VADO VADO-PRO-100P Manual Download Page 9

 

IN-SERVICE TESTING 

The purpose of in-service testing is to regularly monitor the thermal performance of 
thermostatic  mixing  valve.  Deterioration  in  performance  can  indicate  the  need  for 
service work to be carried out on the system. 

If  the  authority  concerned  does  not  have  a  planned  test  and  maintenance  schedule 
then the suggestions below should form the basis of a new system. 

At intervals of 6-8 weeks and 12-15 weeks after commissioning:- 

1.

 

Check supply parameters are still within the expected values if not check system 
for faults. 

2.

 

Carry out commissioning procedures using the same test equipment, if the mixed 
water temperature has changed a significant amount (by more than 1K) check to 
ensure in line filters are clean, that the check valves are working and all isolation 
valves are fully open. If no fault can be found check and record the mixed water 
temperatures  and  readjust  mixed  water  temperature  to  the  values  in  table  2. 
Complete the commissioning procedure if the mixed water temperature exceeds 
the values of the maximum recorded temperature by more than 2K the need for 
service work is indicated. 

Depending on the results of these two tests the following should be adopted 

a)

 

If  a  small  change  (e.g.  1K  to  2K)  occurs  in  one  of  these  tests  or  there  is  no 
significant change (e.g. 1K maximum) then the next in service test should be 24 
to 28 weeks after commissioning. 

b)

 

If  small  changes  occur  in  both  test  or  a  larger  change  occurs  in  one  test 
(exceeding 2K) then the next in service test should be carried out 18 to 21 weeks 
after commissioning. 

These results can then be used to set  a service interval which tests have shown can 
be used with no more than a small change in mixed water temperature. This method 
of  determining  service  intervals  is  used  to  take  into  account  various  in  service 
conditions (i.e. water condition) that the valve may experience. 
 

Summary of Contents for VADO-PRO-100P

Page 1: ...rmostatic mixing valve VADO PRO 100P IMPORTANT Installer This Manual is the property of the customer and must be retained with the product for maintenance and operational purposes and operational purposes ...

Page 2: ...control A single lever provides sequential operation from OFF through COLD and WARM to a maximum blend temperature preset at 41 which can be adjusted if required The VADO PRO 100P is designed for single or two hole basins The supply connections are via flexible inlet tails and check valve assemblies that incorporate check valves and filter SAFETY WARNINGS The VADO PRO 100P is precision engineered ...

Page 3: ...ecessary to maintain the product in good functional order 4 Warning continued use of this product in conditions outside the limits listed in this section can severely affect the performance and reduce the effective service life and can present potential risk to users Table 1 Conditions for normal use NOTE Valves operating outside these conditions cannot be guaranteed by the Scheme to operate as Ty...

Page 4: ...3 Dimensions ...

Page 5: ...r is 1 2 or 15 mm 8 Inlet threaded joint connections should be made with PTFE tape or liquid sealant Do no use oil based non setting jointing compounds 9 To eliminate pipe debris it is essential that supply pipes are thoroughly flushed through before connection to the Thermostatic mixing valve Procedure Refer to Figure 1 1 Screw the fixing studs fully into the Thermostatic mixing valve body 2 Plac...

Page 6: ...es 9 Locate the fibre washers inside the nuts on the flexible inlet tails and screw the flexible inlet tails on to the checkvalve assemblies The flexible inlet tail nearest the outlet of the Thermostatic mixing valve must be connected to the hot supply Use a suitable 24 mm spanner adjustable to tighten the flexible inlet tails Restore the water supplies and check all connections are watertight Ref...

Page 7: ... the hot water must be at least 10 above the desired blend however during resetting this should be close to the typical storage maximum to offset the possibility of any blend shift due to fluctuating supply temperatures Make sure that both inlet isolating valve are fully open Temperatures should always be measured using a thermometer with proven accuracy 1 Use the 2 mm Allen key supplied to loosen...

Page 8: ...ions operating this outlet should cause a drop in supply pressure and note the subsequent effect on blend temperature This should be no more than 2 change Note Causing thermal shutdown of the Thermostatic mixing valve by full closure of the cold supply may not adequately indicate the practical capability of the Thermostatic mixing valve nor its service condition Consequently this is not a recommen...

Page 9: ...ck and record the mixed water temperatures and readjust mixed water temperature to the values in table 2 Complete the commissioning procedure if the mixed water temperature exceeds the values of the maximum recorded temperature by more than 2K the need for service work is indicated Depending on the results of these two tests the following should be adopted a If a small change e g 1K to 2K occurs i...

Reviews: