background image

38

FUNCTIONAL CHECKS
(COMMISSIONING PART III)

I

0

Functional checks

Procedure

Once the unit has been installed and
the gas supply has been checked,
operate the system to ensure that it is
working correctly. 

Operate the system, following the
operating instructions supplied with
the boiler.

Check the system for water leaks
and escaping gas.

Check that the flue has been 
correctly installed, according to the
fitting instructions supplied with the
flue assembly.

Check the burner for correct 
ignition and flame picture.

Check the hot water system for 
correct operation.

Check the heating system for 
correct operation.

Fig. F.1: Test for correct functioning

Euro B/S 058/0

Summary of Contents for TURBOmax Pro 28

Page 1: ...TIONS FOR INSTALLATION AND SERVICING TURBOmax Pro 28 2 E Wall hung room sealed fan assisted combination boilers The code of practice for the installation commissioning servicing of central heating systems I 0 ...

Page 2: ...re relief valve 14 Pressure gauge 14 Expansion vessel 15 Circulating pump 16 System by pass 16 Venting 16 DHW expansion vessel accessory 16 General 17 Preparation of boiler location 17 Selecting position of boiler 17 Using boiler template 18 Fitting the boiler hanging bracket 19 Install the flue system 19 Fitting the boiler 19 Removing boiler casing 20 Gas supply 21 Cold water mains inlet and hot ...

Page 3: ...rodes 46 Fan 47 Gas valve 48 Temperature sensors NTCs 49 Main heat exchanger 49 Expansion vessel 50 Electronic control board 51 Main transformer 51 Pump 52 Air pressure switch 52 System bypass 53 Diverter valve 53 Pressure gauge 54 Aqua sensor 54 DHW heat exchanger 55 Pressure relief valve 55 Checking functions 56 Functional checks Commissioning Part III Functional checks 38 Operation 39 Adjusting...

Page 4: ... 4 I 0 3 Fig L 1 Items supplied with unit Table L 1 Items supplied with unit Euro B S 021 1 GB_Pro Item Quantity Description 1 1 Boiler 2 1 Flue restriction rings 3 1 Cold water inlet valve 5 1 Copper tail for hot water outlet connection 6 1 Template 4 3 Flow and return service valve gas service valve 7 1 Guarantee Card and Benchmark log book 8 1 Installation and connection accessories and PRV pac...

Page 5: ...he heat exchanger is limited by the boiler control system and it is not necessary to install a scale reducer on the cold mains to the boiler However in exceptionally hard water areas to prevent scale formation in the property hot water system pipework a scale reducer may be fitted TURBOmax Pro combination boilers have a built in diagnostic system which indicates the operational status of the boile...

Page 6: ...Inlet gas working pressure required natural gas 20 mbar Gas burner pressure ignition rate 1 8 mbar Gas rate max DHW 3 3 m3 h Weight 45 kg Primary water content 2 0 l Maximum CH heat input net 31 1 106 200 kW Btu h Gas supply G20 Gross CV s t 37 8 MJ m3 Gas burner pressure max rate 10 8 mbar CH temperature flow range 35 82 C Minimum CH water flow for 20 C rise 1203 l h Pump pressure available 0 25 ...

Page 7: ...ection diameters Euro B S 024 2 Key 1 Heating system return 22 mm compression 2 Cold water connection with shut off valve 15 mm compression 3 Gas connection 15 mm compression 4 Hot water connection 15 mm tail 5 Heating system flow 22 mm compression 6 Flue outlet 100 mm flue with turret 7 Hanging bracket 8 Rear flue outlet ...

Page 8: ...tor temperature control 10 Diverter valve 11 DHW heat exchanger 12 Automatic bypass valve 13 CH flow service valve 14 Hot water outlet 15 Gas service valve 16 Service valve 17 Service valve 18 Pressure relief valve 19 Aqua sensor DHW flow switch 21 Main on off control 22 Pressure gauge 23 Indicator lights 24 Expansion vessel 25 Expansion vessel charging valve 26 Circulating pump 27 Automatic air v...

Page 9: ...r forced circulation hot water for domestic premises BS 5546 Specification for gas hot water supplies for domestic premises BS 6700 Services supplying water for domestic use within buildings and their curtilages BS 6798 Specification for installation of gas fired boilers not exceeding 60 kW input BS 6891 Specification for installation of low pressure gas pipework up to 28 mm R1 in domestic premise...

Page 10: ...ct of the installation of a boiler in a room containing a bath or shower Where the installation of the boiler will be in an unusual location special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect The boiler must be mounted on a flat vertical wall which must be sufficiently robust to take the weight of the boiler The boiler may be installed on a combustibl...

Page 11: ...d top outlet flue system 125 mm outside diameter A top outlet horizontal flue system of 125 mm outside diameter is also available Art No 303 609 and can be used to achieve flue lengths of up to 10 m Both 45 and 90 bends and elbows are also available to increase siting flexibility A vertical 125 mm concentric flue system is also available Art No 303 600 Refer to flue system installation instruction...

Page 12: ...tion for fan assisted flue minimum distance mm A1 300 B Below gutters soil pipes or drain pipes 25 C Below eaves 25 D Below balconies below car port roof 25 E From vertical drain pipes and soil pipes 25 F From internal or external corners 25 G Above ground or balcony level 300 I From a terminal facing a terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal...

Page 13: ...oom or internal space in which the boiler is installed Electrical supply A 230 V 50 Hz single phase electricity supply fused to 3 Amp must be provided in accordance with the latest edition of BS7671 IEE Wiring Regulations and any other local regulations that may apply The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary ...

Page 14: ... the new boiler and be in accordance with BS 7593 For advice on the application of system cleansers contact either Sentinel Betz Dearborn Ltd Widnes Cheshire WA8 8UD Tel 0151 495 1861 or Fernox Alpha Fry Technologies Tandem House Marlow Way Beddington Farm Road Croydon CRO 4xS Tel 0870 601 5000 Fernox technical help line 01799 550811 Filling and make up The system should be filled with water via a...

Page 15: ...ble to the boiler in accordance with BS 5449 Part 1 Guidance on the sizing of an additional expansion vessel is given in Table R 2 Table R 2 Sizing of additional expansion vessel Vessel Volume L Initial system pressure bar 1 0 1 5 Pressure relief valve setting bar 3 0 Total water content of system litres 25 50 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 2 7 5 4 10 9 13 6 16...

Page 16: ...the boiler The boiler is suitable for use in systems with thermostatic radiator valves and no additional by pass is required Venting The boiler is fitted with an automatic air vent Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually DHW expansion vessel accessory A DHW expansion vessel kit Art No 3...

Page 17: ... Boiler location for information regarding siting the appliance In general the boiler must be positioned such that There is adequate space around the boiler for service and maintenance The boiler can be correctly flued i e the flue terminal position is sited in accordance with the flue termination section see page 12 and the air flue duct can be installed in accordance with the flue installation i...

Page 18: ... Mark the position of the hanging bracket fixing holes 1 Drill 2 holes Ø 8 mm for the hanging bracket Identify correct flue exit Mark the centre of the selected air flue duct and its circumference e g by drilling through the template For installation of a rear exit outlet please refer to the installation instruc tions of the rear exit outlet kit Art No 303817 Other flue options Flue instructions f...

Page 19: ...es onto the hanging bracket Note Lift the boiler from either side at the bottom edge Install the flue system Install the flue system refer to separate air flue duct installation instructions Fitting the boiler hanging bracket Fix the hanging bracket 2 to the wall using the screws supplied it may be necessary to use additional or alternative fixings to ensure adequate support Note If the boiler is ...

Page 20: ...TION SEQUENCE Removing boiler casing Turn both securing fasteners 1 anti clockwise by 90 to release control panel Lower control panel 2 Pull the case 3 forward at the bottom to disengage from the securing clips Lift the case slightly to clear the top locations and pull forward to remove ...

Page 21: ...ghten Connect a gas supply pipe of not less than 15 mm diameter to the inlet of the gas service cock Tighten all connections Ensure the gas supply pipework is adequately sized such that a 20 mbar gas pressure is available at the boiler inlet at full flow rate I 0 1 2 Euro B S 046 0GB_Pro Fig I 6 Fitting the gas connection ...

Page 22: ...er 2 provided and tigh ten Connect cold water service pipe to the cold water service valve and tighten Connect the 15 mm hot water outlet copper tail 4 to the hot water outlet connection of the appliance with the washer 5 pro vided and tighten Connect hot water outlet pipework to the copper tail Note The hot water outlet union nut is packed in with the PRV fittings pack 1 2 3 4 5 6 I 0 Euro B S 04...

Page 23: ...ce valves Pressure Relief Valve Connect a discharge pipe not less than 15 mm diameter to the outlet of this valve The discharge pipework should be as short as possible and installed with a continuous fall away from the boiler The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premises or cause ...

Page 24: ...connection to the mains supply must allow complete electrical isolation of the boiler and its ancillary controls It should be readily accessible and adjacent to the boiler A 3 core flexible cord according to BS6500 tables 6 8 or 16 3 x 0 75 to 3 x 1 5 mm2 should be used Warning This appliance must be earthed Important Ensure that all cords pass through the cable clamps in the rear of the control b...

Page 25: ...el and secure in place Connection to the main supply Lower the control panel Unclip the terminal box cover 1 from the control panel 2 Feed the power supply cord in to the appliance as shown fig I 9 Use cable clamps Connect the power supply cord as follows Fig I 11 on page 26 Green yellow earth wire boiler terminal Earth sign Blue neutral wire boiler terminal N Brown live wire boiler terminal L Not...

Page 26: ...g valve Socket X7 for accessory box connection Socket X8 for VRC VC connection Room thermostat 230 V connections 3 4 and 5 Socket X12 pump connection Socket X14 gas valve connection Socket X13 fan unit connection Mains power supply connections L N and earth Do not use Electronic board layout Fig I 11 Connection wiring ...

Page 27: ...at is to be connected in addition to a time switch the wire between the time switch ON terminal and boiler terminal 4 should be broken by the contacts of the room thermostat see schematic layout Fig I 14 Vaillant optional plug in timer accessories Refer to the instructions supplied with the optional accessories for connection details Upon completion of all electrical connections refit the terminal...

Page 28: ...water can be drawn at any time Automatic pump spin control APS The boiler incorporates a built in control which will spin the built in circulating pump and operate the diverter valve once in a 24 hour period This control helps to prevent seizure when the boiler is not operated for a period of time This control is not active when the power supply to the appliance is turned off Note To temporarily o...

Page 29: ...that the locating points either side at the top of the boiler engage Push the casing onto the securing clips at the bottom of the boiler Close control panel 2 Secure control panel by turning both securing fasteners 3 clockwise by 90 1 I 0 I 0 90 90 3 2 Abb I 15 Fit boiler casing Euro B S 042 1 ...

Page 30: ...te ventilation extinguish all naked flames and do not smoke whilst purging After purging the gas service valve connection must be retightened and tested for soundness The boiler itself does not require purging as this will be done by the automatic burner sequence control Water supply Open all domestic hot water taps supplied by the boiler turn on the mains water supply to the boiler and open the m...

Page 31: ...31 COMMISSIONING PART I ...

Page 32: ...32 COMMISSIONING PART I 2 5 3 4 Fig Com 1 Draining the heating system Eor B S 207 0GB_Pro ...

Page 33: ...valve by rotating the knob on the valve Filling the heating system Proceed as follows to fill the system Open all radiator valves on the system Fill the system via the seperate filling point Open the valve slowly and fill the unit with water until the required amount has been added 2 Bleed the air from the radiators The boiler is equipped with an automatic air release valve To allow this to vent t...

Page 34: ...ot water tap Ensure that the hot water outlet temperature adjustment control is set to maximum Check that the U gauge is reading in the range of 18 to 20 mbar If the pressure is not within this range this should be investigated before continuing with the commissioning preocedure Lower pressures than this range are indicative of an incorrectly sized or partially blocked gas supply Turn off the hot ...

Page 35: ...oint on the burner inlet gas pipe and attach one arm of a U gauge 2a to the test point Remove plastic sealing plug and connect the other arm to the combustion chamber sensing tube 3a Set the DHW temperature control to maximum and fire the boiler at full rate by fully opening a hot water tap Check that the burner pressure is as the maximum shown in table G2 Measure the domestic hot water mode burne...

Page 36: ...oad The central heating output can now be altered by inserting an electricans screwdriver into the potentiometer 3 Turn the potentiometer fully anticlockwise Slowly turn the potentiometer clockwise whilst observing the U gauge Stop turning the potentiometer when the burner pressure is at the correct setting for the output required Turn off the hot tap Remove U gauge tighten test point sealing scre...

Page 37: ...ow rate Table G 2 Burner pressure Burner Pressure Natural gas 2H Main burner jet mark2 7 120 Burner pressure1 mbar Delivered gas for G20 Output kW 14 0 16 0 18 0 20 0 22 0 24 0 26 0 28 0 LPG 3 Main burner jet mark2 7 072 2 9 Burner pressure1 mbar 3 7 4 7 for G30 6 6 8 2 10 4 12 8 15 5 18 2 21 3 24 6 5 6 6 8 for G31 8 7 11 1 13 7 16 8 20 2 23 8 27 8 32 0 8 0 9 4 10 8 12 0 2 2 10 4 1 8 1 8 Ignition ...

Page 38: ...wing the operating instructions supplied with the boiler Check the system for water leaks and escaping gas Check that the flue has been correctly installed according to the fitting instructions supplied with the flue assembly Check the burner for correct ignition and flame picture Check the hot water system for correct operation Check the heating system for correct operation Fig F 1 Test for corre...

Page 39: ... operation indicator 4 will light The gas valve will open and sparking will commence at the burner The ignition indicator 5 will illuminate As soon as the burner has ignited and the flame has been sensed the flame indicator 6 will illuminate By illuminating in this sequence the indicator lights have demonstrated correct operation of the boiler for DHW I 0 1 2 3 4 5 6 7 Fig F 2 Functional check Eur...

Page 40: ...ration indicator 4 will light The gas valve will open and sparking will commence at the burner The ignition indicator 5 will illuminate As soon as the burner has ignited and the flame has been sensed the flame indicator 6 will illuminate By illuminating in this sequence the indicator lights have demonstrated correct operation of the boiler for CH Note Should the boiler fail to light it will attemp...

Page 41: ...ase water from the system until the system design pressure of 1 0 bar is attained The actual reading on the pressure gauge should ideally be 0 5 bar plus an additional pressure corresponding to the highest point of the system above the base of the boiler 10 m head equals an additional 1 bar reading on the pressure gauge The minimum pressure should not be less than 1 bar in any installation If the ...

Page 42: ...arly serviced by a competent servicing company To ensure regular servicing it is strongly recommended that arrangements are made for a Maintenance Agreement Please contact Vaillant Service Solutions 0870 6060 777 for further details Ensure the boiler log book is fully completed and leave with the end user Failure to install and commission this appliance to the manufacturers instructions may invalu...

Page 43: ... efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals The frequency of servicing will depend upon the particular installation conditions and usage but in general once per year should be adequate It is the law that all ser vicing work is carried out by a com petent person Corgi registered Important Before starting any maintenance work...

Page 44: ...ith a soft brush Reassemble in reverse order Check central heating expansion vessel Release the system water pressure from the boiler Remove valve cap from expansion vessel charge point Check that the internal charge pressure of expansion vessel is between 0 7 0 9 bar If pressure is lower than this the vessel should be re pressurised using an air pump Refit valve cap Open central heating service v...

Page 45: ... out functional checks after any service work and after exchanging any gas carrying component Always check earth continuity polarity and resistance to earth with a multimeter after any service work and after exchanging any electrical component Initial preparation Turn off the boiler Isolate the electrical supply to the boiler Turn off the gas service valve Turn off the boiler CH service valves Tur...

Page 46: ... removing support screw 1 Reassemble by following these instructions in reverse order PARTS REPLACEMENT 3 2 1 2 4 Fig E 2 Burner Euro B S 157 0 Fig E 3 Electrodes Burner Refer to the important information and initial preparation on page 45 Remove combustion chamber cover by unclipping the three clamps Disconnect the ignition and flame sensing leads Remove electrode bracket supporting screw 1 and t...

Page 47: ... the fan outlet when the boiler is installed with a rear outlet flue system push the flue connector 4 towards the rear of the boiler until it clears the fan outlet Disconnect the electrical connections 5 and the air tubes 6 and 7 from the fan Note the respective connection points for each tube Remove two screws 8 and remove the fan 9 Reassemble in reverse order ensuring that the air tubes are reco...

Page 48: ...om gas valve Undo nut 1 on the gas valve outlet connection Undo compression nut on the outlet of the gas service valve Pull off the locating spring 8 Remove complete gas valve assembly and inlet pipe from the boiler Remove both inlet pipe 12 and outlet 14 connection from the gas valve by removing the eight secu ring screws 11 and 13 and refit to new gas valve using new seals provided Reassemble in...

Page 49: ...nt information and initial preparation on page 45 Release central heating water pressure Remove combustion chamber cover by unclipping the three clamps Remove four screws 4 and pull off combustion chamber front panel Remove the fan the locating spring and the fan hood Pull off the flow clamp 5 and disconnect the return connection Remove the main heat exchanger 6 disconnect the return connection by...

Page 50: ...R Remove the boiler from the wall as follows Refer to important information and initial preparation on page 45 Release central heating water pressure Disconnect external wiring from boiler wiring terminal box Disconnect flow and return connections at union nuts between service valves and boiler Disconnect gas connection at compression joint on gas valve outlet Disconnect domestic hot and cold wate...

Page 51: ...lay by releasing the retaining clips Carefully insert the new electronic board into the control box Insert the electronic display by carefully lining up the pins and push until the display locks in to position Re assemble in reverse order Main transformer Refer to the important information and initial preparation on page 45 Lower control box Unclip the terminal box cover by releasing the cover ret...

Page 52: ...itch to blue tube 4 7 5 6 Euro B S 168 0 Pump Refer to the important information and initial preparation on page 45 Release central heating water pressure Unclip the terminal box cover by releasing the cover retaining clips and lift to remove Unplug the pump wire 1 from the electronic board Undo the three pump screws 3 Pull pump forward to remove Fit new O rings supplied to pump connections Re ass...

Page 53: ...ing pipe Re assemble in reverse order Diverter valve Refer to the important information and initial preparation on page 45 Release central heating water pressure Disconnect the plug 4 from the diverter valve Remove the spring clip 5 Undo the unions 6 and remove the diverter valve Re assemble in reverse order 3 2 1 Fig E 13 Automatic Bypass Euro B S 169 0 4 5 6 7 Fig E 14 Diverter valve Euro B S 17...

Page 54: ...e from fascia Remove retaining clip and disconnect pressure gauge capillary tube Re assemble in reverse order Aqua sensor Refer to the important information and initial preparation on page 45 Release central heating water pressure Remove the spring clip 1 Undo union nut between the cold water inlet service valve and aqua sensor Remove the spring clip 3 Pull the aqua sensor forward and release cabl...

Page 55: ... bottom left hand union 2 Push the heat exchanger 5 backwards to disconnect Re assemble in reverse order Pressure relief valve Refer to the important information and initial preparation on page 45 Release central heating water pressure Remove the spring clip 5 Disconnect the discharge pipe from the pressure relief valve Remove pressure relief valve Re assemble in reverse order 5 1 2 3 4 Fig E 17 D...

Page 56: ...tem following the operating instructions supplied with the boiler Check the system for water leaks and escaping gas Check that the flue has been correctly installed according to the separate flue instructions Check the burner for correct ignition and flame picture Check the hot water system for correct operation Check the heating system for correct operation PARTS REPLACEMENT ...

Page 57: ... the external controls are not calling for heat i e the room thermostat has reached temperature this indicator will go out This is perfectly normal Fan operation indicator yellow Illuminates to indicate that the fan is operating and has been checked by the fan pressure switch A flashing indicator shows that the air pressure switch has not made Ignition indicator yellow Illuminates when gas valve o...

Page 58: ...ace LCD display Yes No Repair external fault Is the continuity across fuse F1 Go to sheet B Does ON OFF knob operate switch on electronic board Boiler ON OFF control defective change electronic board Replace switch mechanism No No No Yes Yes Note 1 For test purposes disconnect external controls from terminal 3 4 and replace with a bridge between these terminals It appliance then operates the fault...

Page 59: ...d and approx 17 VDC secondary blue brown Check replace pump Replace fuse F1 If fan commences operation exchange gas valve After approx 20 secs Does fuse F1 blow Produce central heating demand Does fuse blow immediately Turn the main ON OFF control to the 1 position Does green power on indicator glow Yes No No No Yes Check replace fan Replace electronic board No Yes Yes Does green power on indicato...

Page 60: ...heat No Is 230 VAC present across terminals 4 and 5 No External fault Check all external controls are calling for heat replace or repair as necessary see also note 1 sheet A Yes Yes Disconnect built in timer if fitted No Go to sheet D Does ignition commence No Yes Replace defective timer Sheet C Does yellow central heating demand indicator glow Does yellow flame indicator flash ...

