PROFIdrive Parameter Access errors
In addition to the error indications in the error response field, details about the error are provided
in the parameter value field. The third octet in the parameter value is set to 0x00 and the fourth octet
is assigned the error number, as described in Table 86.
Table 86. PROFIdrive parameter access errors
Error number Meaning
When used
0x00
Impermissible parameter
number
Access to unavailable parameter.
0x01
Parameter value cannot be
changed
Change request to a read-only parameter.
0x02
0x0 = invalid index
0xB0 = parameter requests are not supported.
0x03
Invalid subindex
Access to an unavailable subindex of an array pa-
rameter.
0x04
Non-array parameter
Attempt to access subindex of a non-array parame-
ter.
0x05
Incorrect data type
Change request containing invalid data type for the
accessed parameter.
0x06
Setting not permitted (may
only be reset)
Change request to a non-zero value, where this is
not allowed.
0x07
Description element cannot
be changed
Change request to a read-only parameter descrip-
tion element.
0x08
Reserved (not used)
0x09
No description data avail-
able
Access to unavailable parameter description.
0x0A
Reserved (not used)
0x0B
No operation priority
Change request without access rights to perform
the change.
0x0C...0x0E
Reserved (not used)
0x0F
No text array available
Access to unavailable parameter text array.
0x10
Reserved (not used)
0x11
Request cannot be executed
Access is temporarily not possible due to unspeci-
fied reasons.
0x12...0x13
Reserved (not used)
0x14
Value impermissible
Change request with a value within the allowed
range, but is otherwise not permissible.
0x15
Response too long
The length of the respose exceeds the maximum
transmittable length.
0x16
Impermissible parameter
address
Error in the parameter address field.
0x17
Illegal format
Illegal format was provided in write request.
0x18
Number of values are not
consistent
The number of values in the write request does not
match the number of values in the parameter.
0x19
Axis non-existent
Access to non-existent axis number