5.1
SISO3 Labeling
5.1.1
Manufacturer and type:
Vallen Systeme GmbH, 82057 Icking, Germany
Signal Isolator SISO3
Type
SNo. yyyy-xxx
Serial number (yyyy = year, xxx number produced)
CE
0123
Notified body for EN 80079-34:2011 audit and surveillance: TÜV
SÜD
TÜV-A 11ATEX0004X
Notified body for type examination: TÜV Austria, X: Does not contain
overvoltage protection for atmospheric electricity.
5.1.2
ATEX / CENELEC label:
II (1) 3 G Ex nA [ia Ga] IIC T4 Gc
Tamb: -20 to +60 °C IP30
Meaning of the ATEX / CENELEC label elements:
Indicates the following symbols as terms defining the area of use
according to ATEX
II
Group of device which can be used in explosive areas but not in mines
(1)
This is an associated apparatus for a device of category 1 which is
useable in zone 0
3
This apparatus is of category 3 from the group of device (II) useable in
zone 2 (or in non-hazardous area). This operation manual does not deal
with the use of SISO3 in a hazardous area
G
For use in explosion hazardous gas (not dust)
Ex
Label indicating the following symbols are terms defining the protection of
devices according to CENELEC standards
nA
This is a non-sparking apparatus for use in zone 2
[ia Ga]
This is an associated apparatus of an intrinsically safe device "ia" in
accordance with Equipment Protection Level (EPL)
“Ga”. Equipment for
explosive gas atmospheres, having a very high level of protection, which
is not a source of ignition in normal operation, expected malfunction, or
when subject to rare malfunction. Such equipment has a form of
protection which will remain effective even in the presence of two
potential faults or will have two independent means of protection (usable
in zone 0) (EN60079-0 3.18.3)
IIC
Explosion group; for gases needing the lowest amount of energy to ignite
an explosion, e.g. hydrogen
T4
Temperature class, defining that the maximum surface temperature a gas
can reach in this apparatus (SISO3) stays always below 135 °C
Gc
Equipment for explosive gas atmospheres, having a normal level of
protection, which is not a source of ignition in normal operation.