Valley Classic Control Panel
25
Overview
Volt Meter
The volt meter displays the voltage being delivered to
the machine from the control panel. See Figure 25-1.
The recommended operating voltage is the nominal
supply voltage. See Figure 25-2.
During normal operation the meter should read ap-
proximately the nominal supply voltage. See Figure
25-2.
NOTE
• Some long or high amperage machines may
need to be run at 500 VAC, 60 Hz (400 VAC, 50
Hz) minimum.
!
CAUTION
•
DO NOT OPERATE THE MACHINE IF THE
VOLT METER READS BELOW THE MINIMUM
ALLOWED VOLTAGE OR ABOVE THE MAXI-
MUM ALLOWED VOLTAGE. SEE FIGURE 25-2.
• OPERATING THE MACHINE OUTSIDE THESE
LIMITS COULD CAUSE DAMAGE TO THE
DRIVE MOTORS AND OTHER ELECTRICAL
COMPONENTS.
•
CORRECT THE LOW VOLTAGE PROBLEM
BEFORE RESUMING OPERATION.
CAUTION
DANGER
High Voltage!
480 Volts can kill.
Lock Machine Power
in the “OFF” position
before opening cover.
0997326
Do not operate system when temperature
is below 40° F (4.5° C)
Read and understand the valley operator
manual before operating this equipment.
CAUTION
0997300
CAUTION
DO NOT HOLD BUTTON DEPRESSED
LONGER THAN 3 SECONDS. REPEATED
START ATTEMPTS CAN CAUSE SERIOUS
STRUCTURAL DAMAGE
0997302
OFF
ON
TEST
Classic
1
Figure 25-1 1. Volt Meter
Nominal
Supply Voltage
Maximum
Allowed Voltage
Minimum
Allowed Voltage
480 VAC @ 60 Hz
505 VAC
440 VAC
415 VAC @ 50 Hz
420 VAC
375 VAC
400 VAC @ 50 Hz
420 VAC
365 VAC
380 VAC @ 50 Hz
420 VAC
355 VAC
230 VAC @ 60 Hz
253 VAC
220 VAC
220 VAC @ 50 Hz
243 VAC
210 VAC
120 VAC @ 60 Hz
132 VAC
105 VAC
110 VAC @ 50 Hz
121 VAC
95 VAC
Figure 25-2