MLV = heating/cooling radiator
VKL = water-circulating radiator
© Vallox • We reserve the right to make changes without prior notice.
TEKNINEN OHJE
ELECTRONIC CONTROLLER
WITH LCD DISPLAY
• 1.09.280b ENG
• Updated
24.9.2015
• Valid from
24.9.2015
• Type 3486
© Vallox
Vallox 200 SE electric/electric
Vallox 280 SE electric/VKL
Product IDs
Vallox code
Vallox 200 SE electric/electric L
3527800
Vallox 200 SE electric/electric R
3527900
Air volumes Supply air
190 dm
3
/s, 100 Pa
Extract air
220 dm
3
/s, 100 Pa
Electrical connection
230 V, 50 Hz, 15.2 A fixed mounting
Degree of protection provided
IP34
by enclosures
Post-heating radiator
Electric, 1 kW, 4.3 A
Preheating radiator
Electric, 2 kW, 8.7 A
Additional heating radiator
-
Fans
Supply air
2 x 117 W 0.9 A EC
Extract air
2 x 117 W 0.9 A EC
Efficiency
Annual efficiency
60% B
Supply air efficiency
84 %
Specific Fan Power SFP
1.3 (125 dm
3
/s) B
Filters
Supply air
G4 + F7
Extract air
G4
Heat recovery bypass
Automatic
Weight
146 kg
Comes standard with control
Vallox Digit SED controller
Product IDs
Vallox code
Vallox 280 SE electric/VKL L
3528000
Vallox 280 SE electric/VKL R
2528100
Air volumes Supply air
175 dm
3
/s, 100 Pa
Extract air
220 dm
3
/s, 100 Pa
Electrical connection
230 V, 50 Hz, 10.9 A fixed mounting
Degree of protection provided
IP34
by enclosures
Post-heating radiator
VKL water-circulating radiator, 3 kW
Preheating radiator
Electric, 2 kW, 8.7 A
Additional heating radiator
-
Fans
Supply air
2 x 117 W 0.9 A EC
Extract air
2 x 117 W 0.9 A EC
Efficiency
Annual efficiency
60% B
Supply air efficiency
84 %
Specific Fan Power SFP
1.3 (125 dm
3
/s) B
Filters
Supply air
G4 + F7
Extract air
G4
Heat recovery bypass
Automatic
Weight
146 kg
Comes standard with control
Vallox Digit SED controller
VALLOX 200 SE MLV/electric
Product IDs
Vallox code
Vallox 200 SE MLV/electric L
3543900
Vallox 200 SE MLV/electric R
3544000
Air volumes Supply air
180 dm
3
/s, 100 Pa
Extract air
220 dm
3
/s, 100 Pa
Electrical connection
230 V, 50 Hz, 6.5 A fixed mounting
Degree of protection provided
IP34
by enclosures
Post-heating radiator
Electric, 1 kW, 4.3 A
Preheating radiator
MLV heating/cooling radiator
Additional heating radiator
-
Fans
Supply air
2 x 117 W 0.9 A EC
Extract air
2 x 117 W 0.9 A EC
Efficiency
Annual efficiency
60% B
Supply air efficiency
84 %
Specific Fan Power SFP
1.3 (125 dm
3
/s) B
Filters
Supply air
G4 + F7
Extract air
G4
Heat recovery bypass
Automatic
Weight
146 kg
Comes standard with control
Vallox Digit SED controller
Product IDs
Vallox code
Vallox 200 SE MLV/VKL L
3544100
Vallox 200 SE MLV/VKL R
3544200
Air volumes Supply air
165 dm
3
/s, 100 Pa
Extract air
220 dm
3
/s, 100 Pa
Electrical connection
230 V, 50 Hz, 2.2 A fixed mounting
Degree of protection provided
IP34
by enclosures
Post-heating radiator
VKL water-circulating radiator, 3 kW
Preheating radiator
MLV heating/cooling radiator
Additional heating radiator
-
Fans
Supply air
2 x 117 W 0.9 A EC
Extract air
2 x 117 W 0.9 A EC
Efficiency
Annual efficiency
60% B
Supply air efficiency
84 %
Specific Fan Power SFP
1.3 (125 dm
3
/s) B
Filters
Supply air
G4 + F7
Extract air
G4
Heat recovery bypass
Automatic
Weight
146 kg
Comes standard with control
Vallox Digit SED controller
VALLOX 200 SE MLV/VLK
SE
Vallox
200
Vallox
Digit
SED