14
INS
TALLA
TION
Ceiling mounting by using a ceiling
mounting plate
(optional)
The unit can be equipped with an optional ceiling
mounting plate. The ceiling mounting plate must be
fastened on rafter frames or other frame structure with
M8 thread bars. The bars must be fastened so that they
withstand the weight of the unit.
The ceiling mounting plate must be fastened horizontally
to make sure that the unit is level. The ceiling mounting
plate must be fastened so that there is a 10 mm gap
between its rear edge and the finished wall. This way
the ventilation unit will be installed as close to the wall as
possible. The top edge of the white covering strip of the
ceiling mounting plate can be installed against the finished
ceiling. Alternatively, a concealed mounting method can
be used, in which case the finished ceiling can be 30 mm
or less from the top edge of the white covering strip.
The ceiling mounting plate is fastened to the M8 thread
bars with the mounting supplies delivered with the
mounting plate. NOTE! The end of the thread bars must
be 5 mm or less below the fastening nut (more detailed
instructions are provided with the ceiling mounting plate).
Installing the ventilation unit to the ceiling
mounting plate
Remove the unit door. Lift the unit and take the wires
through the opening in the ceiling mounting plate. Lift
the ventilation unit against the ceiling mounting plate so
that it locks in place. The unit has become locked on the
ceiling mounting plate when the two operating levers on
the mounting plate have been restored to the same level
with the white covering strip of the ceiling mounting plate
(more detailed instructions are provided with the ceiling
mounting plate).
Ceiling mounting plate (optional)
The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively,
a concealed mounting method can be used, in which case the finished ceiling can be 30 mm or less from the top edge of the
white covering strip.
The minimum distance from
the finished rear wall is 10 mm
The recommended distance from
the finished side wall is 10 mm
598
10
10
598
Finished wall
Finished wall
Concealed installation
of the ceiling mounting plate
on the ceiling, max. 30 mm
483
453
53
53
Finished ceiling
Siphon Silent Klick
Installation
space of
the siphon
73 mm
Installation
space of
the elbow
47 mm
Concealed installation
of the ceiling mounting plate
on the ceiling, max. 30 mm
483
453
38
38
Finished ceiling
Elbow
10
Finished wall