8 Adapting the unit to the heating installation
30
Installation and maintenance instructions ecoCOMPACT 0020181421_04
Note
The bypass valve remains inoperative as
the pump speed is not sufficient to open
it (provided the factory settings remain
unchanged).
Note
If the "Pump speed target value = fixed (
Δ
p
Limit)" pump operating mode is selected, the
product's maximum heat output is automatic-
ally no longer available. The relevant nominal
output is adapted to the hydraulic potential of
this pump speed at the factory.
Characteristic line for proKlima (25 kW)
30
35
40
25
20
15
10
5
0
500
1000
1500 A
B
1
2
3
4
1
Bypass
closed/Vmax/code
d14=6
2
Bypass in factory set-
ting/Vmax/code d14=6
3
Bypass
closed/Vmax/code
d14=6
4
Bypass open/Vmin/code
d14=6
A
Throughput in circuit
(l/h)
B
Available pressure
(kPa)
Changes must be made during the installation for the proK-
lima or KfW label.
Setting for proKlima
Note
On 25 kW units, the bypass must not be replaced
with the proKlima plug.
▶
Set
D.014
to 6 (= auto (
Δ
p limit)).
▶
Set
D.122
to 200 or a lower value (= maximum hydraulic
pressure difference
≤
200 mbar).
◁
The hydraulic pressure difference with respect to the
heating system is limited to the set value (see dia-
gram).
Note
When starting up the product or after switching
on the power supply, this pump setting does
not take effect until after the burner has run for
the first time.
Setting for KfW
▶
Set
D.014
to 7 (= fixed (
Δ
p Limit)).
Conditions
: The hydraulics in the heating system or the heating sys-
tem itself is suitable for this type of pump operation.
–
The pump is only operated at this pump speed.
The hydraulic power of the pump for transferring
the heat output is limited.
◁
The pump is permanently set to a lower pump speed
with a maximum feed head of 200 mbar.
Note
If the heating system is not suitable for this
type of pump operation, this can lead to in-
sufficient supply to the product and to safety
shutdowns.
▶
Make sure that there is a guaranteed minimum flow of
heating water via the heating system to transfer the heat
output.
Note
The bypass valve remains inoperative as
the pump speed is not sufficient to open
it (provided the factory settings remain
unchanged).
Note
If the "Pump speed target value = fixed (
Δ
p
Limit)" pump operating mode is selected, the
product's maximum heat output is automatic-
ally no longer available. The relevant nominal
output is adapted to the hydraulic potential of
this pump speed at the factory.
8.8.3
Setting the bypass valve
Applicability:
Belgium
OR Austria
The pressure can be adjusted in a range between 17 kPa
(0,17 bar) and 35 kPa (0,35 bar). The default value is ap-
prox. 30 kPa (0,30 bar) (mid-position).
The pressure changes by approximately 1 kPa (0,01 mbar)
each time the adjusting screw is rotated. The pressure is
increased by turning clockwise and decreased by turning
anti-clockwise.
Caution.
Risk of material damage caused by incor-
rect setting of the high-efficiency pump
If the pressure at the bypass valve is in-
creased (by turning it clockwise) and the
pump output is set to less than 100%, the
product may not operate correctly.
▶
In this case, set the pump output to
5
(100%) using diagnostics code
D.014
.
▶
Remove the front casing. (
→
Page 12)