11 Inspection and maintenance
24
Installation and maintenance instructions ecoFIT pure 0020230533_01
10.5.9 Replace the pressure sensor
1
2
1.
Pull out the plug.
2.
Remove the clip
(1)
.
3.
Remove the pressure sensor
(2)
.
4.
Install the new pressure sensor.
5.
Reattach the clip
(1)
.
10.6
Checking the product for leak-tightness
▶
Check that the product is leak-tight. (
→
Page 18)
11 Inspection and maintenance
11.1
Using original seals
If you replace components, use only the enclosed original
seals; additional sealing materials are not required.
11.2
Observing inspection and maintenance
intervals
▶
Comply with the minimum clearances for the inspection
and maintenance. Depending on the results of the in-
spection, it may be necessary to bring maintenance work
forward.
Inspection and maintenance work
–
Overview
(
→
Page 37)
11.3
Procuring spare parts
The original components of the product were also certified
by the manufacturer as part of the declaration of conformity.
If you use other, non-certified or unauthorised parts during
maintenance or repair work, this may void the conformity of
the product and it will therefore no longer comply with the
applicable standards.
We strongly recommend that you use original spare parts
from the manufacturer as this guarantees fault-free and safe
operation of the product. To receive information about the
available original spare parts, contact the contact address
provided on the reverse of these instructions.
▶
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the
product.
11.4
Checking the CO
₂
content
1.
Start up the product with check programme
(P.01)
.
2.
Wait until the value that is read is stable.
–
Waiting period for reading a stable value: 5 min
1
3.
Unscrew the cover from the flue gas analysis point
(1)
.
4.
Measure the CO
₂
content at the flue gas analysis point
(1)
.
5.
Compare the measured value with the corresponding
value in the table.
Checking the CO
₂
content
Great Bri-
tain
Removed
front cas-
ing/installed
front casing
Natural gas
G20
9.2
±
1 %
◁
The value is OK.
▽
The value is not OK; you cannot start up the
product.
▶
Set the CO
₂
content.
11.5
Setting the CO
₂
content
Conditions
: The CO
₂
content must be adjusted
1
A
B
▶
Remove the sticker.
▶
Turn the screw
(1)
to set the CO
₂
content (value with
front casing removed).
◁
To increase the CO
₂
content: Turn anti-clockwise
◁
To decrease the CO
₂
content: Turn clockwise
▶
Only carry out the adjustment in increments of 1/8 turn
and wait approximately 1 minute after each adjustment
until the value has stabilised.