TECHNICAL DATA
Specifications
Property
Specification
Carbon dioxide
Measurement range
0 ... 2000 ppm
Accuracy across temperature range
+20 ... +30 °C
±(30 ppm +3 % of reading)
+10 ... +20 °C, +30 ... +40 °C
±(35 ppm +3.7 % of reading)
+0 ... +10 °C, +40 ... 50 °C
±(40 ppm +4.8 % of reading)
Stability in typical HVAC applications
±(15 ppm + 2% of reading)
over five years
Warmup time
1 min
10 min for full specification
Response time (63 %)
60 s
Carbon dioxide sensor
Vaisala CARBOCAP® GM10
Temperature
Measurement range
0 ... 50 °C
Temperature sensor
on P models
Pt1000 RTD Class F0.15
IEC 60751
for analog outputs
Digital temperature sensor
Accuracy (GMW83)
+10 ... +30 °C
±0.5 °C
+0 ... +10 °C, +30 ... 50 °C
±1 °C
Humidity
Measurement range
0 ... 95 %RH
Accuracy
Temperature range +10 ... +30 °C
0 ... 80 %RH
80 ... 95 %RH
±3%RH
±5%RH
Table 6 Performance