Troubleshooting
42
Operating instructions geoTHERM 0020051578_03
5
Fault code
Fault text/description
Emergency
mode
32
Error heat source outlet sensor T8
Short circuit in sensor.
possible
33
Error in pressure sensor
Short circuit in pressure sensor
not possi-
ble
34
(VWS only)
Error in pressure sensor
Short circuit in pressure sensor
possible
40
Error comp outlet sensor T1
Short circuit in sensor
possible
41
Error heat source inlet sensor T3
Short circuit in sensor.
possible
42
Error HP return sensor T5
Short circuit in sensor.
possible
43
Error HP flow sensor T6
Short circuit in sensor.
possible
44
Error external sensor AF
Short circuit in sensor.
possible
45
Error DHW tank sensor SP
Short circuit in sensor.
possible
46
Error HB flow sensor VF1
Short circuit in sensor.
possible
47
Error HB return sensor RF1
Short circuit in sensor.
possible
48
Error flow sensor VF2
Short circuit in sensor.
Hot water
handling
possible
52
Sensors do not match hydraulic
scheme
_
60
Heat source frost protect source
outlet monitoring
Error 20 has occurred three times
in a row.
possible
61
(VWW only)
Heat source frost protect source
outlet monitoring
Error 21 has occurred three times
in a row.
possible
62
(VWS only)
Heat source frost protect source
outlet monitoring
Error 22 has occurred three times
in a row.
possible
5.3
Fault with permanent lock-out
Fault code
Fault text/description
Emergency
mode
63
(VWW only)
No ground water flow
Error 23 has occurred three times
in a row.
possible
72
CH flow temperature too high for
floor heating
Flow temperature higher than set
value for 15 min. Sensor or controller
defective.
_
81
Refrigerant pressure too high
Error 27 has occurred three times
in a row.
possible
83
Refrigerant pressure too low;
check heat source.
Error 28 has occurred three times
in a row.
possible
84
Refrigerant pressure outside the
range
Error 29 has occurred three times
in a row.
possible
85
Error CH pump
Short circuit or dry run
_
86
Failure brine pump
Short circuit or dry run.
possible
90
System pressure too low
Pressure <0.5 bar
Heat pump shuts down and restarts
automatically when the pressure
rises above 0.7 bar
_
91
(VWS only)
Brine pressure too low
Pressure < 0.2 bar
Heat pump shuts down and goes into
operation automatically when the
pressure rises above 0.4 bar
possible
94
One or two phases are missing
One or more lines missing.
possible
95
Incorrect direction of rotation,
correct the comp. phase sequence
Phase sequence incorrect.
possible
96
Error pressure sensor
Refrigerant circuit
Short circuit in pressure sensor
possible
5.3
Fault with permanent lock-out