6
COMMISSIONING
Commissioning must be carried out in accordance with these instructions, and
must be conducted by designated, qualified and competent personnel.
Maximum Temperature
The maximum blend temperature obtainable by the user should be limited, to
prevent accidental selection of a temperature that is too hot.
The VADO-PRO-100P is fully performance tested, and the maximum temperature is
preset to 41
℃
under ideal installation conditions at the factory. Site conditions and
personal preference may dictate that the maximum temperature has to be reset
following installation.
Adjust the mixed water temperature in accordance with table 2, the method of
adjustment is covered in this COMMISSIONING section.
Table 2: Mixed Water Temperature
Application
Abbreviated Designation
Mixed water temperature
℃
Washbasin
-HP-W, -LP-W,
41 max
Maximum Temperature Setting:
Make sure that an adequate supply of hot water is available at the hot inlet of the
Thermostatic mixing valve.
The minimum temperature of the hot water must be at least 10
℃
above the desired
blend, however during resetting this should be close to the typical storage maximum
to offset the possibility of any blend shift due to fluctuating supply temperatures.
Make sure that both inlet isolating valve are fully open.
Temperatures should always be measured using a thermometer with proven
accuracy.
1.
Use the 2 mm Allen key (supplied) to loosen the grub screw in the lever.
2.
Move the lever to full hot, note its position and remove the lever.
3.
Let the water run until the temperature stabilizes.
4.
Insert the 2 mm Allen key into the grub screw in the centre of the head
assembly.
5.
Rotate the grub screw as necessary until the required maximum blend
temperature is achieved. Rotate the grub screw anticlockwise to increase the
temperature or clockwise to decrease the temperature.
6.
Refit the lever in its original position. If required the lever can be fitted in any
position that allows unobstructed movement of the lever over its operating
range.
7.
Move the lever to the off position.
8.
Use the 2 mm Allen key to tighten the grub screw.
Commissioning Checks
(Temperatures should always be recorded using a thermometer with proven
accuracy)
Summary of Contents for VADO-PRO-100P
Page 4: ...3 Dimensions ...