0020308120_02 Air/flue pipe installation manual
21
5.6.4.5 Routing extensions for the variable terminal
set around eaves
min. 100 mm
When installing the variable terminal set around eaves, ad-
ditional M8 threaded rods are required for the pipe clamps.
The threaded rods are commercially available.
▶
If required, install additional 45° elbows.
5.7
Horizontal wall/roof duct,
60/100 mm diameter (article number 303933,
0010035512)
5.7.1
Scope of delivery
754
48
30
65
65
2
3
5
4
1
1
Wall collar, 100 dia-
meter (2 pcs)
2
Horizontal wall/roof duct
3
48 mm clamp
4
87° elbow
5
30 mm clamp
5.7.2
Shortening the air/flue pipe
87
87
A
A
B
1.
2.
1.
Flue system to the rear
2.
Flue system to the side
A
Clearance to the ex-
ternal wall
B
Clearance to the in-
ternal wall: 125 mm
1.
Measure the clearance
(A)
from outside of the wall to
the centre of the connector.
13 mm
A + 22 mm
2.
Remove the flue pipe from the air pipe.
3.
Shorten the flue pipe and the air pipe by the same
amount.
Condition
: Additional extensions and elbows required
▶
Install the extensions. (
–
All of the sleeves for the flue pipe must point towards
the terminal.
▶
Install the elbows (
5.7.3
Installing the wall duct
87
13
1
3°
1.
Drill a hole.