VWS
Description
Unit
VWS 220/2
VWS 300/2
VWS 380/2
VWS 460/2
Article number
-
0010002797
0010002798
0010002799
0010002800
Height without connections
Width
Depth without pillars
Depth with pillars
mm
mm
mm
mm
1200
760
900
1100
Weight
- with packaging
- without packaging
- ready for operation
kg
kg
kg
356
326
341
370
340
359
394
364
386
417
387
414
Rated voltage
- Compressor
- Brine pump
- Heating circuit pump
- Control circuit
- External auxiliary heating
-
3/N/PE 400 V 50 Hz
1/N/PE 230 V 50 Hz
3/N/PE 400 V 50 Hz
1/N/PE 230 V 50 Hz (max. 1 x 2 A)
1/N/PE 230 V 50 Hz
3/N/PE 400 V 50 Hz (max. 3 x 13 A)
Fuse, slow-blow
A
20
25
32
40
Start-up current
- without start-up current limiter
- with start-up current limiter
A
A
99
44
127
65
167
85
198
110
Electrical power consumption/rated output
- min. for B-5W35
- max. for B20W60
- phase angle, cos phi
- external auxiliary heating
kW
kW
-
kW
4.9
10.0
0.7-0.84
6.6
12.0
0.72-0.83
8.5
16.0
0.76-0.86
10.2
18.0
0.75-0.86
3 x 3 (3 x 13 A)
EN 60529 level of protection
-
IP 20
Hydraulic connections
- Heating circuit flow and return
- Heat source flow and return
mm
mm
G 1 1/2"
G 1 1/2"
Heat source circuit (brine circuit)
- Brine type
- max. operating pressure
- min. inlet temperature
- max. inlet temperature
-
MPa (bar)
°C
°C
Ethylene glycol 30 %
0.3 (3)
-10
20
- Nominal flow rate dT 3 K
- Residual head dT 3 K
- Nominal flow rate dT 4 K
- Residual head dT 4 K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
4858
324
3644
468
390
6660
275
4995
439
390
8640
431
6480
655
585
9840
379
7380
626
585
CH circuit
- max. operating pressure
- min. flow temperature
- max. flow temperature
MPa (bar)
°C
°C
0.3 (3)
25
62
- Nominal flow rate dT 5 K
- Pressure loss dT 5 K
- Nominal flow rate dT 10 K
- Pressure loss dT 10 K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
3726
72
1902
23
5160
87
2580
25
6600
132
3336
40
7680
173
3900
53
refrigerant circuit
- Coolant type
-
R 407 C
- Quantity
kg
4.1
5.99
6.7
8.6
- Permissible operating overpressure
- Compressor type
- Oil
- Oil filling capacity
MPa (bar)
-
-
l
2.9 (29)
Scroll
Ester
4
4
4.14
4.14
Table 7.1 Technical Data VWS