![Vaillant Flue pipe Installation Manual Download Page 7](http://html1.mh-extra.com/html/vaillant/flue-pipe/flue-pipe_installation-manual_3179689007.webp)
7
Installation manual flue pipe for ecoCRAFT 0020058722_03
Appliance type
Minimum
shaft cross-section
Maximum total pipe length (L
1
+ L
2
+ L
3
)
DN 130
DN 140
DN 150
DN 200
ecoCRAFT VKK GB 806/3-E-H
round: DN+60 mm
square DN+40 mm
27.2
34.7
43.6
-
round: DN+80 mm
square: DN+60 mm
30.0
30.0
50.0
-
ecoCRAFT VKK GB 1206/3-E-H
round: DN+60 mm
square DN+40 mm
10.0
12.4
15.0
-
round: DN+80 mm
square: DN+60 mm
24.0
30.0
44.6
-
round: DN+100 mm
square: DN+80 mm
30.0
30.0
50.0
-
ecoCRAFT VKK GB 1606/3-E-H
round: DN+60 mm
square DN+40 mm
8.0
9.8
11.8
-
round: DN+80 mm
square: DN+60 mm
18.2
24.3
31.3
-
round: DN+100 mm
square: DN+80 mm
28.4
30.0
50.0
-
ecoCRAFT VKK GB 2006/3-E-H
round: DN+60 mm
square DN+40 mm
-
-
-
14.1
round: DN+80 mm
square: DN+60 mm
-
-
-
44.9
round: DN+100 mm
square: DN+80 mm
-
-
-
50.0
ecoCRAFT VKK GB 2406/3-E-H
round: DN+60 mm
square DN+40 mm
-
-
-
9.3
round: DN+80 mm
square: DN+60 mm
-
-
-
28.1
round: DN+100 mm
square: DN+80 mm
-
-
-
50.0
round: DN+120 mm
square: DN+100 mm
-
-
-
50.0
ecoCRAFT VKK GB 2806/3-E-H
round: DN+60 mm
square DN+40 mm
-
-
-
6.5
round: DN+80 mm
square: DN+60 mm
-
-
-
19.3
round: DN+100 mm
square: DN+80 mm
-
-
-
43.4
round: DN+120 mm
square: DN+100 mm
-
-
-
50.0
Maximum length of horizontal pipes: each 4 m air pipe plus 2 x 87° elbows and 4 m flue gas pipe plus 2 x 87° elbows
Minimum diameter of the air supply pipe 150 mm
Table 4.2 Maximum total pipe length
(combustion air from the shaft)
System - certifi ed fl ue pipe - open fl ued 4