Description: Low limit for breakaway
pressure low
43505
1 RW
U16
Breakaway pressure high
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: High limit for breakaway
pressure high
43496
2 RW
U32
FST time low
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Low limit for fail
position stroke time warning
43498
2 RW
U32
FST time high
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: High limit for fail
position stroke time warning
43500
2 RW
U32
FST total time low
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Low limit for total time
warning
43502
2 RW
U32
FST total time high
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: High limit for total time
warning
Register Len Access
Type
Name
Parameter Range/Units/Notes
SOT error parameters
43611
1 RW
U16
Enable errors
Default: 00002
Range: 00002: Yes;00001: No;
Description: Show SOT errors
43612
2 RW
U32
Timeout
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: The timeout, before
which a pressure drop must occur
43614
1 RW
U16
Start pressure low
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Low limit for the start
pressure
43615
1 RW
U16
Start pressure high
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: High limit for the start
pressure
43616
2 RW
U32
SOT total timeout
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Total timeout for the
solenoid test
Register Len Access
Type
Name
Parameter Range/Units/Notes
Scheduler