5 Set-up
12
Installation and maintenance instructions flexoTHERM exclusive 0020196687_03
Information on the data plate
Meaning
Read the instructions
Tested for safety by the
Verband deutscher Elektro-
techniker (German Associ-
ation for Electrical, Electronic
& Information Technologies)
Electromagnetic Compatib-
ility in accordance with the
Verband deutscher Elektro-
techniker
4.3
Explanation of product stickers
Symbol on the sticker
Meaning
Heating flow connection
Heating return connection
Heating diaphragm expan-
sion tank connection
A
Connection from the heat
source to the heat pump (hot
brine)
B
Connection from the heat
pump to the heat source
(cold brine)
Brine heat source
Energy supply company anti-
cycling time
4.4
Type designation and serial number
The type designation and serial number can be found on
a plate behind the front flap and on the main identification
plate. The 7th to 16th digits of the serial number form the
article number.
4.5
CE label
The CE label shows that the products comply with the basic
requirements of the applicable directives as stated on the
identification plate.
The declaration of conformity can be viewed at the manufac-
turer's site.
5
Set-up
5.1
Checking the scope of delivery
1.
Carefully remove the packaging and padding without
damaging the parts of the product.
2.
Check that the scope of delivery is complete.
Quantity
Description
1
Heat pump
1
Installation set comprising
–
3 x flat seal (yellow/green) for heating
circuit
–
1 x 3/4" flat seal for the heating expansion
vessel connection
–
2 x O-ring seals for brine circuit
1
Expansion relief valve for brine circuit, 1/2",
3 bar
1
Enclosed documentation
5.2
Selecting the installation site
▶
Select a dry room that is frost-proof throughout and in
which the maximum installation height is not exceeded
and the environmental temperature is neither above nor
below the permitted range.
–
Permissible ambient temperature: 7 … 25
℃
–
Permissible relative air humidity: 40 … 75 %
▶
Ensure that the installation room has the required min-
imum volume.
Heat pump
R 410 A refriger-
ant filling volume
Minimum installa-
tion room volume
VWF 57/4
1.50 kg
3.41 m
³
VWF 87/4
2.40 kg
5.45 m
³
VWF 117/4
2.50 kg
5.68 m
³
VWF 157/4
3.05 kg
6.93 m
³
VWF 197/4
3.95 kg
8.98 m
³
▶
Ensure that the required minimum clearances can be
maintained.
▶
When selecting the installation site, you must take into
consideration that when the heat pump is in operation, it
will transfer vibrations to the floor and any nearby walls.
▶
Ensure that the floor is level and has sufficient load-bear-
ing capacity to bear the weight of the heat pump and a
domestic hot water cylinder.
▶
Ensure that cables can be easily routed (for brine, do-
mestic hot water and heating).