background image

 

35

20. WARRANTY CONDITIONS 

1. Without prejudice to the restrictions stated hereinafter, the contractor guarantees both the 

soundness of the product delivered by him and the quality of the material used and/or delivered for 
it, insofar as this concerns faults in the product delivered which do not become apparent during 
inspection or transfer test, which the principal shall demonstrate to have arisen within 12 months 
from delivery in accordance with subarticle 1A exclusively or predominantly as a direct 
consequence of unsoundness of the construction used by the contractor or as a consequence of 
faulty finishing or the use of poor materials.  

1A. The product shall be deemed to have been delivered when it is ready for inspection (if 

inspection at the premises of the contractor has been agreed) and otherwise when it is ready 
for shipment. 

2. Articles 1 and 1a shall equally apply to faults which do not become apparent during inspection or 

transfer test which are caused exclusively or predominantly by unsound assembly/installation by 
the contractor. If assembly/installation is carried out by the contractor, the guarantee period 
intended in article 1 shall last 12 months from the day on which assembly/installation is completed 
by the contractor, with the understanding that in this case the guarantee period shall end not later 
than 18 months after delivery in accordance with the terms of subarticle 1A. 

3. Defects covered by the guarantee intended under articles 1, 1a and 2 shall be remedied by the 

contractor by repair or replacement of the faulty component either on or off the premises of the 
contractor, or by shipment of a replacement component, this remaining at the discretion of the 
contractor. Subarticle 3A shall equally apply if repair or replacement takes place at the site where 
the product has been assembled/installed. All costs accruing above the single obligation described 
in the first sentence, such as are not restricted to shipment costs, travelling and accommodation 
costs or disassembly or assembly costs insofar as they are not covered by the agreement, shall be 
paid by the principal.  

3A.If repair or replacement takes place at the site where the product has been assembled/installed, 

the principal shall ensure, at his own expense and risk, that:  

a. the employees of the contractor shall be able to commence their work as soon as they have 

arrived at the erection site and continue to do so during normal working hours, and 
moreover, if the contractor deems it necessary, outside the normal working hours, with the 
proviso that the contractor informs the principal of this in good time;  

b. suitable accommodation and/or all facilities required in accordance with government 

regulations, the agreement and common usage, shall be available for the employees of the 
contractor;  

c. the access roads to the erection site shall be suitable for the transport required;  

d. the allocated site shall be suitable for storage and assembly;  

e. the necessary lockable storage sites for materials, tools and other goods shall be available;  

f. the necessary and usual auxiliary workmen, auxiliary machines, auxiliary tools, materials and 

working materials (including process liquids, oils and greases, cleaning and other minor 
materials, gas, water, electricity, steam, compressed air, heating, lighting, etc.) and the 
measurement and testing equipment usual for in the business operations of the principal, 
shall be available at the correct place and at the disposal of the contractor at the correct time 
and without charge;  
 

 

Summary of Contents for Viscosense 3

Page 1: ...echnical Manual Instructions for installation operation and maintenance 775 VISCOSENSE 3 Viscosity Sensor Interface box Valid for ViscoSense 3 Publication nr TIB 775 GB 0517 Supersedes TIB 775 GB 1216...

Page 2: ...ion 11 6 4 1 ViscoSense 3 interface box 11 6 4 2 ViscoSense 3 housing 11 6 4 3 To assemble ViscoSense 3 sensor 13 6 5 Electrical installation 15 6 6 Connection of sensor to interface box 16 6 7 Instal...

Page 3: ...analysis 27 15 5 Diagnostic information 28 16 CERTIFICATES 30 17 DRAWINGS 31 17 1 ViscoSense 3 sensor and sensor housing 31 17 1 1 ViscoSense 3 sensor housing with sensor installed 31 17 2 ViscoSense...

Page 4: ...hnical manuals of VAF Instruments It is not allowed to make any modifications to the sensor or the interface box without prior written permission of VAF Instruments BV To ensure safe and correct insta...

Page 5: ...the interface box in combination with the requirement to switch of the power supply to the box before opening it in order to avoid personal injury 1 3 COPYRIGHT This technical manual is copyrighted w...

Page 6: ...gassing mixing tank operates as a fuel buffer ensuring gradual changes of viscosity which results in a stable control of the viscosity The ViscoSense 3 sensor is used to measure the actual viscosity o...

Page 7: ...al DLC coating and it is mechanically protected by a stainless steel flow tube with 3 oval slits It is supplied with 5 metres of signal cable for connection to the interface box The ViscoSense 3 Inter...

Page 8: ...the head In a low viscosity medium like air the resonance frequency is in the range of 1600 Hz In a high viscosity medium the movement of the head is damped by the liquid Consequently the resonance fr...

Page 9: ...16L Coating Diamond Like Carbon DLC Signal cable length 5 metres integrated with sensor Protection class IP65 Weight 1 kg Warning For hazardous zone I and II the ViscoSense 3 Ex d version is required...

Page 10: ...sensor cable Cable wire Power supply 3 x 1 5 mm double isolated heavy duty PVC Output signals 3 x 2 x 0 50 mm twisted pair individually screened braid shielded Ventilation requirements No special req...

Page 11: ...king material should be done according to the laws of the country where the equipment is installed or according to the rules that are applicable on the vessel Figure 4 Transport locking cap Figure 5 O...

Page 12: ...he housing This can easily happen if the inner diameter of the piping is smaller than the inner diameter of the ViscoSense 3 housing if it has been installed horizontally If the inner diameter of the...

Page 13: ...late the ViscoSense 3 signal 6 4 MECHANICAL INSTALLATION 6 4 1 ViscoSense 3 interface box 1 Install the ViscoSense 3 interface box in a suitable location free from excessive vibrations humidity and ex...

Page 14: ...t be two supports to the inlet and outlet perpendicular to the pipe and perpendicular to the ViscoSense 3 If one support would be used the lateral vibrations would be converted to angular vibrations a...

Page 15: ...ith the closed surface facing the flow illustrated in figure 8 Make sure the flow tube closed surface is pointing towards the inlet of the sensor housing see figure 8 The sensor will not work correctl...

Page 16: ...14 7 The ViscoSense 3 system is now ready for electrical installation Figure 8 ViscoSense 3 sensor assembly A B...

Page 17: ...or circuit breaker in the proximity of the interface box Make sure that the wire to PE is always longer than power wires Figure 9 Power supply terminal J2 2 Feed the cable from ViscoSense 3 sensor th...

Page 18: ...ENSOR TO INTERFACE BOX 1 Tighten the cable glands with a spanner 2 Install the wires to the appropriate terminals of terminal J6 Figure 11 Connecting sensor to interface box Figure 12 External connect...

Page 19: ...Has the ViscoSense housing been installed correct according the fuel flow direction Has the inlet and outlet piping sufficiently been supported as per 6 4 2 Have fuel pressure dampers been installed a...

Page 20: ...at the ViscoSense interface box ViscoSense Controller The ambient temperature at the ViscoSense controller is not higher than 55 C Have all electric connections for external signals been made with a...

Page 21: ...power supply to the ViscoSense 3 system Depending upon the viscosity of the liquid it can take up to 30 seconds before the first reading appears This is due to the automatic signal gain control 7 Gra...

Page 22: ...l 2 Shut off the flow through the ViscoSense 3 sensor by closing the valves on both side of the sensor housing 3 Switch off power supply to the ViscoSense 3 interface box 4 If possible drain and empty...

Page 23: ...ings for this sensor are made in the interface box To make the correct settings a spare sensor is supplied together with an micro SD card which can be connected into the interface box Please note that...

Page 24: ...sor should be taken out of the sensor housing and cleaned See maintenance section for cleaning instructions To protect the pendulum from damage due to mechanical shocks the transport locking cap shoul...

Page 25: ...n a cool and dry place 12 MALFUNCTION AND SEND FOR REPAIR If the sensor or the interface box fails they should be sent back to VAF Instruments for repair 13 ENVIRONMENT There are several electronics i...

Page 26: ...ON THE SENSOR Figure 17 VS3 sensor The sensor and electric wire are moulded together NEVER TRY TO OPEN THE BACK OF THE SENSOR THIS WILL DAMAGE THE WIRE AND SENSOR BEYOND REPAIR The sensor can only be...

Page 27: ...box Check supply Check fuses Check electrical connections Current loop connection broken Check electrical wiring of 4 20 mA output signal ViscoSense 3 malfunctioning Check diagnostic led Problem Possi...

Page 28: ...xed liquid see chapter 6 None Sensor is damaged or fouled Clean and inspect the sensor see chapter 8 Problem Possible cause Corrective action Viscosity output is max range The viscosity in the sensor...

Page 29: ...vershooting Ti too high Decrease Ti High initial overshot followed by fading oscillation Ti too low Increase Ti 15 4 HOW TO TAKE A HFO SAMPLE FOR ANALYSIS The HFO sample must always be taken from the...

Page 30: ...st Adjusting phase Start up of pendulum Adjusting amplitude Measuring negative phase Measuring positive phase During start up the current outputs will be 4 mA When the display turns into 2 3 4 5 or 6...

Page 31: ...out of range 0 0 restart Frequency of pendulum out of range 0 0 restart Unstable phase of pendulum or no pendulum Received measuring signal Urec too low eg very high viscosity Actual open loop Actual...

Page 32: ...30 16 CERTIFICATES Certificates are delivered separately or can be downloaded from www vaf nl...

Page 33: ...31 17 DRAWINGS 17 1 VISCOSENSE 3 SENSOR AND SENSOR HOUSING 17 1 1 ViscoSense 3 sensor housing with sensor installed Figure 18 Dimensions of ViscoSense 3 sensor All dimensions in millimetres...

Page 34: ...32 17 2 VISCOSENSE 3 INTERFACE BOX 17 2 1 ViscoSense 3 interface box Figure 19 Dimensions of ViscoSense 3 interface box All dimensions in millimetres...

Page 35: ...Memory EPROM Erasable Programmable Read Only Memory Hz Hertz Frequency IEC International Electrotechnical Commission IOM Installation Operation and Maintenance JIS Japanese Industrial Standard Kg Kil...

Page 36: ...34 19 PARTS LISTS Spare parts 0279 0096PH consisting of 0279 0096 ViscoSense 3 sensor 0279 0102 dongle 0690 1202 Micro SD card 19 1 VISCOSENSE 3 SENSOR Figure 20 Parts list...

Page 37: ...ent this remaining at the discretion of the contractor Subarticle 3A shall equally apply if repair or replacement takes place at the site where the product has been assembled installed All costs accru...

Page 38: ...to any guarantee regardless of how it is referred to If without previous written approval from the contractor the principal commences disassembly repair or other work on the product or allows it to be...

Page 39: ...will result in a slow and possibly unstable viscosity control VAF Instruments delivers the ViscoSense 3 with housing Refer to the table below for flow rate corresponding to the size of housing Fluid f...

Page 40: ...is less therefore the filter can be smaller The fuel temperature is lower and the fuel is more stable Heaters Heaters can be either steam or electric There must be two heaters placed parallel in the...

Page 41: ...Chapter 6 1 text added Revision 0715 Chapter 19 drawing 0820 1230 adjusted Revision 0516 Chapter 1 1 warning added Chapter 6 5 point 3 adjusted Revision 0916 Coating sensor head changed from Teflon t...

Page 42: ...Dordrecht The Netherlands P O Box 40 3300 AA Dordrecht The Netherlands T 31 0 78 618 3100 F 31 0 78 617 7068 sales vaf nl www vaf nl Specifications subject to change without notice Agents and distrib...

Reviews: