0020297933_07 Installation and maintenance instructions
89
VWL 35/6 A 230V
S2
VWL 55/6 A 230V
S2
VWL 65/6 A 230V
S2
VWL 75/6 A 230V
S2
Power consumption, A7/W55
7.70 A
7.70 A
7.60 A
7.70 A
Heat output, A7/W65
4.50 kW
4.50 kW
6.30 kW
6.30 kW
Coefficient of performance, COP, EN 14511,
A7/W65
2.30
2.30
2.30
2.30
Power consumption, effective, A7/W65
1.96 kW
1.96 kW
2.74 kW
2.74 kW
Power consumption, A7/W65
9.00 A
9.00 A
12.20 A
12.20 A
Heat output, A-7/W35
3.60 kW
5.40 kW
5.40 kW
7.00 kW
Coefficient of performance, COP, EN 14511, A-
7/W35
2.70
2.60
3.00
2.80
Power consumption, effective, A-7/W35
1.33 kW
2.08 kW
1.80 kW
2.50 kW
Power consumption, A-7/W35
6.10 A
10.00 A
8.10 A
11.50 A
Technical data
–
Power, cooling mode
Validity:
Product with cooling mode
VWL 35/6 A 230V
S2
VWL 55/6 A 230V
S2
VWL 65/6 A 230V
S2
VWL 75/6 A 230V
S2
Cooling output, A35/W18
4.50 kW
4.50 kW
6.40 kW
6.40 kW
Energy efficiency ratio, EER, EN 14511,
A35/W18
4.30
4.30
4.20
4.20
Power consumption, effective, A35/W18
1.05 kW
1.05 kW
1.52 kW
1.52 kW
Power consumption, A35/W18
4.90 A
4.90 A
7.00 A
7.00 A
Cooling output, minimum/maximum, A35/W7
1.80 to 5.20 kW
1.80 to 5.20 kW
2.50 to 7.20 kW
2.40 to 7.20 kW
Cooling output, A35/W7
3.40 kW
3.40 kW
5.00 kW
4.90 kW
Energy efficiency ratio, EER, EN 14511,
A35/W7
3.40
3.40
3.50
3.50
Power consumption, effective, A35/W7
1.00 kW
1.00 kW
1.43 kW
1.40 kW
Power consumption, A35/W7
4.70 A
4.70 A
6.60 A
6.60 A
Technical data
–
Power in noise reduction mode, heating mode
VWL 35/6 A 230V
S2
VWL 55/6 A 230V
S2
VWL 65/6 A 230V
S2
VWL 75/6 A 230V
S2
Heat output, EN 14511, A-7/W35, 40% noise
reduction mode
3.40 kW
3.40 kW
3.80 kW
3.80 kW
Coefficient of performance, COP, EN 14511, A-
7/W35, noise reduction mode 40%
3.00
3.00
3.00
3.00
Power consumption, effective, EN 14511, A-
7/W35, 40% noise reduction mode
1.13 kW
1.13 kW
1.27 kW
1.27 kW
Heat output, EN 14511, A-7/W35, 50% noise
reduction mode
2.70 kW
2.70 kW
2.70 kW
2.70 kW
Coefficient of performance, COP, EN 14511, A-
7/W35, noise reduction mode 50%
2.90
2.90
2.60
2.60
Power consumption, effective, EN 14511, A-
7/W35, 50% noise reduction mode
0.93 kW
0.93 kW
1.04 kW
1.04 kW
Heat output, EN 14511, A-7/W35, 60% noise
reduction mode
2.20 kW
2.20 kW
2.50 kW
2.50 kW
Coefficient of performance, COP, EN 14511, A-
7/W35, noise reduction mode 60%
2.90
2.90
2.60
2.60
Power consumption, effective, EN 14511, A-
7/W35, 60% noise reduction mode
0.76 kW
0.76 kW
0.96 kW
0.96 kW
Technical data
–
Noise emissions, heating mode
VWL 35/6 A 230V
S2
VWL 55/6 A 230V
S2
VWL 65/6 A 230V
S2
VWL 75/6 A 230V
S2
Sound power, EN 12102, EN 14511 LWA,
A7/W35
51 dB(A)
51 dB(A)
53 dB(A)
53 dB(A)
Sound power, EN 12102, EN 14511 LWA,
A7/W45
53 dB(A)
53 dB(A)
53 dB(A)
53 dB(A)