Vaillant 0010015166 Installation And Maintenance Instructions Manual Download Page 20

Appendix

20

Installation and maintenance instructions recoVAIR 0020159949_07

Setting level

Values

Unit

Increment, select

Default
setting

Min.

Max.

Nominal flow

(

VAR 260/4

)

115

200

m

³

/h

5

Nominal flow

(

VAR 360/4

)

175

280

m

³

/h

5

Exh. air nom. flow corr.

40

40

%

1

0

Sup. air nom. fl. corr.

40

40

%

1

0

Heat exchanger type

Standard

,

Enthalpy

Standard

Frost prot. element

Not available

,

Electrical

,

Hydraulic

Not avail-
able

Air-earth collector

Not available

,

Available

Not avail-
able

Pressure monitor

Not available

,

Available

Not avail-
able

Step switch

Not available

,

Available

Not avail-
able

Air quality sensor

0

2

1

0

U value

0,2

2,5

W/(m

2

K)

0,1

1,5

Contact data

Phone number

0 - 9

Close the installation assistant?

Yes

,

Back

1)

Fault lists are only available, and can only be deleted, if faults have occurred.

B

Fault messages

Overview

Message

Possible cause

Measure

F.800 Frost protection not
guaranteed

Outside temperature sensor
does not work/is defective

Check that the outside temperature sensor works correctly.

Exit-air temperature sensor
does not work/is defective

Check that the exit-air temperature sensor works correctly.

F.801 Frost protection not
guaranteed

Heat exchanger protection is
active

Wait until the outside temperature increases (the product auto-
matically switches on no later than 60 minutes after the tem-
perature increases.).
Outside temperature: >

3

F.802Fault: Ventilator exit air

Exhaust-air fan does not work/is
defective

Check that the exhaust-air fan works correctly.

F.803 Fault: Supply air ventil-
ator

Supply-air fan does not work/is
defective

Check that the supply-air fan works correctly.

F.804 Supply air temp. too
low

Bypass does not work/is defect-
ive

1.

Press the fault clearance key.

Fault clearance attempts:

3

2.

If you cannot eliminate the fault with the fault clearance at-
tempt, check that the bypass works correctly.

Heat exchanger does not
work/is defective

Check that the heat exchanger works correctly/has no leak-
ages.

F.805 Air supply temp. of heat
exch. too high

The frost protection element
does not work/is defective

Check that the frost protection element works correctly.

F.806 Fault: Frost prot. ele-
ment

The frost protection element is
defective

Replace the frost protection element.

F.807 Failure: Sup. air diff.
pressure sensor

Supply-air differential pressure
sensor does not work/is defect-
ive

Check that the supply-air differential pressure sensor works
correctly.

F.808 Failure: Exit air diff.
pressure sensor

Exit-air differential pressure
sensor does not work/is defect-
ive

Check that the exit-air differential pressure sensor works cor-
rectly.

F.809 Failure: Outside air
temp. sensor

Outside temperature sensor
does not work/is defective

Check that the outside temperature sensor works correctly.

F.810 Failure: Exit air temp.
sensor

Exit-air temperature sensor
does not work/is defective

Check that the exit-air temperature sensor works correctly.

F.811 Failure: Supply air
temp. sensor

Supply-air temperature sensor
does not work/is defective

Check that the supply-air temperature sensor works correctly.

Summary of Contents for 0010015166

Page 1: ...maintenance instructions recoVAIR VAR 260 4 E VAR 360 4 E AT CH de DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de...

Page 2: ...ing external components in the product s connection area 10 5 2 Connecting the VR 32 bus coupler 11 5 3 Connecting the product to the power supply in a fixed installation 12 6 Operation 12 6 1 Operati...

Page 3: ...nd main tenance conditions listed in the instruc tions Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any dire...

Page 4: ...4 Access to the mains plug circuit breaker must be guaranteed Ensure that the mains plug circuit breaker depending on the country is always ac cessible after the installation 1 4 Regulations directive...

Page 5: ...48 VAR 360 4 0010015166 VAR 360 4 E 0010016349 Product article number Applicability Austria Austria VAR 260 4 0010016040 VAR 260 4 E 0010016348 VAR 360 4 0010015166 VAR 360 4 E 0010016349 3 Product de...

Page 6: ...olume flow TMAX Max operating temperature Bar code with serial number The 7th to 16th digits of the serial number form the article number 3 4 CE label The CE label shows that the products comply with...

Page 7: ...sses ensure that the dis tances between the header line of the ventilation system and the product are as short as possible After installation ensure that the pipelines and the ventil ation system are...

Page 8: ...fixing bracket Using the slotted holes in the fixing bracket Spirit level Danger Risk of injury caused by a heavy weight when mounting the product The product weighs 41 kg If you are mount ing the pro...

Page 9: ...ions for the product Diameter of pipelines 150 mm Exit air lines Continuous downward gradient to the unit Using the condensate drain pipework if neces sary 3 Install the silencer in the supply exit an...

Page 10: ...t 5 Close all of the twist locks 4 on the control panel fas cia Quarter turn 6 Push in both filter plugs 3 7 Secure the front flap 1 5 Electrical installation Only qualified electricians may carry out...

Page 11: ...onnect the control to the eBUS connection in the con nection area for external components of the product System control installation instructions Connection type eBUS line Controller Compatibility as...

Page 12: ...230 V or use the circuit breaker depending on the country to switch on the product The product s electronics start up The basic display appears on the display 7 2 Installation assistant As a prerequi...

Page 13: ...isbalance You can use this function to set the dis balance between the exhaust air volume flow and supply air volume flow The ex haust air volume flow must always be greater than the supply air volume...

Page 14: ...ge 12 8 1 1 2 Measuring initialising the system 1 Call up the installer level Page 12 2 Navigate to the Test menu Check programmes Initialisation measure menu item 3 Start the check programme The syst...

Page 15: ...ensate tray 1 Open the product Page 10 2 Undo and remove the heat exchanger cover Caution Risk of material damage to the heat ex changer caused by incorrect handling If your hands or any objects come...

Page 16: ...e impeding the air flows 4 If required re adjust the supply air and exhaust air valves 5 Clean the outside air s intake tract and the exit air s outlet openings 6 Carry out maintenance on the product...

Page 17: ...e frost protection function is no longer active This increases the risk of moisture or mould build ing up Only decommission the product in the case of an emergency for maintenance or repair work or fo...

Page 18: ...Check programmes P 01 Bypass test Yes No No P 02 Test Frost prot element Yes No No P 03 Initialisation measure Yes No No P 04 System efficiency test Yes No No Installer level Test menu Sensor actuato...

Page 19: ...tandard Frost prot element Not available Electrical Hydraulic Not avail able Air earth collector Not available Available Not avail able Diff temp bypass 0 25 0 5 10 Pressure monitor Not available Avai...

Page 20: ...efective Check that the exhaust air fan works correctly F 803 Fault Supply air ventil ator Supply air fan does not work is defective Check that the supply air fan works correctly F 804 Supply air temp...

Page 21: ...emperature increases again The product then starts normal operation Supply air temp 10 Lhm 807 Failure fault Air quality sensor Air quality sensor does not work is defective Check the air quality sens...

Page 22: ...sition Check the flap position The temperature sensor is posi tioned incorrectly Check the positioning of the temperature sensor Noises in the condensate drain pipework Condensate siphon connected inc...

Page 23: ...ten ance The maintenance interval for the product was exceeded Maintaining the product At least annually 3 M 802 System ef ficiency impaired The system efficiency is ad versely affected Increase estab...