50
51
Heat exchangers must be stored indoors and covered for greater protection against
dust, in a location providing temperatures from +1°C to +40°C and relative humidity up
to 90%.
Ensure that no liquids, dust, etc. come into contact with the equipment during storage.
The equipment must be stored in an area free from construction activities and vehicle
transit that could cause accidental damage.
The equipment must not come into contact with the ground.
Adequate free space must be available around equipment to guarantee periodic in-
spections and free movement.
The maximum storage period is 12 months.
Long term storage period (5 years) is possible, if the equipment is ordered with nitrogen
filling.
Upon the expiry of assigned parameters (assigned storage period, assigned service
life) operation of the equipment is stopped, equipment is inspected, repaired (if nec-
essary) and new assigned parameters are established (assigned service life and/or
assigned storage period). If the repair is not possible (or not reasonable) the equipment
is disposed of.
9 Troubleshooting
If the exchanger is not working properly after start-up, please check the following be-
fore contacting your Vahterus representative:
Problem
Cause
Checks
Action
NB
Poor perfor-
mance
Exchanger/
connections
connected
incorrectly
Check flow
directions of
connections.
Do they
comply with
the design/
drawing?
Change
the piping
connections.
Change
direction of
flow
Incorrect
pressure
Check
pressure
and temper-
atures on
both sides
Correct or
adjust valves
Contact the
manufacturer
and provide
the following
values:
pressures,
pressure
differences,
temperatures
and flow
rates