5.4
Valve Test Status
Register Len Access
Type
Name
Parameter Range/Units/Notes
Latest tests
43102
1 RO
U16
Last PST result
Default: 00000
Range: 00000: No Test; 00001: Pass;
00002: Fail; 00003: Warning; 00005:
Abort;
Description: Result of the last Partial
Stroke Test
43103
1 RO
U16
Last FST result
Default: 00000
Range: 00000: No Test; 00001: Pass;
00002: Fail; 00003: Warning; 00005:
Abort;
Description: Result of the last Full
Stroke Test
43104
1 RO
U16
Last SOT result
Default: 00000
Range: 00000: No Test; 00001: Pass;
00002: Fail; 00003: Warning; 00005:
Abort;
Description: Result of the last
Solenoid Valve Test
43108
1 RO
U16
Last EST result
Default: 00000
Range: 00000: No Test; 00001: Pass;
00005: Abort;
Description: Result of the last
Emergency Shutdown Test
Partial stroke test
Last test
Description: Last partial stroke test
measurements
43251
2 RO
TIME
Time
Description: Time for last partial
stroke
43253
2 RO
DATE Date
Description: Date for last partial
stroke
43270
1 RO
U16
Start pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Start pressure
43264
2 RO
U32
SOV reaction time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: SOV reaction time, only
available with pressure sensor
43255
2 RO
U32
Breakaway time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Breakaway time
43271
1 RO
U16
Breakaway pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Breakaway pressure
43257
2 RO
U32
PST time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: PST time
43266
2 RO
U32
PST pressurising time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Pressurising time
43272
1 RO
U16
PST pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Pressure at SP