Vallox 200 SE CONNECTION OF VKL POST-HEATING RADIATOR
Sample connection: separate heat exchanger for ventilation unit (non-freezing connection).

Vallox 200 Se MLV preheating/cooling radiator connection

22

RADIATOR CONNECTIONS

You need no other defrost protection if you choose a non-freezing heat transfer solution. In the sample connection the exchanger (V) is installed in the heat source. Supply air temperature is mainly adjusted

according to the temperature of supply water, adjusted with a three-way valve (SV). Air temperature can also be adjusted and limited with a valve (T) included in the unit delivery. The valve (T) requires

bypass (S). Open expansion tank (A) has a capacity of  circa 2.5 litres and is mounted on the suction side of the pump. Stop valves (R) are also installed in the pipe system. Pump (P2) is a standard heat

pipe pump (pump power 0.1 dm3/s and pressure 5...40 kPa).

MLV preheating/cooling radiator connection

ALWAYS PRIMARILY FOLLOW THE CONNECTION PLAN PREPARED BY THE
HVAC PLANNER OR THE HEAT PUMP MANUFACTURER.

See the adjoining example of connecting an MLV unit to the ground collector. The supply

pipe of the MLV circuit is connected to the pipe returning from the ground collector. The

liquid returning from the MLV circuit is taken back to the return pipe of the ground

collector. If the internal pressure losses of the heat pump in the ground collector are

known to be high, it is recommended to bypass the heat pump. The liquid then circulates

when the heat pump is stopped. In this case the pressure loss of the bypass non-return

valve has to be lower than that of the heat pump. When the conditions for starting the

heating or cooling function have been met, the control function of the unit opens the

solenoid valve (MV) and starts the pump (P). The components of the MLV circuit

mentioned in the diagram are not included in the delivery. Observe the freeze resistance

of the liquid used in the ground collector. The connection pipes of the MLV radiator have

to insulated against condensation. If there is an open expansion tank in the heat pump,

it must be at the highest point in the network. Note! Because of the risk of humidity

damage, supply air temperature in a duct with no condensation insulation should not

go below +16...20 

°

C.

P

Circulation pump, not included in the delivery. Because of the risk of

condensation, the pump should be suitable for pumping a liquid that is cooler

than the surroundings (for example Grundfos Magna 1 25-80).

P2     Circulation pump, not included in the delivery.
MV    Solenoid valve, not included in the delivery. The valve  has to be suitable for

the liquid in the ground collector (for example  ELV05006, Stig Wahlström).

Y    Non-return valve, not included in the delivery.
R     Stop valve, not included in the delivery
IP     Air bleeder, not included in the delivery. Air bleeder is placed after the pump,

at the highest point in the network.

T     2-way control valve, included in the unit delivery.
A

Open expansion tank, not included in the delivery.

SV

Three-way valve, not include in the delivery.

S

Bypass valve, not included in the delivery.

Y2     Non-return valve, not included in the delivery. The pressure  loss of the valve

has to be lower than that of the heat pump.

MLV preheating/cooling radiator connection

The radiator is connected to the pipe coming and returing from the ground

collector. When the conditions for starting the heating or cooling function

have been met, the control function of the unit opens the solenoid valve

(MV) and starts the pump (P). The radiator has Ø12 mm plastic pipes (M)

coated with an oxygen diffusion barrier. Observe the freeze resistance of

the liquid used in the ground collector. The connection pipes of the MLV

radiator have to insulated against condensation. Note! Because of the risk

of humidity damage, supply air temperature in a duct with no condensation

insulation should not go below +16...20 

°

C.

VALLOX 200 SE

GROUND COLLECTOR

GROUND COLLECTOR

HEAT PUMP

P Circulation pump, not included in the delivery. Because of the risk of

condenstion, the pump should be suitable for pumping a liquid that is

cooler than the surroundings (for example Grundfos UPS 25-80 180).

MV Solenoid valve, not included in the delivery. The valve  has to be

suitable for the liquid in the ground collector (for example  ELV05006,

Stig Wahlström).

R Stop valve, not included in the delivery.

IP    Air bleeder, not included in the delivery.

Air bleeder is placed after the pump, at the highest point in the

network.

K Expansion tank, not included in the delivery.

VV  Relief valve, not included in the delivery.

PM  Pressure gauge, not included in the delivery.

PU   Pipe of ground collector (for example 32/10), not included in the

delivery.

Summary of Contents for 3527800

Page 1: ...iency 60 B Supply air efficiency 84 Specific Fan Power SFP 1 3 125 dm3 s B Filters Supply air G4 F7 Extract air G4 Heat recovery bypass Automatic Weight 146 kg Comes standard with control Vallox Digit...

Page 2: ...overy cell Heat recovery bypass Supply air filter F7 Extract air filter G4 Outdoor air filter G4 Condensing water outlet Electrical connection lead ins Control panel Measurement outlets behind the cov...

Page 3: ...ON AIR FLOW 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the room...

Page 4: ...Herz ADJUSTMENT POSITION AIR FLOW Sound power level going from the unit to the extract air ductwork by octave band Lw dB ADJUSTMENT POSITION AIR FLOW ADJUSTMENT POSITION AIR FLOWS supply extract A wei...

Page 5: ...xtract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE MLV electric 5 63...

Page 6: ...IR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE M...

Page 7: ...sorption LpA A painotettu nenpainetaso 10 m2 n nenabsorptio 63 125 250 500 1000 2000 4000 8000 Lw dB LwA dB A Hz LpA dB A 2 70 77 4 96 l s 2 63 l s 2 95 l s 4 125 l s 6 161 s 8 174 l s PERFORMANCE WIT...

Page 8: ...ay contact signal is issued It is possible to manage the whole operation of the unit via remote monitoring control by using a Vallox LON or KNX converter that is available as an option Week clock cont...

Page 9: ...terminal block of the con nection box by connecting the first hu midity sensor to RH1 in place of the 6K8 resistor in the terminal block re move the resistor in this case and the second humidity sens...

Page 10: ...W DC PF EXHAUST AIR FAN 2 X 117 W DC H INTERFERENCE SUPPRESSOR K CHOKE FG DAMPER MOTOR 24 VAC TE TEMPERATURE SENSORS R1 AUXLIARY RESISTOR 6 8 KOHM TR TRANSFORMER 1 3 A 16 V F MOTHERBOARD FUSE 800 mA S...

Page 11: ...L ME HUMIDITY SENSOR 2 OPTION HUMIDITY SENSOR 1 OPTION REMOVE THE RESISTOR WHEN CONNECTING THE FIRST HUMIDITY SENSOR TO THE UNIT BOOST SWITCH FIREPLACE SWITCH Additional control option FAN CONTROL Vol...

Page 12: ...unit also has an automatic defrost function for the water circulating post heating unit VKL model Defrost When exhaust air temperature goes below the threshold value set the automatic defrost function...

Page 13: ...flow Temperature of air coming to the radiator ta1 15 C Temperature of water coming to the radiator tf1 55 C Total power of radiator kW 0 100 dm3 s 0 050 dm3 s 0 020 dm3 s Water flow 160 dm3 s 120 dm...

Page 14: ...ior notice HEATING VKL WATER RADIATOR 14 VKL WATER RADIATOR PRESSURE LOSS IN WATER CIRCULATION Defined for 100 water Water flow Total pressure loss kPa dm3 s 100 90 80 70 60 50 40 30 20 10 9 8 7 6 5 4...

Page 15: ...DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT FIREPLACE BOOSTER SWITCH POST HEATING UNIT WATER LP2 SI...

Page 16: ...ir temperature at the temperature value set on control panel H 10 30 C Heat recovery bypass Heat recovery is enabled whenever post heating has been switched on Automatic heat recovery bypass is active...

Page 17: ...LECTRICAL AND CONTROL CONNECTIONS PRESSURE DIFFERENCE SWITCH LON CONVERTER DISTRIBUTION PANEL CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE REMOTE...

Page 18: ...ating unit LP2 on the basis of the measurement data given by extract air sensor TE4 aiming at keeping extract air temperature at the temperature value set on control panel H 10 30 C Heat recovery bypa...

Page 19: ...the screwed terminal block as specified in the connection instructions The external connection diagram is shown in these instructions and inside the cover of the electrical connection box The interna...

Page 20: ...tions Water condensing from extract air going through the unit can be removed from the bottom tank in two ways When the humidity content of extract air is high as for example in washing rooms the cond...

Page 21: ...et The unit also issues an alarm of freezing risk at the controller It is recommended to have e g a spring actuated check valve E in the outdoor air duct and possibly also in the exhaust air duct This...

Page 22: ...ith no condensation insulation should not go below 16 20 C P Circulation pump not included in the delivery Because of the risk of condensation the pump should be suitable for pumping a liquid that is...

Page 23: ...ure Mount the lead in pipes included in the delivery for cables in place by pushing them first through the lead in seals located at the top of the silencer unit and then through the lead in seals loca...

Page 24: ...Vallox We reserve the right to make changes without prior notice www vallox com Vallox Oy Myllykyl ntie 9 11 32200 Loimaa FINLAND 358 10 7732 200 1 09 280bFIN 24 9 2015 PDF...

Reviews: