Vallox 280 L Technical Specifications Download Page 14

VALLOX 280

INSTALLATION

2

14

© VALLOX • We reserve the right to make changes without prior notification.

Location

• The unit is mounted indoors, in a place where temperature does not fall below

+10 ºC.

• The unit is to be mounted in a place where the sound pressure level coming through

the envelope is not acoustically disturbing (storerooms, corridors, technical rooms,
and in some cases rooms where people spend time, such as classrooms).

•  The unit is equipped with an adjustable base. If the unit is mounted on the wall,

attention needs to be paid to the weight of the unit (206 kg) and to vibration
isolation.

•  The unit is splash protected (IP 34) and can thus also be mounted in a damp room.

Electrical connections

•  The unit is permanently connected to the mains supply. The electrical connection box

of the unit is located inside the unit, in connection with the exhaust air duct.

•  Cables connected to the unit are led through the lead-in seals next to the extract air

duct outlet.

•  The cables are connected to the unit by taking off the upper door and the cover of

the electrical connection box located in the exhaust air duct. Follow the connection
instructions. The external and internal connection diagrams are shown in these
instructions and inside the cover of the electrical connection box.

Duct connections

• The unit is equipped with four ø 250 external connection outlets. Necessary

connecting pieces (e.g. inner or bent connectors) can be attached to external
connection outlets.

NOTE! LENGTH OF THE CONNECTING HEAD OF THE CONNECTING PIECE NO MORE THAN 50 MM.

Fix the ducts steadily and tightly to the relevant outlets. (NOTE! Unit models L/R).
Implement duct insulation if needed as defined in the ventilation plan.

Air flow measurement outlets

•  The fixed air flow measurement outlets are located behind the VALLOX nameplate

(12) at the upper edge the unit. You can easily remove the nameplate by sliding it
upward and pulling it toward yourself.

•  Via the measurement outlets, the total pressure of the supply and extract air ductwork

can be measured with a differential pressure instrument. Pressure readings and air
volume tables (p. 3 or 4) show volume flow rates at various adjustment positions.

•  The red measurement hose is on the pressure side and the black hose on the suction

side of the fan.

Condensing water connections

•  Water condensing from extract air going through the unit can be removed from the

bottom tank in two ways.

•  When the humidity content of extract air is high, as for example in washrooms, the

condensing water is led from the screw-type coupling in the bottom tank to the floor
drain via the condensing water outlet (water seal) delivered with the unit.

•  When the humidity content of extract air is low, as in office rooms, the condensing

water can be led from the screw-type coupling in the bottom tank to the condensing
water tank delivered with the unit. It is pushed below the bottom tank to the guide
posts in the base. In this case, no separate condensing water outlet is used. NOTE!
When a condensing water tank is used, it has to be inspected sufficiently often.

•  The screw-type coupling is located almost in the middle of the unit. This is why the

unit has to be mounted level with the horizontal.

Pipe connections

•  If the unit is equipped with a water-circulating post-heating unit, it is connected to the

warm water circuit with 15/13 copper tubes.

NOTE! WATER-CIRCULATING HEATING RADIATOR INCLUDES A CONTROL VALVE.

Pressure difference switches

If the unit is equipped with pressure difference switches controlling the pressure difference
in the supply and/or extract air filters, they have to be set at correct values according
to the adjustment position chosen. For further instructions, see the instructions for use and
maintenance of VALLOX 280.

483

332

332

483

DOOR

CONDENSING WATER
OUTLET, MODEL L

CONDENSING WATER
OUTLET, MODEL R

VALLOX 280 L

OUTDOOR AIR
SUPPLY AIR
EXTRACT AIR
EXHAUST AIR

VALLOX 280 R

EXHAUST AIR
EXTRACT AIR
SUPPLY AIR
OUTDOOR AIR

A
B

C
D

A
B

C
D

Lead-in seals for electrical connections
Condensing water outlet
Condensing water tank
Base
Measurement outlets

Condensing water outlets

A

10

B

C

D

8

20

12

9

10

9

8

20

12

Summary of Contents for 280 L

Page 1: ...ower 230 V 50 Hz 400 V 15 0 A preheating unit 11 A Class of protection IP 34 Weight Options Direct current fans Extract air Supply air 2 HR cells 70 Summer winter automation 2 5 kW 11 A 2 5 kW 11 A ca 5 kW G3 and F7 G3 206 kg DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY VALLOX We reserve the right to make changes without prior notification TECHNICAL SPECIFICATION VALLOX 280 L VALLOX 280 R Mode...

Page 2: ...3 Condensing water tank Condensing water outlet Electrical connection lead ins Control panel Measurement outlets 2370 665 220 220 1100 187 222 282 222 187 1000 1370 Ø 250 4 PCS 10 9 8 7 6 5 4 3 2 1 A B C D 7 1 13 5 4 14 8 2 3 11 16 17 9 15 19 6 10 VALLOX 280 model L in the picture 18 12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Post heating radiator Electric or water Preheating radiator Elec...

Page 3: ... dB LWA dB A Hz ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope to the rooms where the unit has been installed LpA dB A 2 128 l s 4 164 l s 6 202 l s 8 238 l s 2 171 l s 4 210 l s 6 242 l s 8 261 l s 2 119 171 l s 4 149 209 l s 6 177 239 l s 8 208 260 l s 45 50 53 55 84 73 70 54 49 48 38 28 84 64 86 76 74 57 51 51 42 31 87...

Page 4: ...tract G3 Medium frequency of the octave band Hz 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz LpA dB A 2 99 l s 4 123 l s 6 159 l s 8 199 l s 2 136 l s 4 158 l s 6 186 l s 8 218 l s 2 122 151 l s 4 153 186 l s 6 183 215 l s 8 218 239 l s Volume flow rate Pressure loss in ducts Total pressure Air volumes SUPPLY G3 F7 EXTRACT G3 Supply extract air volumes VALLOX 280 silencer 42 47 50 53 68 51...

Page 5: ...n Humidity adjustment With this button you set humidity adjustment on and off When the indicator is lit the adjustment is on Post heating With this button you set post heating on and off When the indicator is lit post heating is on The summer function is active when the indicator is not lit 1 2 3 4 5 6 7 8 Fan speed Supply air temperature Post heating is on Filter guard alert Maintenance reminder ...

Page 6: ...lly When the first carbon dioxide sensor has been connected to the system the unit is switched on After this the unit gives the sensor an address Follow the same steps for other carbon dioxide sensors Surface mounting Wiring Cable NOMAK 2 x 2 x 0 5 mm2 0 5 mm2 Base plate of the CO2 sensor Electronics card of the CO2 sensor model may vary NOTE Faulty coupling of the wire destroys the carbon dioxide...

Page 7: ... 4 A 24 V 25 VA F MOTHERBOARD FUSE S MAINTENANCE SWITCH DOOR SWITCH LP1 ELECTRIC HEATER 2500 W PREHEATING OPTION LP2 ELECTRIC HEATING UNIT 2500 W POST HEATING OPTION SV WATER HEATING UNIT ACTUATOR POST HEATING UNIT OPTION TZ1 OVERHEAT PROTECTION 60 C TZ2 OVERHEATING PROTECTOR 95 C NEEDS TO BE ACKNOWLEDGED PDS1 SUPPLY AIR FILTER PRESSURE DIFFERENCE SWITCH OPTION PDS2 EXTRACT AIR FILTER PRESSURE DIF...

Page 8: ...ED WHEN THE FIRST HUMIDITY SENSOR IS CONNECTED TO THE UNIT ORANGE 1 WHITE 1 ORANGE 2 A WHITE 2 B METAL M HUMIDITY SENSOR 1 OPTION HUMIDITY SENSOR 2 OPTION CONNECTED TO REPLACE RESISTOR R CONNECTOR RH 1 AND RH1 S NOTE When VALLOX 280 is used with a PREHEATING UNIT and a WATER CIRCULATING POST HEATING UNIT L and L1 in the terminal block are looped There is then NO NEED for a separate supply for preh...

Page 9: ...eedless heating of outdoor air during summer The unit also has an automatic defrost function for the water post heating unit Defrost The automatic defrosting of the heat recovery cells intermittently stops the supply air fans when the temperature of exhaust air goes under the set threshold value In order to minimise momentary stoppages of the supply air fans the fan can also be equipped with an el...

Page 10: ...2 RH TE1 16 A 230 V DISTRIBUTION PANEL VALLOX 280 INTERNAL ELECTRICAL AND CONTROL CONNECTIONS TE2 F 5 TZ1 F 7 Pressure difference switch LP2 PDS1 M EF TE4 HR2 G 3 TE3 FG M SF TZ1 TZ2 LP1 TZ2 G 3 PDS2 1 2x16 A if resistance power exceeds 2 5 kW a separate supply is needed for preheating REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT Electric pre...

Page 11: ...tor LP2 continues to heat Overheating protection of heating unit Overheating protection thermostats TZ1 and TZ2 monitor the surface temperature of hea ting units LP1 and LP2 If surface temperature exceeds the threshold overheat protection is triggered and power supply to the heating unit is stopped Overheat protector TZ1 is reset automatically and TZ2 manually Alarms Pressure difference switches P...

Page 12: ... Electric preheating unit SILENCER UNIT REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT BOOSTER SWITCH FIREPLACE SWITCH CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST CONTROL PANEL 2 AT MOST VENTILATION ZONE S 2 1 H RH 1 CO 2 RH 1 LON CONVERTER TE1 16 A 230 V DISTRIBUTION PANEL VALLOX 280 TE2 F 5 F 7 PDS1 M EF TE4 HR2 G 3 TE3 FG M SF TZ...

Page 13: ...of the measurement data of outdoor temperature sensor TE3 outdoor air 0 C and supply air temperature sensor TE2 supply air 7 C thus preventing water heating unit LP2 from freezing A freezing alert appears in the display of the control panel The fans restart automatically as soon as the risk of freezing passes supply air 10 C Preheating unit overheat protection Overheating protection thermostats TZ...

Page 14: ...ure of the supply and extract air ductwork can be measured with a differential pressure instrument Pressure readings and air volume tables p 3 or 4 show volume flow rates at various adjustment positions The red measurement hose is on the pressure side and the black hose on the suction side of the fan Condensing water connections Water condensing from extract air going through the unit can be remov...

Page 15: ...detach the lamellar silencer plate in the supply air duct of the heater NOTE VALLOX 280 model L or R See the figure Lift the unit on top of VALLOX 280 Mount the lead in pipes included in the delivery for cables in place by pushing them first through the lead in seals located at the top of the silencer unit and then through the lead in seals in the VALLOX 280 unit Thread necessary cables through le...

Page 16: ...1 09 357E 22 01 07 PDF VALLOX We reserve the right to make changes without prior notification Vallox Oy FI 32200 Loimaa Finland Telephone 358 2 7636 300 Fax 358 2 7631 539 www vallox com ...

Reviews: