2 OPTION HUMIDITY SENSOR 1 OPTION REMOVE THE RESISTOR WHEN CONNECTING THE FIRST HUMIDITY SENSOR TO THE UNIT BOOST SWITCH FIREPLACE SWITCH Additional control option FAN CONTROL Vol...

Page 12: ...unit also has an automatic defrost function for the water circulating post heating unit VKL model Defrost When exhaust air temperature goes below the threshold value set the automatic defrost function...

Page 13: ...flow Temperature of air coming to the radiator ta1 15 C Temperature of water coming to the radiator tf1 55 C Total power of radiator kW 0 100 dm3 s 0 050 dm3 s 0 020 dm3 s Water flow 160 dm3 s 120 dm...

Page 14: ...ior notice HEATING VKL WATER RADIATOR 14 VKL WATER RADIATOR PRESSURE LOSS IN WATER CIRCULATION Defined for 100 water Water flow Total pressure loss kPa dm3 s 100 90 80 70 60 50 40 30 20 10 9 8 7 6 5 4...

Page 15: ...DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT FIREPLACE BOOSTER SWITCH POST HEATING UNIT WATER LP2 SI...

Page 16: ...ir temperature at the temperature value set on control panel H 10 30 C Heat recovery bypass Heat recovery is enabled whenever post heating has been switched on Automatic heat recovery bypass is active...

Page 17: ...LECTRICAL AND CONTROL CONNECTIONS PRESSURE DIFFERENCE SWITCH LON CONVERTER DISTRIBUTION PANEL CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE REMOTE...

Page 18: ...ating unit LP2 on the basis of the measurement data given by extract air sensor TE4 aiming at keeping extract air temperature at the temperature value set on control panel H 10 30 C Heat recovery bypa...

Page 19: ...the screwed terminal block as specified in the connection instructions The external connection diagram is shown in these instructions and inside the cover of the electrical connection box The interna...

Page 20: ...tions Water condensing from extract air going through the unit can be removed from the bottom tank in two ways When the humidity content of extract air is high as for example in washing rooms the cond...

Page 21: ...et The unit also issues an alarm of freezing risk at the controller It is recommended to have e g a spring actuated check valve E in the outdoor air duct and possibly also in the exhaust air duct This...

Page 22: ...ith no condensation insulation should not go below 16 20 C P Circulation pump not included in the delivery Because of the risk of condensation the pump should be suitable for pumping a liquid that is...

Page 23: ...ure Mount the lead in pipes included in the delivery for cables in place by pushing them first through the lead in seals located at the top of the silencer unit and then through the lead in seals loca...

Page 24: ...Vallox We reserve the right to make changes without prior notice www vallox com Vallox Oy Myllykyl ntie 9 11 32200 Loimaa FINLAND 358 10 7732 200 1 09 280bFIN 24 9 2015 PDF...

Reviews: