42
Installation and maintenance instructions ecoTEC exclusive 0020193966_04
Appendix
A
Inspection and maintenance work
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed. Each time inspection and maintenance work is carried out, carry out the required preparatory and com-
pletion work.
#
Maintenance work
Interval
1
Record all of the analysis results in the Benchmark Checklist in these
instructions
Annually
2
Ask the end user whether any significant problems occur when operating
the product
Annually
3
Use the diagnostics system to check the product's fault history
Annually
4
Visually inspect whether the air/flue pipe and its opening have been in-
stalled correctly in accordance with the set-up instructions
Annually
5
Check that the unit has been installed correctly and the connections have
been secured
Annually
6
Check that the condensate pipe is in good condition, that it is leak-tight
and that the drain is correct
Annually
7
Check whether all of the externally routed condensate pipes are dimen-
sioned correctly and have been insulated sufficiently (frost protection)
Annually
8
Check whether the gas flow rate corresponds with the specifications on
the data plate and lies within the tolerances specified in these instructions
Annually
9
If the gas flow rate lies outside of the tolerances specified in these in-
structions, eliminate the fault in accordance with the regulations and the
current technology
Annually
10
Check the general condition of the product and, if required, eliminate any
faults that are found
Annually
11
Calibrating the heat generator and measuring the CO/CO
₂
content and
gas flow in heating mode
Annually
12
Logging the CO
₂
content (air ratio) and CO/CO
₂
ratio
Annually
13
Check the product's recirculation at the supply air test point on the air/flue
pipe. If required, inspect the entire air/flue system and, if necessary, cor-
rect the fault
Annually
14
Disconnect the product from the electrical installation
Annually
15
Checking the electrical plug connections
Annually
16
Removing dirt from the product and the vacuum chamber
Annually
17
Visually check the heat cell to ascertain its condition and detect any
leaks, corrosion, rust or damage, and carry out maintenance work, if
required
Annually
18
Check that the gas stopcock and service valves function correctly
Annually
19
Checking the quality of the heating water
Annually
20
Removing the compact thermal module
at regular intervals
21
Checking the burner
at regular intervals
22
Checking the insulating mats in the combustion area and replacing dam-
aged insulating mats
at regular intervals
23
Cleaning the heat exchanger
at regular intervals
24
Clean the condensate siphon and check the condensate discharge pipe
Annually
25
Installing the compact thermal module
at regular intervals
26
Checking the pre-charge pressure for the internal expansion vessel
at regular intervals
27
Reassemble the product
After each time maintenance
work is carried out
28
Opening the service valves
Annually
29
Filling the heating installation
Annually
30
Run the test operation on the product/heating installation including hot
water generation (if available) and, if required, purge the product/heating
installation
Annually
31
Completing inspection and maintenance work
Annually
32
Checking the gas type
Annually