90
Installation and maintenance instructions 0020326637_00
Technical data
–
Heating circuit
VWL 105/6 A
230V S2
VWL 105/6 A S2
VWL 125/6 A
230V S2
VWL 125/6 A S2
Heating water temperature, minimum/maximum
20 … 75
℃
20 … 75
℃
20 … 75
℃
20 … 75
℃
Basic length of the heating water pipe, max-
imum, between the outdoor unit and indoor
unit
20 m
20 m
20 m
20 m
Operating pressure, minimum
0.05 MPa
(0.50 bar)
0.05 MPa
(0.50 bar)
0.05 MPa
(0.50 bar)
0.05 MPa
(0.50 bar)
Operating pressure, maximum
0.30 MPa
(3.00 bar)
0.30 MPa
(3.00 bar)
0.30 MPa
(3.00 bar)
0.30 MPa
(3.00 bar)
Volume flow, minimum
995 l/h
995 l/h
995 l/h
995 l/h
Volume flow, maximum
2,065 l/h
2,065 l/h
2,065 l/h
2,065 l/h
Water volume, in the outdoor unit
2.5 l
2.5 l
2.5 l
2.5 l
Water volume, in the heating circuit, minimum,
thawing mode, activated/deactivated back-up
heater
45 l / 150 l
45 l / 150 l
45 l / 150 l
45 l / 150 l
Remaining feed pressure, hydraulic
55.0 kPa
(550.0 mbar)
55.0 kPa
(550.0 mbar)
55.0 kPa
(550.0 mbar)
55.0 kPa
(550.0 mbar)
Technical data
–
Refrigerant circuit
VWL 105/6 A
230V S2
VWL 105/6 A S2
VWL 125/6 A
230V S2
VWL 125/6 A S2
Refrigerant, type
R290
R290
R290
R290
Refrigerant, fill quantity
1.30 kg
1.30 kg
1.30 kg
1.30 kg
Refrigerant, Global Warming Potential (GWP)
3
3
3
3
Refrigerant, CO
2
equivalent
0.0039 t
0.0039 t
0.0039 t
0.0039 t
Permissible operating pressure, maximum
3.15 MPa
(31.50 bar)
3.15 MPa
(31.50 bar)
3.15 MPa
(31.50 bar)
3.15 MPa
(31.50 bar)
Compressor, type
Scroll compressor
Scroll compressor
Scroll compressor
Scroll compressor
Compressor, oil type
Specific
polyalkylene glycol
(PAG)
Specific
polyalkylene glycol
(PAG)
Specific
polyalkylene glycol
(PAG)
Specific
polyalkylene glycol
(PAG)
Compressor, control
Electronic
Electronic
Electronic
Electronic
Technical data
–
Power, heating mode
VWL 105/6 A
230V S2
VWL 105/6 A S2
VWL 125/6 A
230V S2
VWL 125/6 A S2
Heating output, A2/W35
5.80 kW
5.80 kW
5.90 kW
5.90 kW
Coefficient of performance, COP, EN 14511,
A2/W35
4.60
4.60
4.60
4.60
Power consumption, effective, A2/W35
1.26 kW
1.26 kW
1.28 kW
1.28 kW
Power consumption, A2/W35
6.20 A
2.80 A
6.20 A
2.90 A
Heat output, minimum/maximum, A7/W35
5.40 … 12.50 kW
5.40 … 12.50 kW
5.40 … 14.00 kW
5.40 … 14.00 kW
Heat output, nominal, A7/W35
8.10 kW
8.10 kW
8.50 kW
8.50 kW
Coefficient of performance, COP, EN 14511,
A7/W35
5.30
5.30
5.40
5.40
Power consumption, effective, A7/W35
1.53 kW
1.53 kW
1.57 kW
1.57 kW
Power consumption, A7/W35
7.40 A
3.00 A
7.60 A
3.10 A
Heating output, A7/W45
8.10 kW
8.10 kW
8.10 kW
8.10 kW
Coefficient of performance, COP, EN 14511,
A7/W45
4.10
4.10
4.10
4.10
Power consumption, effective, A7/W45
1.98 kW
1.98 kW
1.98 kW
1.98 kW
Power consumption, A7/W45
9.40 A
3.60 A
9.40 A
3.60 A
Heating output, A7/W55
9.10 kW
9.10 kW
9.10 kW
9.10 kW
Coefficient of performance, COP, EN 14511,
A7/W55
3.10
3.10
3.10
3.10
Power consumption, effective, A7/W55
2.94 kW
2.94 kW
2.94 kW
2.94 kW