Note:
temperature can be adjusted between 17°C and 28°C through 0.5°C gaps.
Note:
heating mode controls every floor convector and SBU400 ones too.
Note:
the air conditioner compressor must be turned OFF, at least 1 minute
before it can be turned ON again.
If the AC button is pressed during this time, the device reschedules the air
conditioner compressor start up for one 1 minute again (the AC button flashes).
The air conditioner compressor runs for at least 1 minute before shutting down.
If it is disabled directly after enabling, it will continue to operate for 1 minute
(the AC button flashes).
Note:
after product start up and at
Cooling Mode, the condenser fans
run for 10 seconds, so just then the
air conditioner compressor is
enabled.
1.5- Heating Mode
1.4- ON/OFF Air Conditioner Compressor
1.6- Desired temperature level SET POINT
3
Air conditioner compressor
disabled.
- OFF:
press button (3) if the status light is
on. If the compressor is ON, the status light
will flash for 1 minute, indicating the
compressor status change from ON to OFF.
The cooling function is disabled then.
Press button (4) to Increase
tempe 0.5 °C.
Press button (5) to Increase
temperature - 0.5 °C.
22.0
Compressor Mode/Auto Enabled.
- ON:
press button (3). Air conditioning
compressor is enabled and turns ON if
necessary, and if minimum waiting time is
kept (see following note). The cooling
function is switched ON again.
22.0
Temperature UP.
22.5
22.5
2 1.5
4
Temperature DOWN.
2 1.5
5
Temperature
decreasing
Set-point
Temperature
increasing
Compressor
ON
Compressor
OFF
Set-point - P22
Set-point + P21
Temperature
decreasing
Set-point
Temperature
increasing
Heating
enabled
Heating
disabled
Set-point - P23
Set-point + P24
Heating Mode is controlled by set-point and parameters P23 and P24, according
to table below:
CONTROLLER
CC 185T - CC 205T - CC 205W
12