Page 61: ...present across fan terminals Replace electronic board Yes No No Yes No Yes Yes Check replace fan Does the boiler commence ignition Check air flue gas system is correctly fitted and not obstructed Yes No Replace electronic board No Yes Are electrodes sparking at the burner Yes Go to sheet E No Check electrodes and electrode leads Replace as necessary Sheet D Does yellow fan operation indicator glow...

Page 62: ...necessary Does burner light No Replace electronic board Yes Is burner indicator illuminated No Check flame rectification lead and electrode Is burner indicator illuminated No Yes Does burner shut down after approx 15 secs No Go to sheet F Yes Check water pressure in central heating system refill and vent as necessary Check pump is running Yes Yes Replace pump No Is 230 VAC present at the pump plug...

Page 63: ...are open No No No Replace electronic board No Check operation of boiler in DHW mode does flame increase in size to full rate Yes Check partial load setting No No Go to sheet G Yes Check connections and modulatior replace gas valve if burner still fails to increase to full rate Turn main ON OFF control to the 0 position Yes Insert a small screwdriver through the hole in the front of the diverter va...

Page 64: ...ure is sufficient and that cold water inlet filter is clear Check cold water inlet is fully open and adjustment is at maximum flow rate Check Clear impeller in Aquasensor replace if necessary Check replace hall sensor Replace electronic board Does hot water indicator glow flash now No No Yes Yes No Sheet G No Check D H W operation Does yellow hot water demand indicator glow Does yellow hot water d...

Page 65: ...65 FAULT FINDING ...

Page 66: ...or Central heating demand indicator Fan operation indicator Ignition indicator Flame indicator Power on indicator green MAIN SWITCHBOARD IGNITION ELECTRODES Legend b blue br brown y g yellow green r red p pink t transparent bl black gr grey w white gr b br y g b br y g br t w p t br br r b br y g Reset button gr p p r CONTROL BOX DIVERTER VALVE bl bl bl bl Fig D 1 Functional Flow diagram Euro B S ...

Page 67: ...on electrode Bridge NTC flow NTC flow Lifting magnet 24 23 1 12 13 14 15 16 17 18 19 20 21 22 2 3 4 5 6 7 8 9 10 11 Fan unit Ignition electrodes Gas fitting Diverter valve Aqua sensor Ionisation electrode Pump Reverberation sensor NTC flow NTC return X8 X4 VUV X12 X14 X13 9 7 L 4 8 N 3 5 X7 Accessories 1 2 3 4 EV1 Fig D 2 Wiring diagram Euro B S 027 1_GB Wiring diagram TURBOmax Pro 28 E VUW GB 282...

Page 68: ...Natural gas 053462 Er 4 Flow NTC Return NTC 252805 Er 5 Main heat exchanger 065087 Er 6 Expansion vessel 10 l 181057 Er 7 Switch and control board 130473 Er 8 Main transformer 287450 Er 9 Pump 160928 Er 10 Air pressure switch 050577 Er 11 Automatic bypass 150240 Er 12 Diverter valve 252457 Er 13 Pressure gauge 101271 Er 14 Aqua sensor 194819 Er 15 DHW heat exchanger 065088 Er 16 Pressure relief va...

Page 69: ...Er 4 Er 6 Er 7 Er 8 Er 9 Er 10 Er 11 Er 12 Euro B S 143 0 Euro B S 148 0 Euro B S 147 0 Euro B S 146 0 Euro B S 156 0 Euro B S 152 0 Euro B S 154 0 Euro B S 144 0 Euro B S 151 0 Euro B S 153 0 Er 2 Er 5 Euro B S 142 1 Euro B S 177 1 ...

Page 70: ...70 SHORT PARTS LIST Er 13 Er 14 Er 17 Er 15 Euro B S 149 0 Euro B S 145 0 Euro B S 178 0 Euro B S 150 0 Er 16 Euro B S 155 1 ...

Page 71: ...71 ...

Page 72: ... 2002 Mü Printed on 100 recycled paper Subject to alteration Head Office Vaillant Ltd Vaillant House Medway City Estate Trident Close Rochester Kent ME2 4EZ Service Solutions 0870 6060 777 Technical Advice 01634 292392 ...

Reviews: