background image

Appendix

24

Installation and maintenance instructions recoVAIR 0020188110_03

F

Maintenance messages

Overview

#

Message

Description

Maintenance work

Interval

1

M.800 Filter
change

The maintenance interval for
the filters was exceeded.

Maintaining the filters

At least twice annually

17

2

M.801 Mainten-
ance

The maintenance interval for
the product was exceeded.

Maintaining the product

At least annually

3

M.802 System ef-
ficiency impaired

The system efficiency is ad-
versely affected.

Increase/establish system effi-
ciency

As required

17

G

Technical data

VAR 150/4 L

VAR 150/4 R

Width

1,412 mm

1,412 mm

Depth

598 mm

598 mm

Height

249 mm

249 mm

Product with packaging

42 kg

42 kg

Product without packaging/ready for
operation

35.8 kg

35.8 kg

Rated voltage/measuring voltage of
the control circuit

230 V

230 V

Power frequency

50 Hz

50 Hz

Fuse, slow-blow

4 A

4 A

Power consumption

4 … 84 W

4 … 84 W

Max. power consumption (with frost
protection element, if available)

684 W

684 W

Current consumption

0.37 A

0.37 A

Minimum cross-section of the supply
line

1.5 mm

²

1.5 mm

²

Protection class

1

1

Level of protection

IP10B

IP10B

Air connection area diameter (internal)

150 mm

150 mm

Air connection area diameter (external)

180 mm

180 mm

Heat exchanger material

PET C/aluminium

PET C/aluminium

Max. air volume flow

150 m

³

/h

150 m

³

/h

Nominal flow

70 … 115 m

³

/h

70 … 115 m

³

/h

Remaining delivery pressure at max.
air volume flow

130 Pa

130 Pa

Specific power consumption at max.
nominal flow and external compres-
sion

0.4 W/(m

3

/h) at

115 m

3

/h, 100 Pa

0.4 W/(m

3

/h) at

115 m

3

/h, 100 Pa

Specific power consumption in ac-
cordance with the Passivhaus Institut
(Passive House Institute)

0.4 W/(m

3

/h) at

115 m

3

/h, 100 Pa

0.4 W/(m

3

/h) at

115 m

3

/h, 100 Pa

Ourdoor air filter class (in accordance
with EN 779)

F7/F9

F7/F9

Ourdoor air filter class (in accordance
with ISO 16890)

ISO ePM2,5
70%/ISO ePM1,0
85%

ISO ePM2,5
70%/ISO ePM1,0
85%

Extract air filter class (in accordance
with EN 779)

G4

G4

Extract air filter class (in accordance
with ISO 16890)

ISO Coarse

ISO Coarse

Filter surface

0.5 m

²

0.5 m

²

Thermal efficiency in accordance with
EN 13141-7

82 %

82 %

Summary of Contents for recoVAIR VAR 150/4 L

Page 1: ...maintenance instructions recoVAIR VAR 150 4 L VAR 150 4 R AT CH de DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de...

Page 2: ...n element 12 5 3 Connecting the bypass 12 5 4 Connecting the VR 32 bus coupler 12 5 5 Connecting the product to the power supply in a fixed installation 13 6 Operation 13 6 1 Operating concept 13 6 2...

Page 3: ...nd main tenance conditions listed in the instruc tions Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any dire...

Page 4: ...lled by at least two people When installing the product secure it against toppling or falling over 1 3 5 Access to the mains plug circuit breaker must be guaranteed Ensure that the mains plug circuit...

Page 5: ...nit 3 1 Symbols on the product Symbol Meaning Opening for the outdoor air filter Opening for the exhaust air filter 3 2 Design 3 2 1 VAR 150 4 R 1 2 3 4 5 6 7 8 15 14 13 12 11 10 9 1 Exhaust air filte...

Page 6: ...flow TMAX Max operating temperature Bar code with serial number The 7th to 16th digits of the serial number form the article number 3 4 CE label The CE label shows that the products comply with the ba...

Page 7: ...ion clear ances when installing on the ceiling 600 400 600 1 Observe the minimum clearances and installation clear ances when installing on the wall Plan sufficient space for installing the ventilatio...

Page 8: ...nd the product If the opening for the exit air pipeline is too close to the inlet opening of the outside air pipeline the exit air can recircu late Prevent exit air from being sucked in directly throu...

Page 9: ...n Risk of material damage caused by con densate If the condensate cannot drain from the product this may damage the product Install the product such that the side of the product with the condensate dr...

Page 10: ...of damage to health caused by incor rectly connected condensate drain pipe work In the interests of hygiene the condensate drain pipework must not be directly connec ted to the waste water piping Con...

Page 11: ...by a missing seal If the pipelines are not connected to the product in way that is vapour diffusion tight condensate may form and damage the product Seal all of the connections for the pipelines to e...

Page 12: ...BUS connection in the con nection area for external components of the product System control installation instructions Connection type eBUS line Controller Compatibility as of VRC 470 4 If the DCF sig...

Page 13: ...verview of the read off and setting options for the in staller level can be found in the Installer level Overview table in the appendix Installer level Overview Page 19 6 2 Calling up the installer le...

Page 14: ...in accordance with the building 0 2 2 5 7 2 13 Recording contact details If you want you can store your telephone number max 16 digits with no spaces in the menu If the telephone number is shorter tha...

Page 15: ...nt options 1 Small wall unit air volume flow 260 m h 2 Large wall unit air volume flow 360 m h 3 Ceiling unit air volume flow 150 m h L variant 4 Ceiling unit air volume flow 150 m h R variant 8 1 Sys...

Page 16: ...rmitted for the product 10 2 Mains connection line defective If the unit s mains connection line is damaged the mains connection line must be replaced by the manufacturer or their customer service dep...

Page 17: ...ating days 182 d Replacement interval reached At least twice annually Replace the filters Exhaust air filter class G4 in accordance with EN 779 ISO Coarse in accordance with ISO 16890 Outdoor air filt...

Page 18: ...ndeckende Kundendienst f r ganz sterreich ist t glich von 0 bis 24 Uhr erreichbar Vaillant Kundendienst techniker sind 365 Tage f r Sie unterwegs sonn und feier tags sterreichweit Applicability Switze...

Page 19: ...el Test menu Check programmes P 01 Bypass test optional Yes No No P 02 Test Frost prot element op tional Yes No No P 03 Initialisation measure Yes No No P 04 System efficiency test Yes No No Installer...

Page 20: ...lable Not avail able Diff temp bypass 0 25 0 5 10 Pressure monitor Not available Available Not avail able Step switch Not available Available Not avail able Air quality sensor 0 2 1 0 Min CO2 content...

Page 21: ...fan does not work is defective Check that the supply air fan works correctly F 804 Supply air temp too low Bypass does not work is defect ive 1 Press the fault clearance key Fault clearance attempts 3...

Page 22: ...power cut Wait until the mains voltage has been re established and the product automatically switches on all settings are retained Frost protection active mains voltage present 1 Check whether S 815 i...

Page 23: ...supply air and exhaust air lines are too close to each other Increase the distances between the openings for the supply air and exhaust air lines Noise transmission between the rooms No T supersonic...

Page 24: ...vailable 684 W 684 W Current consumption 0 37 A 0 37 A Minimum cross section of the supply line 1 5 mm 1 5 mm Protection class 1 1 Level of protection IP10B IP10B Air connection area diameter internal...

Page 25: ...Institute for Civil Engineer ing 84 84 Frost protection mode active prevents freezing and thaws condensate 3 3 Max operating temperature 40 40 Sound power level level 1 at 16 Pa 44 dB A at 46 m 3 h 4...

Page 26: ......

Page 27: ......

Page 28: ...n aus dem Mobilfunknetz ggf abweichende Tarife n here Information erhalten Sie bei Ihrem Mobilnetzbetreiber info vaillant at termin vaillant at www vaillant at www vaillant at werkskundendienst Vailla...

Reviews: