Appendix
30
Installation and maintenance instructions ecoVIT exclusiv 0020258610_00
Code
Parameter
Values
Unit
Explanation, selection, increment
Default
setting
Own
setting
Min.
Max.
D.078
DHW max. flow temperat-
ure
55
80
℃
Limit on cylinder charging temper-
ature
(Target flow temperature in cylinder
charging mode)
1
Note
The chosen value must be at least
15 K above the cylinder target
value.
80
D.080
Heating operating hours
Current value
h
–
After
pressing
the
i
button
once,
the first
three digits
are
displayed;
after
pressing
the
i
button
a second
time,
the second
three digits
of the six-
digit
number
(burner
starts
x 100) are
displayed.
Not ad-
justable
D.081
DHW operating hours
Current value
h
–
Not ad-
justable
D.082
Heating burner starts
Current value
–
Number of burner starts (x 100)
Not ad-
justable
D.083
DHW burner starts
Current value
–
Number of burner starts (x 100)
Not ad-
justable
D.084
Maintenance in
0
3000
h
Number of hours until the next
maintenance
1
300 corresponds to 3000 hrs
"
– – –
" = Deactivated
„
– – –
“
D.087
Set the type of gas
0
–
0: Natural gas
1: Liquefied petroleum gas
–
D.090
eBUS controller
Current value
–
0: Not recognised (eBUS address
≤
10)
1: Recognised
–
Not ad-
justable
D.091
Status DCF77
Current value
–
0: No reception
1: Reception
2: Synchronised
3: Valid
–
Not ad-
justable
D.093
Adjust Device Specific
Number
0
999
–
22 kW: 1
28 kW: 2
36 kW: 3
47 kW: 4
65 kW: 5
–
D.095
Software version: PeBUS
participant
Current value
–
1: PCB (BMU)
1: Display (AI)
–
Not ad-
justable
D.096
Reset to factory settings?
0
1
–
Reset all adjustable parameters to
factory setting
0: No
1: Yes
–
D.097
Installer level
Current value
–
Service code 17
–
D.098
Tel. no. for competent per-
son
10-digit
–
Option to enter a telephone number
that is displayed in the event of
product malfunction
–
D.099
Language
–
–
–
The selected language is displayed
in line 2 (line 1 and 2 in selected
language)
Country-
specific