Installation and maintenance instructions ecoTEC pro 0020209589_04
4
Boiler
5
Inspection hatch
A
Final storey
B
Ground floor
Note
The flue connecting from the appliance to the flue
system must be supplied from the manufacturer of
the boiler.
C43 flue systems must not be a 'pressurised sys-
tem' but act under natural draught principles.
C43 type flue systems must have their own con-
densate drain fitted and not allow condensate to
mix into other appliances.
The flue length must be calculated and installed according to
the relevant standards EN 13384-1 and 2 (C43 flue systems
only) with reference to the manufacturer's instructions sup-
plied. The appliance maximum flue length must be taken into
account when calculating the overall design of the flue sys-
tem.
Consult the separate installation manual for air/flue gas sys-
tems supplied with your appliance for all possibilities and as-
sociated accessories and how to install the flue system.
6.7
Using the installation template
▶
Use the installation template to ascertain the locations at
which you need to drill holes and make breakthroughs.
6.8
Wall-mounting the product
1.
Check the load-bearing capacity of the wall.
2.
Note the total weight of the product.
3.
Only use fixing material that is permitted for the wall.
4.
If required, ensure that mounting apparatus on-site has
sufficient load-bearing capacity.
5.
Wall-mount the product as described.
1
6.
Install the product bracket
(1)
on the wall.
7.
Hang the product on the product bracket from above
using the hanging bracket.
6.9
Removing/installing the front casing
6.9.1
Removing the front casing
▶
Remove the front casing as shown in the illustration.
6.9.2
Installing the front casing
▶
Refit the components in the reverse order.