PROFINET IO
vacon • 97
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
8
* See Chapter 8.3.1 "Choosing telegram type".
Control and Status Word monitoring values
When using this telegram, monitoring values contains values as shown in table below.
8.3.2.2
VACON® specific Telegram 1 and its variants
These telegrams (Table 52) use VACON
®
defined control word, status word, speed setpoint value
and speed actual value to directly access the AC drive application. When using these telegrams, the
process data fields are communicated as 16-bit ®values.
Table 50. Standard Telegram 1 setpoint and actual data
Bytes
Setpoint
Actual value
1...2
STW1
ZSW1
3...4
NSOLL_A
NIST_A
5...6
PDI1
PDO1
7...8
PDI2
PDO2
...
...
...
19...20
PDI8
PDO8
21...22
PDI9*
PDO9*
...
...
...
35...36
PDI16*
PDO16*
Table 51. Control and Status Word monitoring values
Name
Value
Drive CW
FBFixedControlWord
Drive SW
FBFixedStatusWord
Protocol CW
STW1
Protocol SW
ZSW1
Table 52. Vendor telegram 1 and variants
Telegram No.
Telegram
Abbreviation
108
Vendor Telegram 1
Vendor 1
109
Vendor Telegram 1 + 1 Process Data
Vendor 1 + 1 PD
110
Vendor Telegram 1 + 2 Process Data
Vendor 1 + 2 PD
111
Vendor Telegram 1 + 3 Process Data
Vendor 1 + 3 PD
112
Vendor Telegram 1 + 4 Process Data
Vendor 1 + 4 PD
113
Vendor Telegram 1 + 5 Process Data
Vendor 1 + 5 PD
114
Vendor Telegram 1 + 6 Process Data
Vendor 1 + 6 PD
115
Vendor Telegram 1 + 7 Process Data
Vendor 1 + 7 PD
116
Vendor Telegram 1 + 8 Process Data
Vendor 1 + 8 PD
140
Vendor Telegram 1 + 12 Process Data *
Vendor 1 + 12 PD