Vaillant 0010015166 Installation And Maintenance Instructions Manual Download Page 7

Set-up 4

0020159949_07 recoVAIR Installation and maintenance instructions

7

4.2.5

View from above

595

300

154

284

4.2.6

Dimensions, fixing bracket

32

25

32

25

204

270

97

10

30

10

30

4.3

Observing the requirements for the
installation site

4.3.1

Observing the requirements for the
product's installation site

The product can be installed in dwellings, cellar spaces, stor-
age or utility rooms, and in attics. The product is wall-moun-
ted only.

Observe the current applicable national construction reg-
ulations.

Ensure that the installation site is dry and is frost-proof
throughout.

Ensure that the installation site is aerated and ventilated.

Install the supply air pipeline so that there is sufficient
distance to the exit air pipeline, exhaust air pipeline and
outflow purging.

Check the load-bearing capacity of the wall.

Load-bearing capacity:

41 kg

Check whether the supplied fixing elements are sufficient
for the selected installation site.

Ensure that the installation site is not located higher than
max. 2000 metres above sea level.

Minimum clearances and installation clearances

400

30

300

30

400

Observe the minimum clearances and installation clear-
ances.

Plan sufficient space for installing the ventilation system.

In order to minimise pressure losses, ensure that the dis-
tances between the header line of the ventilation system
and the product are as short as possible.

After installation, ensure that the pipelines and the ventil-
ation system are easily accessible.

Ensure that the mains plug/circuit breaker (depending on
the country) is always accessible after the installation.

Ensure that there is sufficient space to install the con-
densate siphon and condensate drain pipework.

4.3.2

Observing the requirements for the
installation site of the remote control (step
switch/control)

Ensure that the remote control is always accessible at
the installation site.

Ensure that there is sufficient space to install and operate
the remote control.

4.3.3

Observe the requirements for silencers and
for installing ducts and the product

If the opening for the exit air pipeline is too close to the inlet
opening of the outside air pipeline, the exit air can recircu-
late.

Prevent exit air from being sucked in through the outside
air opening, supply air from being sucked in through the
exhaust air opening, and transfer air from being sucked
in directly through leaks/cable feedthroughs.

If required, connect the product to the pipelines using a
sound-absorbing hose in order to minimise noise pollu-
tion caused by structure-borne noise.

Install silencers in order to minimise noise pollution via
the duct system.

If you install the product in an attic, select an installation
site that is not above living spaces.

Summary of Contents for 0010015166

Page 1: ...maintenance instructions recoVAIR VAR 260 4 E VAR 360 4 E AT CH de DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de...

Page 2: ...ing external components in the product s connection area 10 5 2 Connecting the VR 32 bus coupler 11 5 3 Connecting the product to the power supply in a fixed installation 12 6 Operation 12 6 1 Operati...

Page 3: ...nd main tenance conditions listed in the instruc tions Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any dire...

Page 4: ...4 Access to the mains plug circuit breaker must be guaranteed Ensure that the mains plug circuit breaker depending on the country is always ac cessible after the installation 1 4 Regulations directive...

Page 5: ...48 VAR 360 4 0010015166 VAR 360 4 E 0010016349 Product article number Applicability Austria Austria VAR 260 4 0010016040 VAR 260 4 E 0010016348 VAR 360 4 0010015166 VAR 360 4 E 0010016349 3 Product de...

Page 6: ...olume flow TMAX Max operating temperature Bar code with serial number The 7th to 16th digits of the serial number form the article number 3 4 CE label The CE label shows that the products comply with...

Page 7: ...sses ensure that the dis tances between the header line of the ventilation system and the product are as short as possible After installation ensure that the pipelines and the ventil ation system are...

Page 8: ...fixing bracket Using the slotted holes in the fixing bracket Spirit level Danger Risk of injury caused by a heavy weight when mounting the product The product weighs 41 kg If you are mount ing the pro...

Page 9: ...ions for the product Diameter of pipelines 150 mm Exit air lines Continuous downward gradient to the unit Using the condensate drain pipework if neces sary 3 Install the silencer in the supply exit an...

Page 10: ...t 5 Close all of the twist locks 4 on the control panel fas cia Quarter turn 6 Push in both filter plugs 3 7 Secure the front flap 1 5 Electrical installation Only qualified electricians may carry out...

Page 11: ...onnect the control to the eBUS connection in the con nection area for external components of the product System control installation instructions Connection type eBUS line Controller Compatibility as...

Page 12: ...230 V or use the circuit breaker depending on the country to switch on the product The product s electronics start up The basic display appears on the display 7 2 Installation assistant As a prerequi...

Page 13: ...isbalance You can use this function to set the dis balance between the exhaust air volume flow and supply air volume flow The ex haust air volume flow must always be greater than the supply air volume...

Page 14: ...ge 12 8 1 1 2 Measuring initialising the system 1 Call up the installer level Page 12 2 Navigate to the Test menu Check programmes Initialisation measure menu item 3 Start the check programme The syst...

Page 15: ...ensate tray 1 Open the product Page 10 2 Undo and remove the heat exchanger cover Caution Risk of material damage to the heat ex changer caused by incorrect handling If your hands or any objects come...

Page 16: ...e impeding the air flows 4 If required re adjust the supply air and exhaust air valves 5 Clean the outside air s intake tract and the exit air s outlet openings 6 Carry out maintenance on the product...

Page 17: ...e frost protection function is no longer active This increases the risk of moisture or mould build ing up Only decommission the product in the case of an emergency for maintenance or repair work or fo...

Page 18: ...Check programmes P 01 Bypass test Yes No No P 02 Test Frost prot element Yes No No P 03 Initialisation measure Yes No No P 04 System efficiency test Yes No No Installer level Test menu Sensor actuato...

Page 19: ...tandard Frost prot element Not available Electrical Hydraulic Not avail able Air earth collector Not available Available Not avail able Diff temp bypass 0 25 0 5 10 Pressure monitor Not available Avai...

Page 20: ...efective Check that the exhaust air fan works correctly F 803 Fault Supply air ventil ator Supply air fan does not work is defective Check that the supply air fan works correctly F 804 Supply air temp...

Page 21: ...emperature increases again The product then starts normal operation Supply air temp 10 Lhm 807 Failure fault Air quality sensor Air quality sensor does not work is defective Check the air quality sens...

Page 22: ...sition Check the flap position The temperature sensor is posi tioned incorrectly Check the positioning of the temperature sensor Noises in the condensate drain pipework Condensate siphon connected inc...

Page 23: ...ten ance The maintenance interval for the product was exceeded Maintaining the product At least annually 3 M 802 System ef ficiency impaired The system efficiency is ad versely affected Increase estab...

Page 24: ...9 m 0 9 m Thermal efficiency in accordance with EN 13141 7 85 78 85 75 Thermal efficiency in accordance with the Passivhaus Institut Passive House Institute 87 85 83 81 Thermal efficiency in accordan...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...n aus dem Mobilfunknetz ggf abweichende Tarife n here Information erhalten Sie bei Ihrem Mobilnetzbetreiber info vaillant at termin vaillant at www vaillant at www vaillant at werkskundendienst Vailla...