vacon • 26
STO AND SS1 SAFETY FUNCTIONS
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3.4.3
Example 3: OPTAF board with external safety relay module with or
without reset for Safe Torque Off (STO) or EN 60204-1 stop category 0
Figure 10. Example 3.
Figure 10 presents a connection example of OPTAF board for STO safety function with external
safety relay module and without reset.
External safety relay module is connected to the switch S1. The used power supply to switch S1 is
230 VAC as an example. The safety relay module is connected to OPTAF board with 4 wires as shown
in Figure 10.
When the switch S1 is activated (contacts open), the drive will go to STO state and motor (if running)
will stop by coasting. The drive will indicate: "A30 SafeTorqueOff".
When switch S1 is released (contacts closed), the drive returns to the ready state. The motor can
then be run with a valid start command.
The external relay can be wired so that manual reset is required to reset the STO safety function.
More information regarding the safety relay module may be found from the safety relay documen-
tation.
NOTE! For EN 60204-1 emergency stop according to stop category 0, use emergency stop button.
* Switch S1 in the figure can be replaced with the gate switch, then only Safe torque off mode is required. In
normal operation, both contacts are closed.
F1
1
2
3
4
5
6
L1
L2
MAIN CIRCUIT
L3
L1
L2
L3
U
V
W
PE
X10
2
7
W1
M1
M
3
~
U1
1
V1
W1
2
PE
R1
SPEED REFERENCE
S
CCW
CW
W12
1r
2p
2s
1sh
2sh
OPTA1
Basic I/O
SLOT A
1
+10Vref
1
2
AIA1+
2
3
AIA1
3
X2
OPTAF
SLOT B
1
SD1+
2
SD1
S6
START
13
14
4
AIA2+
4
5
AIA2
5
6
+24V
6
7
GND
7
3
SD2+
4
SD2
21
RO1 NC
22
RO1 C
CONTROL UNIT
S7
STOP
11
12
8
DIN1
8
9
DIN2
9
10
DIN3
10
11
CMA
11
X1
A B
23
RO1 N O
C D
X2
25
RO2 C
A B C D
26
RO2 NO
X3
B
A
28
TI1+
12
+24V
12
13
GND
13
14
DIN4
14
15
D IN5
15
X10
X6
A B
29
TI1
C D
16
DIN 6
16
17
CMB
17
18
AOA1+
18
19
AOA1
19
20
DOA1
20
START
res et
STO P
Vacon
+
s elect
enter
9
13
14
23
24
230Vac
L1
N
S1
11
12
21
22
SafeDisable
A10
K3.1
K1
K1.2
K3.2
K2
K2.2
K 1.1
K 2.1
K3
S23
T22
A1
A2
X2
T11
T12
26
27
28
29
W1
1
2
OFF
DOLD BN5930.48/204230VAC
EXAMPLE:
+24V
0V
31
33
S2
11
12
32
34
Alternative : Gate Switch *
Open
Shortcircuit and
earth fault
protected supply
Shortcircuit and
earth fault protected supply
For automatic reset
link X2 and T22
(Not allowed with Emergency stop)
PE
PE
PE
W3
2r
1r
ON
PE
PE
PE
PE
PE
PE
PE
PE
PE
S3
13
14
11059.emf
Summary of Contents for OPTAF
Page 1: ...vacon nx ac drives optaf sto and atex option board user manual ...
Page 2: ......
Page 8: ...vacon 6 GENERAL Local contacts https www danfoss com en contact us contacts list ...
Page 9: ...GENERAL vacon 7 Local contacts https www danfoss com en contact us contacts list ...
Page 10: ...vacon 8 GENERAL Local contacts https www danfoss com en contact us contacts list ...
Page 11: ...GENERAL vacon 9 Local contacts https www danfoss com en contact us contacts list ...
Page 12: ...vacon 10 GENERAL Local contacts https www danfoss com en contact us contacts list ...