OPERATING INSTRUCTIONS FOR CONTROL PANEL

3.5  

Week programme programming

Adjust wk. prog.
Press + and -

To go to the week-clock programme 

programming mode press the + 

and – buttons simultaneously. See the 

instructions in 4.1.

3.6  

Erasing week programme

Erase wk. prog.
Press + and -

You can totally erase the week 

programme by pressing the + and – 

buttons simultaneously.

3.7 

Choosing basic humidity level

Rh-level setting
automatic

The basic humidity level can be chosen 

as either automatic or manual.
The selection is done with the + and – 

buttons.

3.8 

Basic humidity level setpoint

Basic %RH level
40%

The desired setpoint is chosen with the + 

and – buttons when manual adjustment 

has been selected as the Rh level setting 

(humidity setting, Section 3.7).

3.9 Changing setpoint for carbon dioxide adjustment

CO2 setting
0900 PPM

The setpoint for CO

2

 adjustment is 

chosen with the + and – buttons.

3.10 

Adjustment interval

Adjust interval
10

The adjustment interval for humidity and 

carbon dioxide adjustments is selected 

with the + and – buttons. The adjustment 

interval refers to minutes.

3.11 

Changing operating temperature of 

               heat recovery cell bypass

Cell bypass
10C

The desired cell bypass temperature 

is selected with the + and – buttons. If 

outdoor temperature is lower than cell 

bypass temperature, the summer/winter 

damper is in the winter position.

3.12 

Mode of operation of fi replace/booster switch

Switch type
fi replace switch

The mode of operation of the switch 

(either fi replace or booster switch) is 

selected with the + and – buttons.

3.13 

Address of control panel

Panel address
1

The address of the control panel is 

changed with the + and – buttons. Two 

control panels cannot have the same 

address. If control panels have the same 

address, they go to bus fault state and 

do not work.

3.14 

Contrast of control panel display

Display contrast
05

The contrast setting for the control panel 

display is changed with the + and – 

buttons.

3.15   Restoring factory settings

Factory settings
see manual

The general factory settings can be 

restored by pressing the + and – buttons 

simultaneously. Remember to ensure that 

the setpoints are in accordance with the 

factory settings for this unit. 

3.16 

Choosing cascade adjustment for supply air 

temperature

Cascade adjust
off

Cascade adjustment is chosen to be on 

or off with the + and – buttons.

3.17 

Choosing post-heating for the unit

Radiator type
Electric rad.

A water or electric radiator is selected 

with the + and – buttons, depending on 

the type of post-heating radiator the unit 

is equipped with. Note! Choosing the 

wrong type of post-heating may cause a 

faulty post-heating function.

3.18 

Choosing additional heater for unit

Extraheater type
Electric rad.

An electric or MLV radiator is chosen 

according to ventilation unit type with the 

+ and – buttons. This unit can be used 

only for electric heater setting

3.19 

MLV additional heater setpoint

MLV winter temp
0C

Changing MLV radiator setpoint. When 

outdoor air temperature goes below this 

setpoint, the ventilation unit starts the MLV 

pump. If a message “Preheating not in 

use” is displayed, no setpoint is in use.

3.20 

Choosing melting mode

Defrost mode
bypass

Choose one of the two modes of melting 

to be used in the unit. Melting is done 

either by stopping the supply air fan or by 

bypassing the HR cell. 

3.21 

Winter parameter A

Winterparam. A

           

The winter function of the unit is 

adjusted from the menu when it is not 

too cold outside (warmer than –15 °C). 

Decreasing the value of the parameter 

increases the freezing of the HR cell. 

Increasing the value decreases the freezing of the HR cell. The unit operates 

optimally on the factory settings. There is no need to adjust this setpoint 

except in extreme problem situations, and even then it is advisable to 

contact Vallox Maintenance. The adjustment is made with the + and – 

buttons. See the table for the factory setting.

3.22 

Winter parameter B

Winterparam. B

           

The winter function of the unit is adjusted 

from the menu in very cold weather 

(colder than –15 °C). Increasing the 

value of the parameter increases the 

freezing of the HR cell. 

Decreasing the value decreases the freezing of the HR cell. The unit 

operates optimally on the factory settings. There is no need to adjust this 

setpoint except in extreme problem situations, and even then it is advisable 

to contact Vallox Maintenance. The adjustment is made with the + and – 

buttons. See the table for the factory setting.

3.23 

Setting base fan speed

MIN speed
1

The desired base fan speed (minimum 

fan speed) is chosen with the + and – 

buttons. Active when week-clock control 

is not on. Week-clock control changes 

this speed.

3.24 

Choosing maximum fan speed

MAX speed 
8

The desired maximum fan speed is 

selected with the + and – buttons. 

Maximum fan speed is on either with 

adjustments or always. See Section 

3.25. Mode of operation of maximum 

speed setting.

3.25   Mode of operation of maximum speed setting

MAX speed limit 
with adjustments

The maximum fan speed setting can 

be selected to be active either only 

in connection with (carbon dioxide 

and humidity) sensor adjustments or 

permanently. The selection is done with 

the + and – buttons.

Summary of Contents for 096 SE R

Page 1: ...erating maintenance and technical instructions Electrical connection 230 V 50 Hz 5 1 A plug Degree of protection provided by enclosures IP 34 Fans Extract air 89 dm3 s 100 Pa direct current DC Supply...

Page 2: ...ring result 1 to 2 carbon dioxide sensors can be connected as options to the VALLOX 096 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel Th...

Page 3: ...heating indicator light Maintenance reminder symbol Maintenance reminder The maintenance reminder switches on the maintenance reminder symbol on the main display of the control panel at defined interv...

Page 4: ...menu you can change setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on wh...

Page 5: ...water or electric radiator is selected with the and buttons depending on the type of post heating radiator the unit is equipped with Note Choosing the wrong type of post heating may cause a faulty pos...

Page 6: ...ttons The rotation speed of the extract air fan can be decreased by decreasing the percentage Move the cursor with the arrow keys and change values with the and buttons Note that to exit and save when...

Page 7: ...By using original Vallox filters you ensure good operation of the ventilation unit and the best filtering result The replacement interval of filters depends on dust content in ambient air It is recomm...

Page 8: ...you wish to detach the fan lift it upwards and crank the plastic lock to the right using for instance a chisel gure 6 The fan then falls down and can be pulled out of the unit Disconnect the quick co...

Page 9: ...t message is displayed and the unit operates at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type C...

Page 10: ...ing range E Extract air fan S Supply air fan Input power total W Air flow max dm3 s SFP SFP Specific Fan Power recommended value 2 5 kW m3 s At a lower total pressure SFP will be smaller at this speed...

Page 11: ...P W M 5 4 3 2 1 M 2x0 25 3x0 25 BN WT BN GN connection box on top of the unit 5 3 10 1 FAN CONTROL 0 10 V DC A B M S S 1 2 S S RH1 RH2 RS 485 BUS FAULT SIGNAL FIREPLACE SWITCH 12x0 25mm2 N GND L1 L 1...

Page 12: ...t state In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional contr...

Page 13: ...t protective enclosure the unit must be located in a place with no acoustic disturbance storerooms technical rooms etc Wall mounting VALLOX 096 SE is mounted on the wall with a mounting plate as shown...

Page 14: ...ting plate in place Then 4 332 544 600 600 push a rubber damper and washer to each thread bar all the way into the cup of the plate and turn the nut Shorten the lower ends of the thread bars so that t...

Page 15: ...l 3467200 10 Filter stand 3464500 No Part Code 11 G4 coarse filter 978045 extract air 12 Bypass duct assembly 3475100 indicate if right or left handed 13 Damper motor 930613 14 Extract air outlet 9850...

Page 16: ...1 09 602E 3 12 2013 PDF...

Reviews: