MP80.PUB  Version 1.07                                              21                        

 

ADD-ON TO OIL FURNACE 

 

The MP80 may be connected to an oil furnace having a rated input of up to 1.2 USGPH.  Minimum blower 
capacity must be at least 900 cfm..  A regular upflow oil furnace may be used and connected as per fig. 1on 
page 15.  The MP80 can be located on either side of the oil furnace.  Minimum interconnect duct size is 12" X 
18" with minimum 6" inside radius elbows   The wood furnace requires a chimney approved for solid fuel use.  
Maintain clearances to all combustibles.  Refer to general instructions portions of this manual also. 
If changes are made to the installation of the oil furnace these shall comply with CSA Standard B139. 
 
An interconnect limit switch system must be included in the control circuitry to prevent the simultaneous 
operation of both furnaces when the hot air plenum reaches the preset level of 150°F.  See Typical wiring 
Diagram 6 on pg. 22.

 

ADD-ON TO GAS FURNACE 

 

The MP80 may be connected to a gas furnace having a rated input up to 120,000 BTU.  Minimum blower 
capacity must be at least 900 cfm..  A counterflow gas furnace may be used with an interconnect duct as 
indicated in Fig 1. page 15.  A regular upflow gas furnace may also be used and connected as per Fig 1on pg. 
22.  The MP80 can be located on either side of the gas furnace.  Minimum interconnect duct size is 12" x 18" 
with minimum 6" inside radius elbows.  The wood furnace requires a chimney approved for solid fuel use.  
Maintain clearances to all combustibles. Refer to general instructions portions of this manual also.  
THE OPERATION OF THE GAS FURNACE MUST BE VERIFIED, FOR ACCEPTABLE OPERATION 
BEFORE AND AFTER INSTALLATION OF THE ADD ON, BY A GAS FITTER WHO IS RECOGNIZED 
BY THE REGULATORY AUTHORITY.  DO NOT CONNECT TO ANY FURNACE THAT HAS NOT 
BEEN CERTIFIED INITIALLY AS COMPLYING WITH CGA STANDARD CAN1-2.3 OR ITS 
PRECEDENTS.  DO NOT CONNECT TO ANY FURNACE THAT IS NOT EQUIPPED WITH AN AIR 
CIRCULATION BLOWER. 
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT THE MP80 TO A CHIMNEY WHICH ALSO 
VENTS A GAS FURNACE OR OTHER GAS APPLIANCE. 
 

ADD-ON TO ELECTRIC FURNACE 

 

The MP80 may be added to an electric furnace with heating capacity between 10KW and 25 KW.  Minimum 
blower capacity must be at least 900 cfm.  Electric furnaces approved for installation in any position can be 
inverted and used in a down flow position using an adapter duct between the furnace and the add-on as 
indicated in fig. 1 pg. 13.  The electric furnace can be located on either side of the MP80 but clearances to 
combustibles must be maintained. Refer to general and pressure loss instruction portions of this manual. (pg. 
15)  
If changes are made to the installation of the electric furnace they must comply with CSA Standard C22.1. 
An interconnect limit switch system must be included in the control circuitry that prevents the simultaneous 
operation of both furnaces when the hot air plenum reaches the preset level of 150°F.  Typical wiring diagram 
follows below re: Diagram 8A (with W1,R,C and G connections.) and 6 for basic units. 
 

An interconnect limit switch system must be included in the control circuitry to prevent the 
simultaneous operation of both furnaces when the hot air plenum reaches the preset level of 150°F.  
Typical wiring diagram follows, see Diagram 6 on pg. 20 

Summary of Contents for MP80

Page 1: ...50 493 7444 www blazeking com Email sales blazeking com READ THOROUGHLY AND COMPLY WITH ALL LOCAL CODES AND REGULATIONS MP80 SOLID FUEL FURNACE FOR USE AS AN ADD ON TO OIL GAS OR ELECTRIC FURNACE OR A...

Page 2: ...MP80 PUB Version 1 07 2...

Page 3: ...UDED 14 OPTIONAL EQUIPTMENT 14 INSTALLATION OPTIONS 14 TYPICAL INSTALLATION DIAGRAMS 15 CLEARANCES 16 ALTERNATE FURNACE LOCATIONS 16 PRESSURE LOSS 17 COMBUSTION AIR 17 INTERCONNECT DUCT RETAINERS 17 F...

Page 4: ...ept as noted for replacement parts Warranty Period Components Covered Parts Labor Wood 1 Year X All parts materials and surface finishes flaking and peeling Subject to Conditions Exclusion and Limitat...

Page 5: ...see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty How the Warranty Works 1 All warranties by the manufacturer are set herein and no claim sh...

Page 6: ...wind hills mountains inadequate venting or ventilation excessive offsets negative air pressures or other influences caused by mechanical systems such as furnaces fans clothes dryers etc 11 The Limite...

Page 7: ...air work the customer will pay any in home travel fees or service charges required by the Authorized Dealer 26 At no time will Blaze King be liable for any consequential damages which exceed the purch...

Page 8: ...plenum opening 30 5 8 L x 18 W Fire door opening 12 x 13 Firebox length 26 Width 14 Height 19 Capacity 4 cu ft Fuel length 24 Firebox design features 1 distributed draft system with preheated primary...

Page 9: ...Combustible material including firewood must be stored well away from the furnace outside of the distances specified for clearance to combustibles Never operate the furnace unless you are sure the smo...

Page 10: ...this booklet thoroughly and save it for future reference Carefully follow instructions for installation OPERATING INSTRUCTIONS LIGHTING THE FIRE NEVER START A FIRE UNLESS THE FURNACE IS CORRECTLY INST...

Page 11: ...ttle draft results in a sluggish fire and smoke backing up into the house when the furnace door is opened Too much draft over 06 in w c is unsafe and wastes fuel Use a Barometric damper when necessary...

Page 12: ...y cleaning to remove creosote buildup Remember the hotter the fire the less creosote A large smoldering fire causes more creosote than a small high heat fire We recommend that each day preferably in t...

Page 13: ...E IS BE ING OVERFIRED OPERATE THE ALTERNATE ELECTRIC GAS OR OIL FURNACE PERIODICALLY TO EN SURE THAT IT WILL OPERATE SATISFACTORILY WHEN NEEDED INSPECT VENT PIPES VENT PIPE JOINTS AND VENT PIPE SEALS...

Page 14: ...150 or equivalent White Rodgers 5D51 78 set at 220 or equivalent White Rodgers 5D51 78 set at 250 or equivalent Thermostat White Rodgers 1E78 or equivalent Poker Ash shovel Instruction book Insulation...

Page 15: ...OOD COUNTERFLOW INSTALLATION REQUIRES NOTE IN THIS CONFIGURATION SPECIAL CLEARANCES APPLY SEE CF6KIT INSTRUCTIONS DO NOT INSTALL IN THIS CONFIGURATION WITHOUT USING THE CF6KIT CF6 KIT OPTION ALTERNATE...

Page 16: ...on and maintenance of wood heating systems across Canada For your safety and satisfaction your system must be properly installed MINIMUM CLEARANCES TO COMBUSTIBLES See label copy addendum If the furna...

Page 17: ...e drop Static pressure at furnace minus static pressure at duct exit Record the pressure drop of the original system Addition of the add on furnace will add air flow resistance in the system After ins...

Page 18: ...chimney connector must be attached to either an approved masonry chimney or one of the listed factory built chimneys suitable for use with solid wood fuel All joints must be tight and fastened with sh...

Page 19: ...not necessarily assure proper flue draft Use a minimum total system height of 12 feet measured from the stove flue collar to the top of the chimney not including the chimney cap THERMOSTATS Stand alo...

Page 20: ...must not compress leads tightly against the surface DOOR AND LATCH INSTALLATION Install the firebox door on the frame hinges Install the door latch catch on to the frame mounting bracket as shown bel...

Page 21: ...l also THE OPERATION OF THE GAS FURNACE MUST BE VERIFIED FOR ACCEPTABLE OPERATION BEFORE AND AFTER INSTALLATION OF THE ADD ON BY A GAS FITTER WHO IS RECOGNIZED BY THE REGULATORY AUTHORITY DO NOT CONNE...

Page 22: ...S INDEPENDENT WOOD FURNACE When installed with a blower cabinet mounted on either side the MP80 becomes an INDE PENDENT wood only furnace The blower must have a minimum 900 cfm capacity In this config...

Page 23: ...ECTIONS WHEN USING ELECTRICAL FURNACE WITH W1 R C G CONNECTIONS You must connect the alternate furnace thermostat through the interlock limit switch to provide interlock lockout of the alternate furna...

Page 24: ...hen installing in a stand alone configura tion with a VB1000 blower Only 2 out of the three limit switches are used The middle limit is the Operating Limit and the right limit switch is the Safety Lim...

Page 25: ...10V Motor Adjustable from 900cfm to 1200 cfm 20Ga Steel Cabinet Construction High Quality Baked Enamel Finish Color matched to Valley Comfort Wood Furnaces Complete with 24 X 20 Air Filter Please chec...

Page 26: ...MP80 PUB Version 1 07 26...

Reviews: