User's Guide _______________________________________________________________________
48 ___________________________________________________________________ M211399EN-F
Set Analog Output Scaling
Use the
ASEL
command to select the output parameter and scaling for
analog output channels.
ASEL
[
channel parameter lo_value hi_value
]<cr>
where
channel = Analog output channel, 1 or 2.
parameter = Parameter that is output on the channel.
Available parameters are:
RH
relative humidity
T
temperature
Tdf
dew/frost point temperature
Td
dew point temperature
Tw
wetbulb temperature
h
enthalpy
x
mixing ratio
a
absolute humidity
dTd
dew/frost point depression
lo_value = Low limit of the scaling, in the units of the selected
parameter.
hi_value = High limit of the scaling in the units of the selected
parameter.
Example (set channel 1 to output dewpoint, in the range -10 ... 20 °C):
>
pass 9000
>
asel 1 TD -10 20
Aout 1 quantity : Td (
-
10.00 ... 20.00 'C)