For the fitter
V 7-025NWV 7-035NW
Installation Manual
Air-conditioner - climaVAIR
Split Type
EN
Page 1: ...For the fitter V 7 025NW V 7 035NW Installation Manual Air conditioner climaVAIR Split Type EN...
Page 2: ...ssembly Plate 9 9 3 Installation of the Pipes 10 9 3 1 Methods for the Correct Discharge of the Condensed Water 10 9 3 2 Handling the Coolant Pipes 10 9 3 3 Handling the Condensed Water Pipe 11 9 3 4...
Page 3: ...s installation manual Note Keep the manuals throughout the service life of the unit Note The information relating to this unit is divided between two manuals installation manual and user manual 2 Extr...
Page 4: ...ts Legend 1 Indoor Unit 2 Outdoor Unit 3 Remote controller and holder 4 Connections and channels 5 Condensed water drainage pipe 5 1 Indoor Unit The indoor unit provides acclimatised air inside the ro...
Page 5: ...tdoor unit are shown on Figure 5 3 and Table 5 2 depending on the model please consult the model nameplate The dimensions are given in mm Fig 5 3 Dimensions of the outdoor unit Legend H Height L Lengt...
Page 6: ...the water to be properly discharged which condenses during the normal operation of the unit Electric connections they supply electric energy to the unit 5 5 Accessories This unit is provided with the...
Page 7: ...10 Outdoor Unit Air Flow volume m3 h 1800 2100 Sound Power level dB A 58 55 Sound Pressure level dB A 50 50 Refrigerant R410A Refrigerant charge gr 700 1000 Compressor type Rotary Expansion system Ca...
Page 8: ...dispose of it without the proper controls 8 Installation 8 1 Qualification of the Installation Personnel Ensure that this unit is installed by authorised personnel The personnel authorised by Vaillant...
Page 9: ...l the indoor unit close to the ceiling Choose a mounting site that will allow air to reach all parts of the room evenly Avoid beams installations or lights which obstruct the airflow Install the indoo...
Page 10: ...nger of burns and eye injuries In the event of soldering use suitable protection equipment protective soldering mask soldering gloves solderer clothing Warning Danger of breakdowns or malfunction Dang...
Page 11: ...pe is installed in a room fit thermal insulation Avoid installing the condensed water pipe with an ascending bend see Figure 9 2 Fig 9 2 Avoid ascending bends Avoid installing the condensed water pipe...
Page 12: ...h the condensed water pipe through the hole Seal the hole properly after installing the pipes Carefully bend the installation pipe in the right direction Warning Danger of breakdowns or malfunction Da...
Page 13: ...ecured In the event that the body does not slot into the supports properly repeat this process 10 Installation of the Outdoor Unit 10 1 Selecting the Assembly Location Danger of personal injury and ma...
Page 14: ...rtical position At heights exceeding 7 5 m An additional oil deposit should be installed at each 7 5 m interval to collect the oil and suction it returning it to the outdoor unit and An elbow can be i...
Page 15: ...of electric shock Before connecting the unit to the electric supply line ensure that the line is not live Danger Danger of electric shock If the mains cable is damaged it must be replaced by the manu...
Page 16: ...a 32 A fusing point Check that no other equipment is connected to this power supply line Note For more detailed information on the electric installation please consult the Technical Connection Conditi...
Page 17: ...f the electrical connections in the outdoor unit Loosen the screws in the bushing block and fully insert the cable terminals of the power supply line in the bushing block and tighten the screws Warnin...
Page 18: ...er INTERCONNECT INTERCONNECT Interconnect section up to 2 meter 1 1 Interconnect section up to 25 meter 1 5 1 5 Indoor Unit section up to 2m PLUG PLUG Indoor Unit section up to 25m 1 5 1 5 Thermal mag...
Page 19: ...r and remove the nitrogen cylinder Release the pressure from the system by slowly opening the faucets In the event of detecting leaks repair them and repeat the test 12 2 Purging the Installation 12 2...
Page 20: ...et Open the two way valve by twisting the rod 90 anticlockwise and close it after 6 seconds The installation will be filled with coolant Check the installation again for tightness If there are leaks s...
Page 21: ...a suction pump and a recycling bottle Warning Never dump coolant into the environment Coolant is a harmful product for the environment Check the flaring joins Repair the leak replace indoor and outdoo...
Page 22: ......