Installation manual flue pipe for ecoCRAFT 0020058722_03
4
a
Caution!
Risk of corrosion in the flue gas installation!
The combustion air fed to the unit must be free
of chemicals which contain, e.g. fluorine, chlo-
rine or sulphur. Sprays, release or cleaning
agents, paints and adhesives can contain such
materials which can, in certain circumstances,
lead to corrosion when operating the unit, in-
cluding the exhaust gas installation. The ex-
haust ducting may only be installed using the
corresponding parts from Vaillant.
Caution!
Electronic damage and danger of fire by
lightning strike!
If the building is equipped with a lightning con-
ductor system, the flue pipes must be incorpo-
rated in the lightning protection system. The
vertical ducting must be incorporated in the po-
tential balancing system if it contains metallic
components.
Caution!
Malfunction of the unit by obstruction of the
flue gas flow!
Make sure that, during the installation process,
no swarf, mortar remnants etc. are left in the
flue pipes.
Caution!
Malfunctions and water condensate escape as a
result of leaks in the exhaust gas route!
The gaskets are sensitive to mineral oil based
greases. They must therefore not be greased.
Only use water to facilitate the assembly, if re-
quired.
Caution!
Danger of fire!
Outside the ducting, the exhaust pipe must be
at least 5 cm away from combustible building
components.
3.2 Regulations
For installation of the appliance laws, regulations, tech-
nical rules and standards must be considered and ad-
hered to ensure the safe installation of your appliance.
3.2.1
Regulations (Great Britain and Eire)
Attention shall be made to the regulations, guidelines
and standards in force. In particular reference shall be
given to the following regulations, guidelines, standards
and rules:
- The electrical connections to the boiler MUST be in ac-
cordance with the I.E.E Wiring Regulations, and tested
accordingly.
- The Clean Air Act 1993 and the 3rd Edition of the 1956
Clean Air Act.
- The Building Regulations England and Wales,
The Building Standards Scotland and any require-
ments determined by the local authorities within.
- Water supply (water fittings) regulations 1999
Detailed recommendations are also contained in the fol-
lowing documents:
BS 5854
Code of practice for flues and flue structures
in buildings.
BS EN 12828
Design for water-based heating systems.
BS 6644
Specification for Installation of gas-fired hot
water boilers of rated inputs between 70 kW (net) and
1.8 MW (net) (2nd and 3rd familygases).
BS 6880
Code of practice for low temperature heating
systems of output greater than 45 kW.
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and maintenance.
BS 6981
Installation of low pressure gas pipework of up
to 28 mm in domestic premises.
BS 7074
Application selection and installation of ex-
pansion vessels and ancillary equipment for sealed
water systems.
Part 1 Code of practice for domestic heating and hot
water.
Part 2 Code of practice for low and medium tempera-
ture hot water systems.
BS 6700
Specification for design, installation, testing
and maintenance of services supplying water for domes-
tic use within buildings and their curtilages.
Institute of Gas Engineers Publications
IGE/UP/1
Soundness testing and purging of industrial
and commercial gas installations.
IGE/UP/1A
Soundness testing and purging of small low
pressure industrial and commercial natural gas installa-
tions.
IGE/UP/10
Installation of gas appliances in industrial
and commercial premises.
Part 1 Flued appliances