background image

 

COMMISSIONING 

Commissioning must be carried out in accordance with these instructions, and 
must be conducted by designated, qualified and competent personnel. 

Maximum Temperature 

The  maximum  blend  temperature  obtainable  by  the  user  should  be  limited,  to 
prevent accidental selection of a temperature that is too hot. 
The VADO-PRO-100P is fully performance tested, and the maximum temperature is 
preset to 41

  under ideal installation conditions at the factory. Site conditions and 

personal  preference  may  dictate  that  the  maximum  temperature  has  to  be  reset 
following installation. 
Adjust  the  mixed  water  temperature  in  accordance  with  table  2,  the  method  of 
adjustment is covered in this COMMISSIONING section.

 

Table 2: Mixed Water Temperature 

Application 

Abbreviated Designation 

Mixed water temperature 

 

Washbasin 

-HP-W, -LP-W,   

41 max 

Maximum Temperature Setting: 

Make  sure  that  an  adequate  supply  of  hot  water  is  available  at  the  hot  inlet  of  the 
Thermostatic mixing valve. 
The minimum temperature of the hot water must be at least 10

  above the desired 

blend, however during resetting this should be close to the typical storage maximum 
to offset the possibility of any blend shift due to fluctuating supply temperatures. 
Make sure that both inlet isolating valve are fully open. 
Temperatures  should  always  be  measured  using  a  thermometer  with  proven 
accuracy. 
1.

 

Use the 2 mm Allen key (supplied) to loosen the grub screw in the lever. 

2.

 

Move the lever to full hot, note its position and remove the lever. 

3.

 

Let the water run until the temperature stabilizes. 

4.

 

Insert  the  2  mm  Allen  key  into  the  grub  screw  in  the  centre  of  the  head 
assembly. 

5.

 

Rotate  the  grub  screw  as  necessary  until  the  required  maximum  blend 
temperature  is  achieved.  Rotate  the  grub  screw  anticlockwise  to  increase  the 
temperature or clockwise to decrease the temperature. 

6.

 

Refit the lever in its original position. If required the lever can be fitted in any 
position  that  allows  unobstructed  movement  of  the  lever  over  its  operating 
range. 

7.

 

Move the lever to the off position. 

8.

 

Use the 2 mm Allen key to tighten the grub screw. 

Commissioning Checks 

(Temperatures  should  always  be  recorded  using  a  thermometer  with  proven 
accuracy) 

Summary of Contents for VADO-PRO-100P

Page 1: ...rmostatic mixing valve VADO PRO 100P IMPORTANT Installer This Manual is the property of the customer and must be retained with the product for maintenance and operational purposes and operational purposes ...

Page 2: ...control A single lever provides sequential operation from OFF through COLD and WARM to a maximum blend temperature preset at 41 which can be adjusted if required The VADO PRO 100P is designed for single or two hole basins The supply connections are via flexible inlet tails and check valve assemblies that incorporate check valves and filter SAFETY WARNINGS The VADO PRO 100P is precision engineered ...

Page 3: ...ecessary to maintain the product in good functional order 4 Warning continued use of this product in conditions outside the limits listed in this section can severely affect the performance and reduce the effective service life and can present potential risk to users Table 1 Conditions for normal use NOTE Valves operating outside these conditions cannot be guaranteed by the Scheme to operate as Ty...

Page 4: ...3 Dimensions ...

Page 5: ...r is 1 2 or 15 mm 8 Inlet threaded joint connections should be made with PTFE tape or liquid sealant Do no use oil based non setting jointing compounds 9 To eliminate pipe debris it is essential that supply pipes are thoroughly flushed through before connection to the Thermostatic mixing valve Procedure Refer to Figure 1 1 Screw the fixing studs fully into the Thermostatic mixing valve body 2 Plac...

Page 6: ...es 9 Locate the fibre washers inside the nuts on the flexible inlet tails and screw the flexible inlet tails on to the checkvalve assemblies The flexible inlet tail nearest the outlet of the Thermostatic mixing valve must be connected to the hot supply Use a suitable 24 mm spanner adjustable to tighten the flexible inlet tails Restore the water supplies and check all connections are watertight Ref...

Page 7: ... the hot water must be at least 10 above the desired blend however during resetting this should be close to the typical storage maximum to offset the possibility of any blend shift due to fluctuating supply temperatures Make sure that both inlet isolating valve are fully open Temperatures should always be measured using a thermometer with proven accuracy 1 Use the 2 mm Allen key supplied to loosen...

Page 8: ...ions operating this outlet should cause a drop in supply pressure and note the subsequent effect on blend temperature This should be no more than 2 change Note Causing thermal shutdown of the Thermostatic mixing valve by full closure of the cold supply may not adequately indicate the practical capability of the Thermostatic mixing valve nor its service condition Consequently this is not a recommen...

Page 9: ...ck and record the mixed water temperatures and readjust mixed water temperature to the values in table 2 Complete the commissioning procedure if the mixed water temperature exceeds the values of the maximum recorded temperature by more than 2K the need for service work is indicated Depending on the results of these two tests the following should be adopted a If a small change e g 1K to 2K occurs i...