Commissioning
vacon • 35
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
More information on the safety relay module may be found in the safety relay documentation.
NOTE!
According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-
setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart
the drive.
NOTE!
The VACON
®
100 default application software uses edge-sensitive start as a default start
command. With the edge-sensitive start command, disactivating the STO does not cause immediate
start.
NOTE!
For EN 60204-1 emergency stop according to stop category1, use emergency stop button.