Modbus TCP / Modbus UDP
vacon • 83
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7
Once the ID Map address range has been initialized with the parameter IDs, the parameter values
can be read and written in the IDMap Read/Write address range address (IDMap a 100).
Table 34. Parameter Values in 16-bit IDMap Read/Write registers
If the ID Map table has not been initialized, all the fields show index as '0'. If it has been initialized,
the parameter IDs included in it are stored in the flash memory of the option board.
Table 35. Example of parameter values in 32-bit IDMap Read/Write registers
7.3.2.5.5.
O
PERATION
DAY
COUNTER
Control unit operating time counter (total value). This counter cannot be reset. The values are read
only.
NOTE!
The feature Operation day counter does not work with VACON
®
20, VACON
®
20 X or VACON
®
20 CP AC drives.
Operation day counter as seconds
This counter in registers 40011
d
to 40012
d
holds the value of operation days as seconds in a 32-bit
unsigned integer.
Table 36. Operation days counter as seconds
Operation day counter
This counter in registers 40001
d
to 40005
d
holds the value of operation days counter. The values are
read only.
For compatibility with VACON
®
100 family internal Modbus TCP/UDP and the OPT-CI option board,
this counter is found from two different register areas: holding registers 40001
d
to 40005
d
and input
registers 1
d
to 5
d
.
Address
Data
10601
Data included in parameter ID700
10602
Data included in parameter ID702
10603
Data included in parameter ID707
10604
Data included in parameter ID704
Address
Data
10701
Data High, parameter ID700
10702
Data Low, parameter ID700
10703
Data High, parameter ID702
10704
Data Low, parameter ID702
Address
Description
40011 High data
40012 Low data
Holds the counter value as seconds.