11
© Vallox • We reserve the right to make changes without prior notice
EXPERT SETTINGS
DEPLOYMENT WIZARD
FAN SETTINGS
In the following chapters, you will set the output ratio between the
supply and extract air fans.
IMPORTANT
Adjust the air flows, according to the values in the ventilation plan.
Try to adjust the air flows in a way that you do not have to choke
the air flows at the valves. This is the most energy efficient set up.
First, set both values as close to the ideal value as possible.
The ideal values are presented in the supply and extract air
volume graphs. If, at the beginning, the air flows differ greatly
from each other, the ventilation unit may have to carry out extra
defrosting cycles on sub-zero temperatures, thus complicating the
adjustment of the air flows. Check the air flows by measuring them
at the valves, and fine tune the percentage values, if necessary.
NOTE
If the outside air is extremely cold (below -10°C on an aluminium
cell or below -3°C on a plastic cell), the ventilation device may
have to defrost the heat exchanger cell. If this occurs, you cannot
adjust the air flows and the Defrosting figure is shown on the control
panel.
SUPPLY AIR
When you want to make the system supply air settings, proceed as
follows:
1. The deployment wizard Fan settings screen is opened.
2. Set the supply air quantity as a percentage of the maximum
by using the
Plus
and
Minus
buttons. The fan speed (1/min)
will change, according to the percentage value.
3. Once you have set the supply air fan settings, press the
Right
arrow
button.
EXTRACT AIR
When you want to make the system extract air settings, proceed
as follows:
1. The deployment wizard Fan settings screen is opened.
2. Set the extract air quantity as a percentage of the maximum
by using the
Plus
and
Minus
buttons. The fan speed (1/min)
will change, according to the percentage value.
3. Press the
OK
button.
4. The extract air fan ratio is now set.
WARNING
The ventilation specialist has
made the supply and exhaust
air settings when deploying
the Vallox ventilation unit. If you
make changes to the settings,
ensure that they conform with the
ventilation plan.